14-1 Control Word

Use the control word to read and write the register of parameters or monitor the status.

Type and Range

Range

Parameters

HR

ROR

DR

R0
|
R34767

R43224
|
R47319

D0

|

D7999

Control Word

O

O

O

Control Word

Value

Function

0

Wait Operation

1

In Action

2

Read Settings

3

Write Settings

4

Error

14-2 Plug-in

14-2-1 MB-2ADL

Setting Item

Register Value

Function

Word Type

WORD Usage

A/D Conversion Setting

A/D Channel Enable/Disable

0

Enable

BIT

–

1

Disable

A/D Conversion Method Enable/Disable

0

Enable

BIT

–

1

Disable

A/D Conversion Method

0

No Average

WORD

1

1

Count Average

A/D Conversion Method Set Value

0

2 Times

BIT

–

1

4 Times

Input Signal Range Setting

Input Signal Range

0

0~10V(0~20mA)

WORD

1

Alert Output Setting

Alert Output Enable/Disable

1

Enable

BIT

–

0

Disable

Upper Upper Limit Value

0~4095

WORD

1

Upper Lower Limit Value

0~4095

WORD

1

Lower Upper Limit Value

0~4095

WORD

1

Lower Lower Limit Value

0~4095

WORD

1

Alarm Mode Setting

Alarm: Alert Output (Upper Limit)

1

Latch Mode

BIT

–

0

Momentary Mode

Alarm: Alert Output (Lower Limit)

1

Latch Mode

BIT

–

0

Momentary Mode

14-2-2 MB-2DAL

Setting Item

Register Value

Function

Word Type

Word Usage

D/A Conversion Setting

D/A Channel Enable/Disable

1

Enable

BIT

–

0

Disable

Output Signal Range Setting

Output Signal Range

0

0~5V (0~10mA)

WORD

1

1

0~10V(0~20mA)

14-3 Local I/O Expansion Modules

14-3-1 DIO

Registers Settings Table

Setting Item

Register Value

Function

Word Type

WORD Usage

Input Filter Setting

Input Filter Value

0

No Filter

WORD

1

1

0.5ms

2

1ms

3

5ms

4

10ms

5

20ms

6

70ms

14-3-2 M04AD(S)(R)

Registers Settings Table

Setting Item

Register Value

Function

Word Type

WORD Usage

A/D Conversion Setting

A/D Channel Enable/Disable

0

Enable

BIT

–

1

Disable

A/D Conversion Method

0

No Average

WORD

1

1

Count Average

2

Time Average

3

Moving Average

A/D Conversion Method Set Value

2~1000

Count Average

WORD

2

1~1604000

Time Average

2~1000

Moving Average

A/D Conversion Time

*M04ADS Not Support High Speed

0

High Speed

WORD

1

1

Middle Speed

2

Slow Speed

3

50Hz

4

60Hz

Input Signal Range Setting

Input Signal Range

0

0~5V

WORD

1

1

0~10V

2

-5~5V

3

-10~10V

4

1~5V

5

4~20mA

6

0~20mA

7

-20~20mA

Scaling Setting

Scaling Enable/Disable

1

Enable

BIT

–

0

Disable

Upper Limit Value

-32768~32767

M04AD

WORD

2

-65536~65535

M04ADS

-131072~131071

M04ADR

Lower Limit Value

-32768~32767

M04AD

WORD

2

-65536~65535

M04ADS

-131072~131071

M04ADR

Setting Item

Register Value

Function

Word Type

WORD Usage

Data Offset Setting

Data Offset Enable/Disable

1

Enable

BIT

–

0

Disable

Data Offset Value

-32768~32767

M04AD

WORD

1

-65536~65535

M04ADS

-131072~131071

M04ADR

Digital Clip Setting

Digital Clip Setting Enable/Disable *OnlyforM04ADR

1

Enable

BIT

–

0

Disable

Overflow Underflow Setting

Overflow Underflow Enable/Disable

1

Enable

BIT

–

0

Disable

Alert Output Setting

Alert Output Enable/Disable

1

Enable

BIT

–

0

Disable

Upper Upper Limit Value(2)

-32768~32767

M04AD

WORD

2

-65536~65535

M04ADS

-131072~131071

M04ADR

Upper Lower Limit Value (2)

-32768~32767

M04AD

WORD

2

-65536~65535

M04ADS

-131072~131071

M04ADR

Lower Upper Limit Value(2)

-32768~32767

M04AD

WORD

2

-65536~65535

M04ADS

-131072~131071

M04ADR

Lower Lower Limit Value (2)

