In addition to timer, counter, register, and contact data access function, the date setter of FB-DAP can connect to many others for alarm message display, self-defined buttons, wireless card reading, and the like simple human-machine (HM) functions.
FB-DAP Simple HM
|
Model Spec. Display |
FB-DAP-A(R) |
FB-DAP-B(R) |
|
LCD (English version), 2-line×16-character, LED backlight 20-key (4×5) |
||
|
5V |
24V |
|
|
100mA (120mA) |
41mA (48mA) |
|
|
HCMOS |
RS-485 |
|
|
Single set |
Max. 16-set connected |
|
|
port 0 |
port 0,1,2 (In which port 0 and 1 needed to be converted as RS-485) |
|
|
Timing/counting、register、contact access(write protected for each) Alarm、message display、self-definition of special speed keys Order for machine types with special numbers to us is required |
||
※ PLC’s MA、MU type machines can be connected to FB-DAP-B(R) only through FB-485 switch.
Wireless sensing card
|
Model Spec. Memory Power supply Sensing distance Number of writing Size (mm) |
CARD-1 |
CARD-2 |
|
64bits with Cyclic Redundancy Check (CRC) on data −25°C~50°C (conforming to ISO7810) Battery not required (power supplied from wireless electric waves released by an −AR/−BR card-reading module) 12cm~18cm(from FB-DAP front) |
||
|
unwritable(uncopiable,exclusively) |
10000 times at least |
|
|
86×54×13 |
||



|
1.1Profile |
112
|
6.5 |
7 |
T |
X |
98 |
7 |
30 |
148 |
Back |
8 |
16 |
外徑 4ψ×4 埋螺帽 |
118.45 |
Lateral |
148 |
14.8 |
|||||
|
Front |
FB-DAP |
DATA ACCESS PANEL |
1.5 |
22.43 |
||||||||||||||||
|
FATEK |
||||||||||||||||||||
|
7 |
+ |
8 |
ON / OFF |
FUN |
||||||||||||||||
|
9 |
CLEAR |
|||||||||||||||||||
|
Y |
||||||||||||||||||||
|
E |
F |
ADR / DOC |
||||||||||||||||||
|
C |
||||||||||||||||||||
|
4 |
5 |
6 |
||||||||||||||||||
|
M |
||||||||||||||||||||
|
A |
B |
DEC / HEX |
||||||||||||||||||
|
D |
||||||||||||||||||||
|
1 |
2 |
3 |
||||||||||||||||||
|
S |
||||||||||||||||||||
|
W |
CV / PV |
|||||||||||||||||||
|
R |
0 |
SHIFT |
ENTER |
|||||||||||||||||
14.75
|
102.5 |
4.75 |
12 |
17.6 |
9.9 |
1.2Important points before operation
1、 FB-DAP possesses a function to return to the operation mode (general data setter and self-definition 8/16 speed keys) before power failure and each DAP can be place in a different mode when connecting many sets.
2、 When operating FB-DAP,D2944~D3071 register of PLC will be used as the systematic architecture zone (in which data set by all the FUN functions can be stored except item 11) , the user shall avoid this zone.
3、 Any communication port, once converted to a RS-485 interface (port 2 is itself a RS-485 interface), can be connected to a maximum of 16 FB-DAP-B(R) sets.
|
PLC port0 |
FB-485P0 switch head |
RS-485 interface |
|
Only thus so the FB-DAPB (R) can |
|
(HCMOS) |
FB-485 switch |
RS-485 interface |
be connected to. |
|
|
PLC port1 |
(RS-232)
4、 When PLC is connected with FB-DAP-B(R),the service point numbers of PLC are limited to a range of 1~32.
5、 Parameters for the connection between PLC and FB-DAP-B(R)(DAP automatic detection Baud Rate 9600 / 19200 / 38400)
port0、1、2:9600 / 19200 / 38400、Even、7Data bits、1Stop bit
ex:R4158=5521H, i.e. port2 being 9600;R4158=5523H, i.e. port2 being 38400.
6、 When many sets of DAP are connected, if any two or more have the same service point number, then DAP will
|
request for number change, which can be done by only entering〝 |
|
〞即可。 |
7、 The transmission line of the RS-485 interface must use a twisted pair with a shielded cover on the outer layer. Please refer to chapter 12-5 in the Operation Manual II for other important points.
