Maintenance and Inspections
11-1 Operating Instructions
When executing the servicing and maintenance, please observe the following instructions because false or careless operations may result in personnel injury and equipment damage.
- Be sure to disconnect the PLC input power when it is required to be in contact with any terminal or to insert or remove the parts (e.g., expanding the harness, etc.) of the PLC during the maintenance process. If the aforesaid work is conducted under an energizing status, then it may result in electrocution, short circuit, PLC damage or even false action of the PLC. In this case, do not touch the terminal to prevent the terminal from oxidizing or personnel from electrocution.
- Before supplying power, please remove the impurities such as wire chips and screws.
- Do not apply heavy load on the cable or drag or clamp the cable by force to avoid cable damage or terminal loosening and electrocution.
- Confirm that the input power is identical with the type of power supplied to the PLC. If using AC as the input power, connect the live wire (L) to the “L” terminal and connect the neutral wire (N) to the “N” terminal of the PLC, respectively. If falsely connected to the input power to the PLC supplied with DC power or to any terminal other than the “L” and “N”, then it will cause the electrocution and serious damage of the PLC or other equipment.
- Confirm that the SINK/SOURCE polarity of the DC24V input end and the transistor output end are identical with the polarity of your wires. Incorrect wiring will lead to invalid PLC input and output circuit damage.
- The M series itself has no parts that can be maintained by ordinary users. Any repairs must be performed by professionals. During use, if there is any hardware failure, please contact the local dealer first to determine the problem. , Do not attempt to disassemble, modify or repair the product or it may lead to function failure, fire or even personnel injury.
- Do not install the M-Series PLC Module in the environment exposing it to direct sunlight or humidity.
- Confirm that the M-Series PLC Module is located at an appropriate distance from the heat source such as coil, heater or resistor to prevent the component temperature from rising.
- Please set up emergency power disconnection system and over-current protection device according to actual needs in order to protect the M-Series PLC Module.
- During the operations and maintenance process, please confirm the stability of the installation results to avoid unexpected vibrations as to cause damage to the M-Series PLC Module and the controlled component.
- After replacing the CPU module, confirm that all programs and parameters are logged into the new CPU module and that the setting is duly completed. After that, restart the M-Series PLC Module to prevent the controlled component from performing false action.
- The M-Series can disable all of the input or output points one by one or in a total manner. In other words, although the PLC has completed the program operations scanning and the I/O updating, but it does not update the status of the disabled input point according to the actual external input results; likewise, it does not transmit the computed output results for the disabled output point. Instead, it allows the user to set up the status of such input or outpoint point compulsorily in order to simulate its action. By using the disable function with the monitoring function, it allows the user to execute the simulation for the input or output point through the UperLogic and then check the computation results. After confirming that the simulation results are correct, the user will be allowed to enable all of the input or output points and the module will operate normally once again.
|
Warning |
|
|
The disable function resembles a program control that can be used to disable any PLC input or output point and then deliver the result to the user (the tester) for setting such disable input or output point as “ON” or “OFF” through the compulsory setting method as desired. When the PLC is under normal running status, the user must confirm whether or not the safety-related input or output point (e.g., upper/lower limit detecting input or emergency stop output, etc.) is available for disable or compulsory ON/OFF. After that, the user shall be allowed to execute the disable or the compulsory ON/OFF control to avoid machinery equipment damage or personnel injury. |
|
|
Avertissement |
|
|
La fonction de désactivation s’apparente à un contrôle de programme qui peut être utilisée pour désactiver tout point d’entrée ou de sortie du PLC, puis transmettre le résultat à l’utilisateur (testeur) afin de définir ce point désactivé en position « ON » ou « OFF » par la méthode de réglage forcé, selon le besoin. Lorsque le PLC est en état de fonctionnement normal, l’utilisateur doit confirmer si les points d’entrée ou de sortie liés à la sécurité (par exemple les entrées de détection de limite supérieure/inférieure ou les sorties d’arrêt d’urgence, etc.) peuvent être désactivés ou forcés en ON/OFF. Ce n’est qu’après cette vérification que l’utilisateur est autorisé à exécuter la commande de désactivation ou de forçage ON/OFF, afin d’éviter tout dommage aux équipements ou toute blessure corporelle. |
|
11-2 Daily Maintenance
To maintain the M-Series PLC Module at normal operating conditions, please check if the ambient environment and M-Series PLC Module comply with the precautions specified in Section 11.1 and then execute the daily inspection according to the items listed below. When detecting any abnormal situations, take maintenance action immediately according to the specified solutions.