-32768~32767

M04AD

WORD

2

-65536~65535

M04ADS

-131072~131071

M04ADR

Burnout Detection Setting

Burnout Detection Enable/Disable

1

Enable

BIT

–

0

Disable

Burnout Detection Output

0

High Scale

WORD

1

1

Down Scale

Setting Item

Register Value

Function

Word Type

WORD Usage

Alarm Mode Setting

Alarm: Overflow

1

Latch Mode

BIT

–

0

Momentary

Mode

Alarm: Underflow

1

Latch Mode

BIT

–

0

Momentary

Mode

Alarm: Alert Output(Upper Limit)

1

Latch Mode

BIT

–

0

Momentary

Mode

Alarm: Alert Output (Lower Limit)

1

Latch Mode

BIT

–

0

Momentary

Mode

Alarm: Burnout Detection

1

Latch Mode

BIT

–

0

Momentary

Mode

Max, Min Hold Setting

Max, Min Hold Setting Enable/Disable

1

Enable

BIT

–

0

Disable

Data Buffer Setting

Data Buffer Setting Points

1~600

WORD

1

Data Buffer Setting Points Before Trigger

0~599

WORD

1

14-3-3 M08ADS

Registers Settings Table

Setting Item

Register Value

Function

Word Type

WORD Usage

A/D Conversion Setting

A/D Channel Enable/Disable

1

Enable

BIT

–

0

Disable

A/D Conversion Method

0

No Average

WORD

1

1

Count Average

2

Time Average

3

Moving Average

A/D Conversion Method Set Value

2~1000

Count Average

WORD

2

1~1604000

Time Average

2~1000

Moving Average

A/D Conversion Time

1

Middle Speed

WORD

1

2

Low Speed

3

50Hz

4

60Hz

Input Signal Range Setting

Input Signal Range

0

0~5V

WORD

1

1

0~10V

2

-5~5V

3

-10~10V

4

1~5V

5

4~20mA

6

0~20mA

7

-20~20mA

Scaling Setting

Scaling Enable/Disable

1

Enable

BIT

–

0

Disable

Upper Limit Value

-65536~65535

WORD

2

Lower Limit Value

-65536~65535

WORD

2

Data Offset Setting

Data Offset Enable/Disable

1

Enable

BIT

–

0

Disable

Data Offset Value

-65536~65535

WORD

1

Overflow Underflow Setting

Overflow Underflow Enable/Disable

1

Enable

BIT

–

0

Disable

Setting Item

Register Value

Function

Word Type

WORD Usage

Alert Output Setting

Alert Output Enable/Disable

1

Enable

BIT

–

0

Disable

Upper Upper Limit Value

-65536~65535

WORD

2

Upper Lower Limit Value

-65536~65535

WORD

2

Lower Upper Limit Value

-65536~65535

WORD

2

Lower Lower Limit Value

-65536~65535

WORD

2

Burnout Detection Setting

Burnout Detection Enable/Disable

1

Enable

BIT

–

0

Disable

Burnout Detection Output

0

High Scale

WORD

1

1

Down Scale

Alarm Mode Setting

Alarm: Overflow

1

Latch Mode

BIT

–

0

Momentary

Mode

Alarm: Underflow

1

Latch Mode

BIT

–

0

Momentary

Mode

Alarm: Alert Output(Upper Limit)

1

Latch Mode

BIT

–

0

Momentary

Mode

Alarm: Alert Output (Lower Limit)

1

Latch Mode

BIT

–

0

Momentary

Mode

Alarm: Burnout Detection

1

Latch Mode

BIT

–

0

Momentary

Mode

Max, Min Hold Setting

Max, Min Hold Setting Enable/Disable

1

Enable

BIT

–

Disable

14-3-4 M04DA(R)

Registers Settings Table

Setting Item

Register Value

Function

Word Type

Word Usage

D/A Conversion Setting

D/A Channel Enable/Disable

1

Enable

BIT

–

0

Disable

Output Signal Range Setting

Output Signal Range

0

0~5V

WORD

1

1

0~10V

2

-5~5V

3

-10~10V

4

1~5V

5

4~20mA

6

0~20mA

Output Hold Function

Output Hold Enable/Disable

1

Enable

BIT

–

0

Disable

Output Hold Setting

0

Clear

WORD

1

1

Hold

2

User-Define Value

User-Defined Value

0~60000

M04DAR

WORD

2

0~16383

M04DA

Slew Rate Setting

Slew Rate Enable/Disable

1

Enable

BIT

–

0

Disable

Slew Rate (steps/sec)

