14-1 Control Word
Use the control word to read and write the register of parameters or monitor the status.

Type and Range
|
Range Parameters |
HR |
ROR |
DR |
|
R0 |
R43224 |
D0 | D7999 |
|
|
Control Word |
O |
O |
O |
Control Word
|
Value |
Function |
|
0 |
Wait Operation |
|
1 |
In Action |
|
2 |
Read Settings |
|
3 |
Write Settings |
|
4 |
Error |
14-2 Plug-in
14-2-1 MB-2ADL
|
Setting Item |
Register Value |
Function |
Word Type |
WORD Usage |
|
A/D Conversion Setting |
||||
|
A/D Channel Enable/Disable |
0 |
Enable |
BIT |
– |
|
1 |
Disable |
|||
|
A/D Conversion Method Enable/Disable |
0 |
Enable |
BIT |
– |
|
1 |
Disable |
|||
|
A/D Conversion Method |
0 |
No Average |
WORD |
1 |
|
1 |
Count Average |
|||
|
A/D Conversion Method Set Value |
0 |
2 Times |
BIT |
– |
|
1 |
4 Times |
|||
|
Input Signal Range Setting |
||||
|
Input Signal Range |
0 |
0~10V(0~20mA) |
WORD |
1 |
|
Alert Output Setting |
||||
|
Alert Output Enable/Disable |
1 |
Enable |
BIT |
– |
|
0 |
Disable |
|||
|
Upper Upper Limit Value |
0~4095 |
WORD |
1 |
|
|
Upper Lower Limit Value |
0~4095 |
WORD |
1 |
|
|
Lower Upper Limit Value |
0~4095 |
WORD |
1 |
|
|
Lower Lower Limit Value |
0~4095 |
WORD |
1 |
|
|
Alarm Mode Setting |
||||
|
Alarm: Alert Output (Upper Limit) |
1 |
Latch Mode |
BIT |
– |
|
0 |
Momentary Mode |
|||
|
Alarm: Alert Output (Lower Limit) |
1 |
Latch Mode |
BIT |
– |
|
0 |
Momentary Mode |
|||
14-2-2 MB-2DAL
|
Setting Item |
Register Value |
Function |
Word Type |
Word Usage |
|
D/A Conversion Setting |
||||
|
D/A Channel Enable/Disable |
1 |
Enable |
BIT |
– |
|
0 |
Disable |
|||
|
Output Signal Range Setting |
||||
|
Output Signal Range |
0 |
0~5V (0~10mA) |
WORD |
1 |
|
1 |
0~10V(0~20mA) |
|||
14-3 Local I/O Expansion Modules
14-3-1 DIO
Registers Settings Table
|
Setting Item |
Register Value |
Function |
Word Type |
WORD Usage |
|
Input Filter Setting |
||||
|
Input Filter Value |
0 |
No Filter |
WORD |
1 |
|
1 |
0.5ms |
|||
|
2 |
1ms |
|||
|
3 |
5ms |
|||
|
4 |
10ms |
|||
|
5 |
20ms |
|||
|
6 |
70ms |
|||
14-3-2 M04AD(S)(R)
Registers Settings Table
|
Setting Item |
Register Value |
Function |
Word Type |
WORD Usage |
|
A/D Conversion Setting |
||||
|
A/D Channel Enable/Disable |
0 |
Enable |
BIT |
– |
|
1 |
Disable |
|||
|
A/D Conversion Method |
0 |
No Average |
WORD |
1 |
|
1 |
Count Average |
|||
|
2 |
Time Average |
|||
|
3 |
Moving Average |
|||
|
A/D Conversion Method Set Value |
2~1000 |
Count Average |
WORD |
2 |
|
1~1604000 |
Time Average |
|||
|
2~1000 |
Moving Average |
|||
|
A/D Conversion Time *M04ADS Not Support High Speed |
0 |
High Speed |
WORD |
1 |
|
1 |
Middle Speed |
|||
|
2 |
Slow Speed |
|||
|
3 |
50Hz |
|||
|
4 |
60Hz |
|||
|
Input Signal Range Setting |