8、 The scanning time of PLC will affect the update time of DAP.
9、 The OS of FB-DAPB(R) shall be new V2.00 above PCB so that multiple sets can be connected. Press
then the OS version is displayed.
10、 When PROLADDER(or FP07) and DAP are connected to the same set of PLC, to change the program through PROLADDER is not allowed; if so, the timer information displayed by DAP won’t be correct (In this




case, the DAP shall be reset).
11、 Versions after the OS V3.15 (including) of FP-07 can be aimed for DOCs in 16 words of contacts, registers.
1.3The Main Functions of FB-DAP
The main functions of FB-DAP can be categorized as: setter functions of general information, FUN functions of parameter setting, wireless card reading, and message display function. The details of the functions will be introduced in the following sections.
1.4Setter Functions of General Information
FB-DAP can be used as a 〝TC setter〞as well as the access to registers (R、D、W) and contacts (X、Y、M、S). In the FUN functions in the following sections, it can also be used as write-protect with T、C、R、D、X、Y、M、S. There are two measures to monitor information: ADR (general addresses) and DOC monitoring. The latter shall make DOC compilation (16 words in English, symbols, numbers) in advance through Proladder or FP07 for T, C, register R/D and contacts so the DOC can be displayed.
1、 ADR Monitoring
A. Timer and Counter Monitoring
|
【Pressing Keys】: |
|
|||
|
T or C number |
Cursor position |
|||
|
|
↓ |
|||
|
• • •••• •••••• |
← Set value |
|||
|
•• ••• •••••• |
← Current value |
|||
|
↑ |
↑ |
|||
|
Status |
FB-DAP automatic detecting a decimal point position |
|||
B. Registers (R、D、DR、DD、WX、WY、WM、WS) and contacts (X、Y、M、S) monitoring
【Monitored range】
|
Type |
T |
C |
D |
R |
DD |
DR |
WX |
WY |
WM |
WS |
X |
Y |
M |
S |
|
Range |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
|
【Pressing keys】: |
|
or |
or |
or |
) |
|
+ |
|||
|
+ ( |
or |
) |
||||||||
|
+ |
( |
or |
||||||||
|
( |
or |
or |
) |
|||||||
|
Cursor position |
Value |
|||||||||
|
↓ |
↓ |
|||||||||
|
•••••••• |
•••• |
← Item 1 |
||||||||
|
• |
•••••• |
← Item 2 |
||||||||
↑
Status

〝H〞 indicates hexadecimal
↓
|
Note:1、Pressing
3、For a monitored item value, input a new value directly and then press can decrease or increase the monitored item number. pressing status is available. contacts can be changed by pressing |
||||||||||||||||||
|
4、Pressing |
|
can change the means to display a value (either with decimal or hexadecimal |
||||||||||||||||
system).
2、 DOC monitoring
|
••••• |
•• |
← DOC of T10 |
|
|
•• |
••• |
•••••• |
← Current value |
↑
Contact status
|
••••••• |
• |
← Register DOC |
||||||
|
• |
•••• |
← Value |
||||||
|
Note:1、Pressing |
|
can switch the monitoring of ADR and DOC. |
||||||
|
|
. |
|||||||
|
2、The display switch between CV (current value) and PV of the timer (counter) can use |
||||||||
|
3、 |
|
can be moved up or down to next monitored item with DOC. |
||||||
3、 Speed monitoring FUN keys(FUN KEY 0~9, totaling 10 keys)
|
【Pressing keys】: |
+ |
( |
~ |
) Direct display of a monitored item set by the client. |
Note:1、Items to be monitored can be set from the following “FUN functions”.
2、Items to be monitored can be displayed with general or DOC means.