4

Slew Rate 500

WORD

2

5

Slew Rate 1000

6

Slew Rate 2000

7

Slew Rate 4000

8

Slew Rate 8000

9

Slew Rate 16000

10

Slew Rate 32000

11

Slew Rate 64000

12

Slew Rate 128000

13

Slew Rate 256000

14

Slew Rate 512000

15

Slew Rate 1024000

Setting Item

Register Value

Function

Word Type

Word Usage

Scaling Setting

Scaling Enable/Disable

1

Enable

BIT

–

0

Disable

Upper Limit Value

-30000~30000

WORD

2

Lower Limit Value

-30000~30000

WORD

2

Data Offset Setting

Data Offset Enable/Disable

1

Enable

BIT

–

0

Disable

Data Offset Value

-2000~2000

WORD

2

Alarm Mode Setting

Alarm:Short Circuit

1

Latch Mode

BIT

–

0

Momentary

Mode

Alarm: Open Circuit

1

Latch Mode

BIT

–

0

Momentary

Mode

Alarm: LED Display Mask

1

Enable

BIT

–

0

Disable

14-3-5 M0202AH (A/D)

Registers Settings Table

Setting Item

Register Value

Function

Word Type

Word Usage

A/D Conversion Setting

A/D Channel Enable/Disable

1

Enable

BIT

–

0

Disable

A/D Conversion Method

0

No Average

WORD

1

1

Count Average

2

Time Average

3

Moving Average

A/D Conversion Method Set Value

2~1000

Count Average

WORD

2

1~1604000

Time Average

2~1000

Moving Average

A/D Conversion Time

0

High Speed

WORD

1

1

Middle Speed

2

Low Speed

3

50Hz

4

60Hz

Input Signal Range Setting

Input Signal Range

0

0~5V

WORD

1

1

0~10V

2

-5~5V

3

-10~10V

4

1~5V

5

4~20mA

6

0~20mA

7

-20~20mA

Scaling Setting

Scaling Enable/Disable

1

Enable

BIT

–

0

Disable

Upper Limit Value

-30000~30000

WORD

2

Lower Limit Value

-30000~30000

WORD

2

Data Offset Setting

Data Offset Enable/Disable

1

Enable

BIT

–

0

Disable

Data Offset Value

-2000~2000

WORD

1

Setting Item

Register Value

Function

Word Type

Word Usage

Overflow Underflow Setting

Overflow Underflow Enable/Disable

1

Enable

BIT

–

0

Disable

Alert Output Setting

Alert Output Enable/Disable

1

Enable

BIT

–

0

Disable

Upper Upper Limit Value

-32000~32000

WORD

2

Upper Lower Limit Value

-32000~32000

WORD

2

Lower Upper Limit Value

-32000~32000

WORD

2

Lower Lower Limit Value

-32000~32000

WORD

2

Burnout Detection Setting

Burnout Detection Enable/Disable

1

Enable

BIT

–

0

Disable

Burnout Detection Output

0

High Scale

WORD

1

1

Down Scale

Alarm Mode Setting

Alarm: Overflow

1

Latch Mode

BIT

–

0

Momentary

Mode

Alarm: Underflow

1

Latch Mode

BIT

–

0

Momentary

Mode

Alarm: Alert Output(Upper Limit)

1

Latch Mode

BIT

–

0

Momentary

Mode

Alarm: Alert Output (Lower Limit)

1

Latch Mode

BIT

–

0

Momentary

Mode

Alarm: Burnout Detection

1

Latch Mode

BIT

–

0

Momentary

Mode

Max, Min Hold Setting

Max, Min Hold Enable/Disable

1

Enable

BIT

–

0

Disable

Data Buffer Setting

Data Buffer Points

1~600

WORD

1

Data Buffer Points Before Trigger

0~599

WORD

1

14-3-6 M0202AH (D/A)

Registers Settings Table

Setting Item

Register Value

Function

Word Type

Word Usage

D/A Conversion Setting

D/A Channel Enable/Disable

1

Enable

BIT

–

0

Disable

Output Signal Range Setting

Output Signal Range

0

0~5V

WORD

1

1

0~10V

2

-5~5V

3

-10~10V

4

1~5V

5

4~20mA

6

0~20mA

Output Hold Function

Output Hold Enable/Disable

1

Enable

BIT

–

0

Disable

Output Hold Setting

0

Clear

WORD

1

1

Hold

2

User-Define Value

User-Defined Value

0~16383

WORD

2

Slew Rate Setting

Slew Rate Enable/Disable

1

Enable

BIT

–

0

Disable

Slew Rate (steps/sec)