||||
|
Input Signal Range |
0 |
0~5V |
WORD |
1 |
|
1 |
0~10V |
|||
|
2 |
-5~5V |
|||
|
3 |
-10~10V |
|||
|
4 |
1~5V |
|||
|
5 |
4~20mA |
|||
|
6 |
0~20mA |
|||
|
7 |
-20~20mA |
|||
|
Scaling Setting |
||||
|
Scaling Enable/Disable |
1 |
Enable |
BIT |
– |
|
0 |
Disable |
|||
|
Upper Limit Value |
-32768~32767 |
M04AD |
WORD |
2 |
|
-65536~65535 |
M04ADS |
|||
|
-131072~131071 |
M04ADR |
|||
|
Lower Limit Value |
-32768~32767 |
M04AD |
WORD |
2 |
|
-65536~65535 |
M04ADS |
|||
|
-131072~131071 |
M04ADR |
|||
|
Setting Item |
Register Value |
Function |
Word Type |
WORD Usage |
|
Data Offset Setting |
||||
|
Data Offset Enable/Disable |
1 |
Enable |
BIT |
– |
|
0 |
Disable |
|||
|
Data Offset Value |
-32768~32767 |
M04AD |
WORD |
1 |
|
-65536~65535 |
M04ADS |
|||
|
-131072~131071 |
M04ADR |
|||
|
Digital Clip Setting |
||||
|
Digital Clip Setting Enable/Disable *OnlyforM04ADR |
1 |
Enable |
BIT |
– |
|
0 |
Disable |
|||
|
Overflow Underflow Setting |
||||
|
Overflow Underflow Enable/Disable |
1 |
Enable |
BIT |
– |
|
0 |
Disable |
|||
|
Alert Output Setting |
||||
|
Alert Output Enable/Disable |
1 |
Enable |
BIT |
– |
|
0 |
Disable |
|||
|
Upper Upper Limit Value(2) |
-32768~32767 |
M04AD |
WORD |
2 |
|
-65536~65535 |
M04ADS |
|||
|
-131072~131071 |
M04ADR |
|||
|
Upper Lower Limit Value (2) |
-32768~32767 |
M04AD |
WORD |
2 |
|
-65536~65535 |
M04ADS |
|||
|
-131072~131071 |
M04ADR |
|||
|
Lower Upper Limit Value(2) |
-32768~32767 |
M04AD |
WORD |
2 |
|
-65536~65535 |
M04ADS |
|||
|
-131072~131071 |
M04ADR |
|||
|
Lower Lower Limit Value (2) |
-32768~32767 |
M04AD |
WORD |
2 |
|
-65536~65535 |
M04ADS |
|||
|
-131072~131071 |
M04ADR |
|||
|
Burnout Detection Setting |
||||
|
Burnout Detection Enable/Disable |
1 |
Enable |
BIT |
– |
|
0 |
Disable |
|||
|
Burnout Detection Output |
0 |
High Scale |
WORD |
1 |
|
1 |
Down Scale |
|||
|
Setting Item |
Register Value |
Function |
Word Type |
WORD Usage |
|
Alarm Mode Setting |
||||
|
Alarm: Overflow |
1 |
Latch Mode |
BIT |
– |
|
0 |
Momentary Mode |
|||
|
Alarm: Underflow |
1 |
Latch Mode |
BIT |
– |
|
0 |
Momentary Mode |
|||
|
Alarm: Alert Output(Upper Limit) |
1 |
Latch Mode |
BIT |
– |
|
0 |
Momentary Mode |
|||
|
Alarm: Alert Output (Lower Limit) |
1 |
Latch Mode |
BIT |
– |
|
0 |
Momentary Mode |
|||
|
Alarm: Burnout Detection |
1 |
Latch Mode |
BIT |
– |
|
0 |
Momentary Mode |
|||
|
Max, Min Hold Setting |
||||
|
Max, Min Hold Setting Enable/Disable |
1 |
Enable |
BIT |
– |
|
0 |
Disable |
|||
|
Data Buffer Setting |
||||
|
Data Buffer Setting Points |
1~600 |
WORD |
1 |
|
|
Data Buffer Setting Points Before Trigger |
0~599 |
WORD |
1 |
|
14-3-3 M08ADS
Registers Settings Table
|
Setting Item |