1.5FUN Functions
|
1.5.1In and out of FUN functions |
■ Enter FUN functions
|
Press + + |
Press |
* |
1、PASSWORD OPEN |
(Password open) |
|
2、PASSWORD CLOSE |
(Password blocked) |
|||
|
3、PASSWORD SET |
(Password setting) |
|||
|
4、DEFINE FUN KEY |
(Self-define speed monitoring function key FUN KEY 0-9) |
|||
|
5、DEFINE ALARM |
(Self-define start address of content for display at an alarm) |
|||
|
ADDRESS |
||||
|
6、DEFINE SOFTKEY |
(Self-define 8 special keys) |
|||
|
(8-KEY) |
||||
|
7、DEFINE SOFTKEY |
(Enter into the modes of the 8 special keys) |
|||
|
MODE (8-KEY) |
||||
|
* |
8、DEFINE SOFTKEY |
(Self-define 16 special keys) |
||
|
(16-KEY) |
||||
|
9、ENTER SOFTKEY |
||||
|
(Enter into the modes of the 16 special keys) |
||||
|
MODE(16-KEY) |
||||
|
○ |
10、VOLUME |
(Adjust volume) |
||
|
○ |
11、SET DAP NO. |
(Set DAP number(s) at multi-link) |
||
|
12、MAX. DAP NO. |
||||
|
(Set the max. DAP numbers on network (1-16) at multi-link) |
||||
|
ON NETWORK(1~16) |
||||
|
○ |
13、WRITE PROTECT |
(Data write-in protection) |
||
|
○ |
14、RF CARD MODE |
(RF card mode selection) |
||
|
○ |
15、RF CARD |
(Start address of a RF card number storage) |
||
|
START ADDR. |
||||
|
* |
16、ENABLE |
(Corresponding special contacts of ENABLE keys) |
||
|
KEYS MAPPING |
*:Indicates when multiple DAPs are connected, each DAP can be set respectively.
○:Indicates when multiple DAPs are connected, the information set by one of them is not available for use until PLC is reset.
■ Exit of FUN functions to general information setter functions. Press •••+••• +• •• +
Note:1、When several DAPs are connected, information can be stored to PLC (D2944~D3071) if one of the DAP is set in
all the FUN functions (except item 11).
2、After entering FUN 4~15, without password protection, all the FUN functions can be executed by only pressing
. With password protection, it is required to pass it first before executing FUN functions.
3、If it is password-protected, FB-DAP will be set in a password protection status at each beginning of operation.
4、FUN items 1~9 can be entered with numeric keys directly and then go straight to that function.
5、After executing a item of FUN functions, if execution of other items is required, press the three keys
|
|
again. |


|
1.5.2FUN function description |
FUN 1~3(password)
1、 Password contains up to 4 digits(unrelated to LADDER program’s password).
2、 After the password is set, it will enter a password-locked status once it is started.
3、 After the password is locked, all the FUN functions are not available.
FUN 4(DEFINE FUN KEY):Self-setting speed monitoring function keys
4、DEFINE FUN KEY
、
1、 There are ten self-setting speed monitoring function keys in total.
2、 All items available for monitoring can be defined in the ten function keys.
|
3、 Pressing |
+ |
can select ADR or DOC. |
FUN 5(DEFINE ALARM ADDRESS):The address for display at self-setting an alarm.
1. There are ten start addresses, that is, ten levels of alarm signals.
2. All items available for monitoring can be defined in the said ten start addresses.
|
3. Pressing |
|
can select ADR or DOC for display. |
4. Control measures of alarm signals for display are shown as follows:
【Corresponding list for control】
|
Alarm level |
Control contact |
Indication register |
Start address of the content displayed |
|
ALARM 0 |
M1900 |
R3820 |
Client-defined |
|
ALARM 1 |
M1901 |
R3821 |
Client-defined |
|
ALARM 9 |
M1909 |
R3829 |
Client-defined |
【Example】Assume the start address of ALARM 0 displayed content to be R100, If M1900=1 then the alarm address for display is R100 +(R3820)
If R3820=0 Display address or DOC of R100
R3820=1 Display address or DOC of R101
R3820=2 Display address or DOC of R102
Note 1:When a multi-level alarm occurs, only the address or DOC with priority can be displayed. The address or DOC of a sub level alarm will not be displayed until this alarm with priority is released.
Note 2:To display a DOC (message) with 16 digits above, the corresponding indication register (R3820~ R3829) content can be changed anytime to reach this purpose.
Note 3:M1911 can control whether to sound the alarm buzzer. If M1911=0 (preset), it shall be activated.