4

Slew Rate 500

WORD

2

5

Slew Rate 1000

6

Slew Rate 2000

7

Slew Rate 4000

8

Slew Rate 8000

9

Slew Rate 16000

10

Slew Rate 32000

11

Slew Rate 64000

12

Slew Rate 128000

13

Slew Rate 256000

14

Slew Rate 512000

15

Slew Rate 1024000

Scaling Setting

Scaling Enable/Disable

1

Enable

BIT

–

0

Disable

Upper Limit Value

-30000~30000

WORD

2

Lower Limit Value

-30000~30000

WORD

2

Data Offset Setting

Data Offset Enable/Disable

1

Enable

BIT

–

0

Disable

Data Offset Value

-2000~2000

WORD

2

Alarm Mode Setting

Alarm: Short Circuit

1

Latch Mode

BIT

–

0

Momentary

Mode

Alarm: Open Circuit

1

Latch Mode

BIT

–

0

Momentary

Mode

Alarm: LED Display Mask

1

Enable

BIT

–

0

Disable

14-3-7 M04RTD

Registers Settings Table

Setting Item

Register Value

Function

Word Type

Word Usage

RTD Setting

D/A Channel Enable/Disable

1

Enable

BIT

–

0

Disable

Moving Average Count

1~10

WORD

1

Sensor Setting

Sensor Type

0

Pt100

WORD

1

1

JPt100

2

Pt1000

3

JPt1000

Sensor Range

0

RANGE1

WORD

1

Function Setting

Temperature Unit

1

℃

BIT

–

0

℉

Control Method

0

ON/OFF control

BIT

–

1

PID control

Control Output

0

OFF

WORD

1

1

ON

2

HOLD

Post Processing Setting

Scaling Enable/Disable

1

Enable

BIT

–

0

Disable

Maximum Scaled Value

-32000~32000

WORD

1

Minimum Scaled Value

-32000~32000

WORD

1

Data Buffer Setting

Data Buffer Setting Points

1~600

WORD

1

Data Buffer Setting Points Before Trigger

0~600

WORD

1

Setting Item

Register Value

Function

Word Type

Word Usage

Alert Setting

Alert Standby Mode Enable/Disable

1

Enable

BIT

–

0

Disable

Upper Limit Input Value

-200~850

WORD

2

Lower Limit Input Value

-200~850

WORD

2

Upper Limit Deviation Value

-1050~1050

WORD

2

Lower Limit Deviation Value

-1050~1050

WORD

2

Upper Lower Limit Deviation Value

0~1050

WORD

2

Dead Band Alert

0~10

WORD

1

Number Of Alert delay

0~255

WORD

1

Loop Disconnection Detection

0~7200

WORD

1

Loop Detection Dead Band

0~1050

WORD

2

14-3-8 M0202TH (RTD)

Registers Settings Table

Setting Item

Register Value

Function

Word Type

Word Usage

RTD Setting

RTD Channel Enable/Disable

1

Enable

BIT

–

0

Disable

Moving Average Count

1~10

WORD

1

Sensor Setting

Sensor Type

0

Pt100

WORD

1

1

JPt100

2

Pt1000

3

JPt1000

Sensor Range

0

RANGE1

WORD

1

Function Setting

Temperature Unit

1

℃

BIT

–

0

℉

Control Method

0

ON/OFF control

BIT

–

1

PID control

Control Output

0

OFF

WORD

1

1

ON

2

HOLD

Post Processing Setting

Scaling Enable/Disable

1

Enable

BIT

–

0

Disable

Maximum Scaled Value

-32000~32000

WORD

1

Minimum Scaled Value

Data Buffer Setting

Data Buffer Setting Points

1~600

WORD

1

Data Buffer Setting Points Before Trigger

0~600

WORD

1

Alert Setting

Alert Standby Mode Enable/Disable

1

Enable

BIT

–

0

Disable

Upper Limit Input Value

-200~850

WORD

1

Lower Limit Input Value

-200~850

WORD

1

Upper Limit Deviation Value

-1050~1050

WORD

1

Lower Limit Deviation Value

-1050~1050

WORD

1

Upper Lower Limit Deviation Value

0~1050

WORD

1

Dead Band Alert

0~10

WORD

1

Number Of Alert delay

0~255

WORD

1

Loop Disconnection Detection

0~7200

WORD

1

Loop Detection Dead Band

0~1050

WORD

1

14-3-9 M0202TH (TC)