Register Value |
Function |
Word Type |
WORD Usage |
|
A/D Conversion Setting |
||||
|
A/D Channel Enable/Disable |
1 |
Enable |
BIT |
– |
|
0 |
Disable |
|||
|
A/D Conversion Method |
0 |
No Average |
WORD |
1 |
|
1 |
Count Average |
|||
|
2 |
Time Average |
|||
|
3 |
Moving Average |
|||
|
A/D Conversion Method Set Value |
2~1000 |
Count Average |
WORD |
2 |
|
1~1604000 |
Time Average |
|||
|
2~1000 |
Moving Average |
|||
|
A/D Conversion Time |
1 |
Middle Speed |
WORD |
1 |
|
2 |
Low Speed |
|||
|
3 |
50Hz |
|||
|
4 |
60Hz |
|||
|
Input Signal Range Setting |
||||
|
Input Signal Range |
0 |
0~5V |
WORD |
1 |
|
1 |
0~10V |
|||
|
2 |
-5~5V |
|||
|
3 |
-10~10V |
|||
|
4 |
1~5V |
|||
|
5 |
4~20mA |
|||
|
6 |
0~20mA |
|||
|
7 |
-20~20mA |
|||
|
Scaling Setting |
||||
|
Scaling Enable/Disable |
1 |
Enable |
BIT |
– |
|
0 |
Disable |
|||
|
Upper Limit Value |
-65536~65535 |
WORD |
2 |
|
|
Lower Limit Value |
-65536~65535 |
WORD |
2 |
|
|
Data Offset Setting |
||||
|
Data Offset Enable/Disable |
1 |
Enable |
BIT |
– |
|
0 |
Disable |
|||
|
Data Offset Value |
-65536~65535 |
WORD |
1 |
|
|
Overflow Underflow Setting |
||||
|
Overflow Underflow Enable/Disable |
1 |
Enable |
BIT |
– |
|
0 |
Disable |
|||
|
Setting Item |
Register Value |
Function |
Word Type |
WORD Usage |
|
Alert Output Setting |
||||
|
Alert Output Enable/Disable |
1 |
Enable |
BIT |
– |
|
0 |
Disable |
|||
|
Upper Upper Limit Value |
-65536~65535 |
WORD |
2 |
|
|
Upper Lower Limit Value |
-65536~65535 |
WORD |
2 |
|
|
Lower Upper Limit Value |
-65536~65535 |
WORD |
2 |
|
|
Lower Lower Limit Value |
-65536~65535 |
WORD |
2 |
|
|
Burnout Detection Setting |
||||
|
Burnout Detection Enable/Disable |
1 |
Enable |
BIT |
– |
|
0 |
Disable |
|||
|
Burnout Detection Output |
0 |
High Scale |
WORD |
1 |
|
1 |
Down Scale |
|||
|
Alarm Mode Setting |
||||
|
Alarm: Overflow |
1 |
Latch Mode |
BIT |
– |
|
0 |
Momentary Mode |
|||
|
Alarm: Underflow |
1 |
Latch Mode |
BIT |
– |
|
0 |
Momentary Mode |
|||
|
Alarm: Alert Output(Upper Limit) |
1 |
Latch Mode |
BIT |
– |
|
0 |
Momentary Mode |
|||
|
Alarm: Alert Output (Lower Limit) |
1 |
Latch Mode |
BIT |
– |
|
0 |
Momentary Mode |
|||
|
Alarm: Burnout Detection |
1 |
Latch Mode |
BIT |
– |
|
0 |
Momentary Mode |
|||
|
Max, Min Hold Setting |
||||
|
Max, Min Hold Setting Enable/Disable |
1 |
Enable |
BIT |
– |
|
Disable |
||||
14-3-4 M04DA(R)
Registers Settings Table
|
Setting Item |
Register Value |
Function |
Word Type |
Word Usage |
|
D/A Conversion Setting |
||||
|
D/A Channel Enable/Disable |
1 |
Enable |
BIT |
– |
|
0 |
Disable |
|||
|
Output Signal Range Setting |
||||
|
Output Signal Range |
0 |
0~5V |
WORD |
1 |
|
1 |
0~10V |
|||
|
2 |
-5~5V |
|||
|
3 |
-10~10V |