11-2-1 Daily maintenance items
1. Appearance inspection:
Check if the appearance is presenting any dirt contamination signs. If seriously contaminated by dust, wipe with a clean cotton rag to improve the heat dissipating results while preventing the dust from falling into the board as to cause short circuit risks.
2. Check if the module is securely fixed:
Touch the module by the hand to check if any loosening sign existed between modules. If the module is equipped with a fixed-type DIN guide rail, check if the bottom-side installation latch-hook is properly connected with the fixed-type DIN guide rail. If not securely fixed, it may affect the operating function.
3. Wire connection status:
Pull the cable lightly by the hand to check if it is loosening. If the cable is loose, it may produce sparks and operate incorrectly.
4. Power module lamp:
Check if the POWER lamp is under “ON” status. If the POWER lamp is under “OFF” status but the power is supplied normally, please refer to the solutions specified in the “Troubleshooting” section of this Manual.
5. CPU module lamp:
Normal indicator shall be displayed as POWER lamp “ON” and “RUN” lamp flickering status. If connected with the RS485 communication equipment, the P01 or P02 will be under “ON” status. If the lamp is other than the aforesaid status or when the ERR red lamp is under “ON” status, please refer to the solutions specified in the “Troubleshooting” section of this Manual.
11-3 Regular Maintenance
When executing the scheduled daily inspection, it will also be required to conduct the scheduled regular maintenance according to the actual operating environment. After confirming that the ambient environment and the M-Series PLC Module comply with the precautions specified in Section 11.1, please start the regular inspection according to the items listed below. When detecting any abnormal situations, take maintenance action immediately according to the specified solutions.
11-3-1 Regular maintenance items
|
No. |
Inspection item |
Content |
Judgment standard |
Solutions |
|
|
1 |
Ambient temperature |
Environmental temperature / humidity |
Measured with temperature gauge and humidity gauge |
To meet the specifications established for each module. If different specifications are existing, then the most stringent standard shall prevail. |
Confirm the cause of the environment variation and then solve the problem so that the system may operate under a stabilized environment. |
|
Air |
Measure the corrosive gas |
Without corrosive gas |
|||
|
2 |
Power voltage |
Measure the input AC or DC power |
To meet the power module related specifications. |
Confirm the power supply system. |
|
|
3 |
Installation |
Correctly installed |
Check if the module is properly installed |
Refer to “Chapter 10: Correct installation of module” |
Check if the modules are fixed securely with each other and if the side buckle/Side Slider are also at the correct position. |
|
Contaminated by dust and dirt |
Check the appearance |
Without dust or dirt. |
Remove dust or dirt |
||
|
4 |
Connection |
Connecting terminal board is loose. |
Confirm by inserting and removing the connection terminal board. |
Securely connected without loosening. |
The terminal board latch should be installed securely. |
|
5 |
PLC System diagnosis |
Check the error record |
There’s no other error. |
Follow the error code displayed by the software, find the manual and try to troubleshoot the error |
|
|
6 |
Max. scanning time |
Confirm the status of the R35370 and R35371 through UperLogic status monitoring page. |
The max. scanning time must be within the scope allowed by the system specifications. |
Confirm the reasons causing the delay of scanning time. |
|
Details of Regular Mainteinance