Registers Settings Table

Setting Item

Register Value

Function

Word Type

Word Usage

TC Setting

TC Channel Enable/Disable

1

Enable

BIT

–

0

Disable

TC Conversation Time

0

Standard

WORD

1

1

Fast

Moving Average Count

1~10

WORD

1

Sensor Setting

Sensor Type

0

K

WORD

1

1

J

2

T

3

E

4

R

5

B

6

N

7

S

8

+-100mv

Sensor Range

0

RANGE1

WORD

1

Function Setting

Temperature Unit

1

℃

BIT

–

0

℉

Control Method

0

ON/OFF control

BIT

–

1

PID control

Control Output

0

OFF

WORD

1

1

ON

2

HOLD

Post Processing Setting

Scaling Enable/Disable

1

Enable

BIT

–

0

Disable

Maximum Scaled Value

-32000~32000

WORD

1

Minimum Scaled Value

Data Buffer Setting

Data Buffer Setting Points

1~600

WORD

1

Data Buffer Setting Points Before Trigger

0~600

WORD

1

Alert Setting

Alert Standby Mode Enable/Disable

1

Enable

BIT

–

0

Disable

Upper Limit Input Value

-200~1350

WORD

2

Lower Limit Input Value

-200~1350

WORD

2

Upper Limit Deviation Value

-1550~1550

WORD

2

Lower Limit Deviation Value

-1550~1550

WORD

2

Upper Lower Limit Deviation Value

0~1550

WORD

2

Dead Band Alert

0~10

WORD

1

Number Of Alert delay

0~255

WORD

1

Loop Disconnection Detection

0~7200

WORD

1

Loop Detection Dead Band

0~1550

WORD

2

14-3-10 M02LC(R)

Registers Settings Table

Setting Item

Register Value

Function

Word Type

Word Usage

LC Setting

LC Channel Enable/Disable

1

Enable

BIT

–

0

Disable

Weight Unit

0

G

WORD

1

1

Kg

2

T

Decimal

0

1

WORD

1

1

0.1

2

0.01

3

0.001

Rated Capacity

0~999999

WORD

2

Rated Output

0

0~1mV/V

WORD

1

1

0~2mV/V

2

0~3mV/V

3

0~4mV/V

Number Of LC In Connection

1~4

WORD

1

Maximal Weight Capacity

1~4

WORD

2

Minimal Division

0

1

WORD

1

1

2

2

5

3

10

4

20

5

50

Zero Point Range

0~100

WORD

1

Weight Conversion Method

0

Sampling

WORD

1

1

Count Average

2

Moving Average

Average Count

4~255

Count Average

WORD

1

2~255

Moving Average

Conversion Setting

Conversion Method

1

Auto Restoration

BIT

–

0

Auto Stop

Gravity Acceleration Setting

Installation Site

9.7~9.9999

WORD

2

Calibration Site

9.7~9.9999

WORD

2

Zero Point Tracking Setting

Zero Point Tracking Range

0~100

WORD

1

Zero Point Tracking Time

0~100

WORD

1

Input Signal Error Setting

Input Signal Error Enable/Disable

1

Enable

BIT

–

0

Disable

Input Signal Error

0~25

WORD

1

Gross Weight Setting

Warning Output Enable/Disable

1

Enable

BIT

–

0

Disable

Upper Upper Limit Value

-99999~99999

WORD

2

Upper Lower Limit Value

-99999~99999

WORD

2

Lower Upper Limit Value

-99999~99999

WORD

2

Lower Lower Limit Value

-99999~99999

WORD

2

Center Point Detection Setting

Center Point Detection Enable/Disable

1

Enable

BIT

–

0

Disable

Stable Status Setting

Disable

Stable Status Range

0~100

WORD

1

Stable Status Time

0~100

WORD

1

Zero Point Detection Setting

Zero Point Detection Enable/Disable

1

Digital Value

BIT

–

0

Gross Weight

Zero Point Detection Maximum

-2147483648~10000

WORD

2

Zero Point Detection Minimum

-2147483648~10000

WORD

2

Data Buffer Setting

Data Type

1

Digital Value

BIT

–

0

Gross Weight

Data Buffer Points

1~600

WORD

1

Data Buffer Points Before Trigger

0~599

WORD

1

Tare Subtraction Setting

Tare Subtraction Mode

1

Digital

BIT

–

0

One Touch

Was this page helpful?

Tip: press ← → to switch chapters, Ctrl+K to search