|||
|
4 |
1~5V |
|||
|
5 |
4~20mA |
|||
|
6 |
0~20mA |
|||
|
Output Hold Function |
||||
|
Output Hold Enable/Disable |
1 |
Enable |
BIT |
– |
|
0 |
Disable |
|||
|
Output Hold Setting |
0 |
Clear |
WORD |
1 |
|
1 |
Hold |
|||
|
2 |
User-Define Value |
|||
|
User-Defined Value |
0~60000 |
M04DAR |
WORD |
2 |
|
0~16383 |
M04DA |
|||
|
Slew Rate Setting |
||||
|
Slew Rate Enable/Disable |
1 |
Enable |
BIT |
– |
|
0 |
Disable |
|||
|
Slew Rate (steps/sec) |
4 |
Slew Rate 500 |
WORD |
2 |
|
5 |
Slew Rate 1000 |
|||
|
6 |
Slew Rate 2000 |
|||
|
7 |
Slew Rate 4000 |
|||
|
8 |
Slew Rate 8000 |
|||
|
9 |
Slew Rate 16000 |
|||
|
10 |
Slew Rate 32000 |
|||
|
11 |
Slew Rate 64000 |
|||
|
12 |
Slew Rate 128000 |
|||
|
13 |
Slew Rate 256000 |
|||
|
14 |
Slew Rate 512000 |
|||
|
15 |
Slew Rate 1024000 |
|||
|
Setting Item |
Register Value |
Function |
Word Type |
Word Usage |
|
Scaling Setting |
||||
|
Scaling Enable/Disable |
1 |
Enable |
BIT |
– |
|
0 |
Disable |
|||
|
Upper Limit Value |
-30000~30000 |
WORD |
2 |
|
|
Lower Limit Value |
-30000~30000 |
WORD |
2 |
|
|
Data Offset Setting |
||||
|
Data Offset Enable/Disable |
1 |
Enable |
BIT |
– |
|
0 |
Disable |
|||
|
Data Offset Value |
-2000~2000 |
WORD |
2 |
|
|
Alarm Mode Setting |
||||
|
Alarm:Short Circuit |
1 |
Latch Mode |
BIT |
– |
|
0 |
Momentary Mode |
|||
|
Alarm: Open Circuit |
1 |
Latch Mode |
BIT |
– |
|
0 |
Momentary Mode |
|||
|
Alarm: LED Display Mask |
1 |
Enable |
BIT |
– |
|
0 |
Disable |
|||
14-3-5 M0202AH (A/D)
Registers Settings Table
|
Setting Item |
Register Value |
Function |
Word Type |
Word Usage |
|
A/D Conversion Setting |
||||
|
A/D Channel Enable/Disable |
1 |
Enable |
BIT |
– |
|
0 |
Disable |
|||
|
A/D Conversion Method |
0 |
No Average |
WORD |
1 |
|
1 |
Count Average |
|||
|
2 |
Time Average |
|||
|
3 |
Moving Average |
|||
|
A/D Conversion Method Set Value |
2~1000 |
Count Average |
WORD |
2 |
|
1~1604000 |
Time Average |
|||
|
2~1000 |
Moving Average |
|||
|
A/D Conversion Time |
0 |
High Speed |
WORD |
1 |
|
1 |
Middle Speed |
|||
|
2 |
Low Speed |
|||
|
3 |
50Hz |
|||
|
4 |
60Hz |
|||
|
Input Signal Range Setting |
||||
|
Input Signal Range |
0 |
0~5V |
WORD |
1 |
|
1 |
0~10V |
|||
|
2 |
-5~5V |
|||
|
3 |
-10~10V |
|||
|
4 |
1~5V |
|||
|
5 |
4~20mA |
|||
|
6 |
0~20mA |
|||
|
7 |
-20~20mA |
|||
|
Scaling Setting |
||||
|
Scaling Enable/Disable |
1 |
Enable |
BIT |
– |
|
0 |
Disable |
|||
|
Upper Limit Value |
-30000~30000 |
WORD |
2 |
|
|
Lower Limit Value |
-30000~30000 |
WORD |
2 |
|
|
Data Offset Setting |
||||
|
Data Offset Enable/Disable |
1 |
Enable |
BIT |
– |
|
0 |
Disable |
|||
|
Data Offset Value |
-2000~2000 |
WORD |
1 |
|
|
Setting Item |
Register Value |
Function |
Word Type |
Word Usage |
|
Overflow Underflow Setting |
||||
|
Overflow Underflow Enable/Disable |
1 |
Enable |
BIT |
– |
|
0 |
Disable |
|||
|
Alert Output Setting |
||||
|
Alert Output Enable/Disable |
1 |
Enable |
BIT |
– |
|
0 |
Disable |
|||
|
Upper Upper Limit Value |
-32000~32000 |
WORD |
2 |
|
|
Upper Lower Limit Value |
-32000~32000 |
WORD |
2 |
|
|
Lower Upper Limit Value |
-32000~32000 |
WORD |
2 |
|
|
Lower Lower Limit Value |
-32000~32000 |
WORD |
2 |
|
|
Burnout Detection Setting |
||||
|
Burnout Detection Enable/Disable |
1 |
Enable |
BIT |
– |
|
0 |
Disable |
|||
|
Burnout Detection Output |
0 |
High Scale |
WORD |
1 |
|
1 |
Down Scale |
|||
|
Alarm Mode Setting |
||||
|
Alarm: Overflow |
1 |
Latch Mode |
BIT |
– |
|
0 |
Momentary Mode |
|||
|
Alarm: Underflow |
1 |
Latch Mode |
BIT |
– |
|
0 |
Momentary Mode |
|||
|
Alarm: Alert Output(Upper Limit) |
1 |
Latch Mode |
BIT |
– |
|
0 |
Momentary Mode |
|||
|
Alarm: Alert Output (Lower Limit) |
1 |
Latch Mode |
BIT |
– |
|
0 |
Momentary Mode |
|||
|
Alarm: Burnout Detection |
1 |
Latch Mode |
BIT |
– |
|
0 |
Momentary Mode |
|||
|
Max, Min Hold Setting |
||||
|
Max, Min Hold Enable/Disable |
1 |
Enable |
BIT |
– |
|
0 |
Disable |
|||
|
Data Buffer Setting |
||||
|
Data Buffer Points |
1~600 |
WORD |
1 |
|
|
Data Buffer Points Before Trigger |
0~599 |
WORD |
1 |
|
14-3-6 M0202AH (D/A)
Registers Settings Table
|
Setting Item |
Register Value |
Function |
Word Type |
Word Usage |
|
|
D/A Conversion Setting |
|||||
|
D/A Channel Enable/Disable |
1 |
Enable |
BIT |
– |
|
|
0 |
Disable |
||||
|
Output Signal Range Setting |
|||||
|
Output Signal Range |
0 |
0~5V |
WORD |
1 |
|
|
1 |
0~10V |
||||
|
2 |
-5~5V |
||||
|
3 |
-10~10V |
||||
|
4 |
1~5V |
||||
|
5 |
4~20mA |
||||
|
6 |
0~20mA |
||||
|
Output Hold Function |
|||||
|
Output Hold Enable/Disable |
1 |
Enable |
BIT |
– |
|
|
0 |
Disable |
||||
|
Output Hold Setting |
0 |
Clear |
WORD |
1 |
|
|
1 |
Hold |
||||
|
2 |
User-Define Value |
||||
|
User-Defined Value |
0~16383 |
WORD |
2 |
||
|
Slew Rate Setting |
|||||
|
Slew Rate Enable/Disable |
1 |
Enable |
BIT |
– |
|
|
0 |
Disable |
||||
|
Slew Rate (steps/sec) |
4 |
Slew Rate 500 |
WORD |
2 |
|
|
5 |
Slew Rate 1000 |
||||
|
6 |
Slew Rate 2000 |
||||
|
7 |
Slew Rate 4000 |
||||
|
8 |
Slew Rate 8000 |
||||
|
9 |
Slew Rate 16000 |
||||
|
10 |
Slew Rate 32000 |
||||
|
11 |
Slew Rate 64000 |
||||
|
12 |
Slew Rate 128000 |
||||
|
13 |
Slew Rate 256000 |
||||
|
14 |
Slew Rate 512000 |
||||
|
15 |
Slew Rate 1024000 |
||||
|
Scaling Setting |
|||||
|
Scaling Enable/Disable |
1 |
Enable |
BIT |
– |
|
|
0 |
Disable |
||||
|
Upper Limit Value |
-30000~30000 |
WORD |
2 |
||
|
Lower Limit Value |
-30000~30000 |
WORD |
2 |
||
|
Data Offset Setting |
|||||
|
Data Offset Enable/Disable |
1 |
Enable |
BIT |
– |
|
|
0 |
Disable |
||||
|
Data Offset Value |
-2000~2000 |
WORD |
2 |
||
|
Alarm Mode Setting |
|||||
|
Alarm: Short Circuit |
1 |
Latch Mode |
BIT |
– |
|
|
0 |
Momentary Mode |
||||
|
Alarm: Open Circuit |
1 |
Latch Mode |
BIT |
– |
|
|
0 |
Momentary Mode |
||||
|
Alarm: LED Display Mask |
1 |
Enable |
BIT |
– |
|
|
0 |
Disable |
||||
14-3-7 M04RTD
Registers Settings Table
|
Setting Item |
Register Value |
Function |
Word Type |
Word Usage |
|
RTD Setting |
||||
|
D/A Channel Enable/Disable |
1 |
Enable |
BIT |
– |
|
0 |
Disable |
|||
|
Moving Average Count |
1~10 |
WORD |
1 |
|
|
Sensor Setting |
||||
|
Sensor Type |
0 |
Pt100 |
WORD |
1 |
|
1 |
JPt100 |
|||
|
2 |
Pt1000 |
|||
|
3 |
JPt1000 |
|||
|
Sensor Range |
0 |
RANGE1 |
WORD |
1 |
|
Function Setting |
||||
|
Temperature Unit |
1 |
℃ |
BIT |
– |
|
0 |
℉ |
|||
|
Control Method |
0 |
ON/OFF control |
BIT |
– |
|
1 |
PID control |
|||
|
Control Output |
0 |
OFF |
WORD |
1 |
|
1 |
ON |
|||
|
2 |
HOLD |
|||
|
Post Processing Setting |
||||
|
Scaling Enable/Disable |
1 |
Enable |
BIT |
– |
|
0 |
Disable |
|||
|
Maximum Scaled Value |
-32000~32000 |
WORD |
1 |
|
|
Minimum Scaled Value |
-32000~32000 |
WORD |
1 |
|
|
Data Buffer Setting |
||||
|
Data Buffer Setting Points |
1~600 |
WORD |
1 |
|
|
Data Buffer Setting Points Before Trigger |
0~600 |
WORD |
1 |
|
|
Setting Item |
Register Value |
Function |
Word Type |
Word Usage |
|
Alert Setting |
||||
|
Alert Standby Mode Enable/Disable |
1 |
Enable |
BIT |
– |
|
0 |
Disable |
|||
|
Upper Limit Input Value |
-200~850 |
WORD |
2 |
|
|
Lower Limit Input Value |
-200~850 |
WORD |
2 |
|
|
Upper Limit Deviation Value |
-1050~1050 |
WORD |
2 |
|
|
Lower Limit Deviation Value |
-1050~1050 |
WORD |
2 |
|
|
Upper Lower Limit Deviation Value |
0~1050 |
WORD |
2 |
|
|
Dead Band Alert |
0~10 |
WORD |
1 |
|
|
Number Of Alert delay |
0~255 |
WORD |
1 |
|
|
Loop Disconnection Detection |
0~7200 |
WORD |
1 |
|
|
Loop Detection Dead Band |
0~1050 |
WORD |
2 |
|
14-3-8 M0202TH (RTD)
Registers Settings Table
|
Setting Item |
Register Value |
Function |
Word Type |
Word Usage |
|
RTD Setting |
||||
|
RTD Channel Enable/Disable |
1 |
Enable |
BIT |
– |
|
0 |
Disable |
|||
|
Moving Average Count |
1~10 |
WORD |
1 |
|
|
Sensor Setting |
||||
|
Sensor Type |
0 |
Pt100 |
WORD |
1 |
|
1 |
JPt100 |
|||
|
2 |
Pt1000 |
|||
|
3 |
JPt1000 |
|||
|
Sensor Range |
0 |
RANGE1 |
WORD |
1 |
|
Function Setting |
||||
|
Temperature Unit |
1 |
℃ |
BIT |
– |
|
0 |
℉ |
|||
|
Control Method |
0 |
ON/OFF control |
BIT |
– |
|
1 |
PID control |
|||
|
Control Output |
0 |
OFF |
WORD |
1 |
|
1 |
ON |
|||
|
2 |
HOLD |
|||
|
Post Processing Setting |
||||
|
Scaling Enable/Disable |
1 |
Enable |
BIT |
– |
|
0 |
Disable |
|||
|
Maximum Scaled Value |
-32000~32000 |
WORD |
1 |
|
|
Minimum Scaled Value |
||||
|
Data Buffer Setting |
||||
|
Data Buffer Setting Points |
1~600 |
WORD |
1 |
|
|
Data Buffer Setting Points Before Trigger |
0~600 |
WORD |
1 |
|
|
Alert Setting |
||||
|
Alert Standby Mode Enable/Disable |
1 |
Enable |
BIT |
– |
|
0 |
Disable |
|||
|
Upper Limit Input Value |
-200~850 |
WORD |
1 |
|
|
Lower Limit Input Value |
-200~850 |
WORD |
1 |
|
|
Upper Limit Deviation Value |
-1050~1050 |
WORD |
1 |
|
|
Lower Limit Deviation Value |
-1050~1050 |
WORD |
1 |
|
|
Upper Lower Limit Deviation Value |
0~1050 |
WORD |
1 |
|
|
Dead Band Alert |
0~10 |
WORD |
1 |
|
|
Number Of Alert delay |
0~255 |
WORD |
1 |
|
|
Loop Disconnection Detection |
0~7200 |
WORD |
1 |
|
|
Loop Detection Dead Band |
0~1050 |
WORD |
1 |
|
14-3-9 M0202TH (TC)
Registers Settings Table
|
Setting Item |
Register Value |
Function |
Word Type |
Word Usage |
|
TC Setting |
||||
|
TC Channel Enable/Disable |
1 |
Enable |
BIT |
– |
|
0 |
Disable |
|||
|
TC Conversation Time |
0 |
Standard |
WORD |
1 |
|
1 |
Fast |
|||
|
Moving Average Count |
1~10 |
WORD |
1 |
|
|
Sensor Setting |
||||
|
Sensor Type |
0 |
K |
WORD |
1 |
|
1 |
J |
|||
|
2 |
T |
|||
|
3 |
E |
|||
|
4 |
R |
|||
|
5 |
B |
|||
|
6 |
N |
|||
|
7 |
S |
|||
|
8 |
+-100mv |
|||
|
Sensor Range |
0 |
RANGE1 |
WORD |
1 |
|
Function Setting |
||||
|
Temperature Unit |
1 |
℃ |
BIT |
– |
|
0 |
℉ |
|||
|
Control Method |
0 |
ON/OFF control |
BIT |
– |
|
1 |
PID control |
|||
|
Control Output |
0 |
OFF |
WORD |
1 |
|
1 |
ON |
|||
|
2 |
HOLD |
|||
|
Post Processing Setting |
||||
|
Scaling Enable/Disable |
1 |
Enable |
BIT |
– |
|
0 |
Disable |
|||
|
Maximum Scaled Value |
-32000~32000 |
WORD |
1 |
|
|
Minimum Scaled Value |
||||
|
Data Buffer Setting |
||||
|
Data Buffer Setting Points |
1~600 |
WORD |
1 |
|
|
Data Buffer Setting Points Before Trigger |
0~600 |
WORD |
1 |
|
|
Alert Setting |
||||
|
Alert Standby Mode Enable/Disable |
1 |
Enable |
BIT |
– |
|
0 |
Disable |
|||
|
Upper Limit Input Value |
-200~1350 |
WORD |
2 |
|
|
Lower Limit Input Value |
-200~1350 |
WORD |
2 |
|
|
Upper Limit Deviation Value |
-1550~1550 |
WORD |
2 |
|
|
Lower Limit Deviation Value |
-1550~1550 |
WORD |
2 |
|
|
Upper Lower Limit Deviation Value |
0~1550 |
WORD |
2 |
|
|
Dead Band Alert |
0~10 |
WORD |
1 |
|
|
Number Of Alert delay |
0~255 |
WORD |
1 |
|
|
Loop Disconnection Detection |
0~7200 |
WORD |
1 |
|
|
Loop Detection Dead Band |
0~1550 |
WORD |
2 |
|
14-3-10 M02LC(R)
Registers Settings Table
|
Setting Item |
Register Value |
Function |
Word Type |
Word Usage |
||
|
LC Setting |
||||||
|
LC Channel Enable/Disable |
1 |
Enable |
BIT |
– |
||
|
0 |
Disable |
|||||
|
Weight Unit |
0 |
G |
WORD |
1 |
||
|
1 |
Kg |
|||||
|
2 |
T |
|||||
|
Decimal |
0 |
1 |
WORD |
1 |
||
|
1 |
0.1 |
|||||
|
2 |
0.01 |
|||||
|
3 |
0.001 |
|||||
|
Rated Capacity |
0~999999 |
WORD |
2 |
|||
|
Rated Output |
0 |
0~1mV/V |
WORD |
1 |
||
|
1 |
0~2mV/V |
|||||
|
2 |
0~3mV/V |
|||||
|
3 |
0~4mV/V |
|||||
|
Number Of LC In Connection |
1~4 |
WORD |
1 |
|||
|
Maximal Weight Capacity |
1~4 |
WORD |
2 |
|||
|
Minimal Division |
0 |
1 |
WORD |
1 |
||
|
1 |
2 |
|||||
|
2 |
5 |
|||||
|
3 |
10 |
|||||
|
4 |
20 |
|||||
|
5 |
50 |
|||||
|
Zero Point Range |
0~100 |
WORD |
1 |
|||
|
Weight Conversion Method |
0 |
Sampling |
WORD |
1 |
||
|
1 |
Count Average |
|||||
|
2 |
Moving Average |
|||||
|
Average Count |
4~255 |
Count Average |
WORD |
1 |
||
|
2~255 |
Moving Average |
|||||
|
Conversion Setting |
||||||
|
Conversion Method |
1 |
Auto Restoration |
BIT |
– |
||
|
0 |
Auto Stop |
|||||
|
Gravity Acceleration Setting |
||||||
|
Installation Site |
9.7~9.9999 |
WORD |
2 |
|||
|
Calibration Site |
9.7~9.9999 |
WORD |
2 |
|||
|
Zero Point Tracking Setting |
||||||
|
Zero Point Tracking Range |
0~100 |
WORD |
1 |
|||
|
Zero Point Tracking Time |
0~100 |
WORD |
1 |
|||
|
Input Signal Error Setting |
||||||
|
Input Signal Error Enable/Disable |
1 |
Enable |
BIT |
– |
||
|
0 |
Disable |
|||||
|
Input Signal Error |
0~25 |
WORD |
1 |
|||
|
Gross Weight Setting |
||||||
|
Warning Output Enable/Disable |
1 |
Enable |
BIT |
– |
||
|
0 |
Disable |
|||||
|
Upper Upper Limit Value |
-99999~99999 |
WORD |
2 |
|||
|
Upper Lower Limit Value |
-99999~99999 |
WORD |
2 |
|||
|
Lower Upper Limit Value |
-99999~99999 |
WORD |
2 |
|||
|
Lower Lower Limit Value |
-99999~99999 |
WORD |
2 |
|||
|
Center Point Detection Setting |
||||||
|
Center Point Detection Enable/Disable |
1 |
Enable |
BIT |
– |
||
|
0 |
Disable |
|||||
|
Stable Status Setting |
Disable |
|||||
|
Stable Status Range |
0~100 |
WORD |
1 |
|||
|
Stable Status Time |
0~100 |
WORD |
1 |
|||
|
Zero Point Detection Setting |
||||||
|
Zero Point Detection Enable/Disable |
1 |
Digital Value |
BIT |
– |
||
|
0 |
Gross Weight |
|||||
|
Zero Point Detection Maximum |
-2147483648~10000 |
WORD |
2 |
|||
|
Zero Point Detection Minimum |
-2147483648~10000 |
WORD |
2 |
|||
|
Data Buffer Setting |
||||||
|
Data Type |
1 |
Digital Value |
BIT |
– |
||
|
0 |
Gross Weight |
|||||
|
Data Buffer Points |
1~600 |
WORD |
1 |
|||
|
Data Buffer Points Before Trigger |
0~599 |
WORD |
1 |
|||
|
Tare Subtraction Setting |
||||||
|
Tare Subtraction Mode |
1 |
Digital |
BIT |
– |
||
|
0 |
One Touch |
|||||
Tip: press ← → to switch chapters, Ctrl+K to search