FUN 6(DEFINE SOFTKEY-8 KEYS):Self-defining 8 soft keys
FUN 7(ENTER SOFTKEY MODE-8 KEYS):Enter 8 soft key mode
1. Can self-define 8 soft keys:
2. Definable range:R0~R3839、D0~D2943、M0~M1899.
3. In defining M0~M1899, this key can be defined as one of the 5 modes.
|
Mode |
Definition |
Description |
|||
|
0 |
Set |
(S) |
Set this contact to 1 |
||
|
1 |
Reset |
(R) |
Set this contact to 0 |
||
|
2 |
Moment |
(M) |
1 in pressing, 0 in being released |
||
|
3 |
Inverse |
(I) |
Pressing once will have one inverse phase. |
||
|
4 |
Monitor |
(V) |
Monitor this contact |
||
|
【Example】 Assume |
|
definition as R0, |
|
definition as M0 mode 0(Set). Once enter the 8 soft key |
|
mode in function 7,
|
Then pressing |
|
display address or DOC of R0. |
|
|
||
|
display address or DOC of M0 and force M0 ON |
Note 1:After defining the 8 soft keys, once function 7 is executed, it will enter 8 soft key operation mode.
And then the 8 soft keys will be executed according to function 6 definitions.
Note 2:
both are allowed out of definition, but the other keys will not be effected without
definition.
|
Note 3:To return to normal operation mode, press〝 |
|
+(D2972 content)+ |
|
〞, among which |
D2972 content is from 0000~9999(4 digits required).
FUN 8(DEFINE SOFTKEY-16 KEYS):Self-define 16 soft keys
FUN 9(ENTER SOFTKEY MODE-16 KEYS):Enter 16 soft key mode
1. Available for defining 16 soft keys:
2. Definable range:T0~T255、C0~C199、R0~R3839、D0~D2943、M0~M1899。
3. In defining M0~M1899, this key can be defined as one of the 5 modes and when a message is being
displayed, if the key is pressed, the display will not be changed.
|
Mode |
Definition |
Description |
||||||
|
0 |
Set |
(S) |
Set this contact to 1 |
|||||
|
1 |
Reset |
(R) |
Set this contact to 0 |
|||||
|
2 |
Moment |
(M) |
1 in pressing, 0 in being released |
|||||
|
3 |
Inverse |
(I) |
Pressing once will have one inverse phase. |
|||||
|
4 |
Monitor |
(V) |
Monitor this contact |
|||||
|
4. When defined as T, C, R or D, the value change is by pressing |
|
or |
|
to make the corresponding |
||||
M1840~M1871 ON (the client is required to write a plus/minus 1 program in the LADDER program) to achieve
this purpose.
|
Soft |
0 |
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
T |
C |
D |
R |
SHIFT |
|
|
|
key |
M1840M1841M1842M1843M1844M1845M1846M1847M1848M1849M1850M1851M1852M1853M1854M1855
M1856M1857M1858M1859M1860M1861M1862M1863M1864M1865M1866M1867M1868M1869M1870M1871

|
【Example】Assume |
|
definition as R0, |
|
defined as M0 mode 1 (Reset). |
After entering 16 soft key mode in function 9,
|
Press |
|
Display the address or DOC of R0, and then pressing |
|
, its corresponding |
M1850 will be ON; OFF after it is released.
Display the address or DOC of M0 and force M0 OFF.
Note 1:After the 16 soft keys are defined, once function 9 is executed, it will enter 16 soft key operation mode and then the 16 soft keys will be executed according to function 8 definition.
|
Note 2:to return to normal operation mode, press〝 |
+ ( |
+ |
+ |
+ |
) + |
〞。 |
FUN 11(SET DAP NO.):When several sets are connected, set DAP number.
After any communication of FB-PLC is converted to RS-485 interface (Among which port2 as such is a RS-485 interface), the FB-DAP-B(R) of the 16 sets can be connected. Each DAP shall need a unique number, 1~16 (but one of them must be number 1). This DAP is not related to PLC numbers, meaning the number can have the same PLC number.
FUN 12(MAX. DAP NO. ON NETWORK):when several sets are connected, set the biggest DAP number on the Web. (Max. 16 DAPs, preset 7)
In a connection of several sets, FB-PLC can be joined with new DAPs. But the more the DAP number, the longer the time to update information of each DAP. As a result, set the DAP number (the DAP number can not be bigger than this number) on the Web appropriately will decrease time for information to update.
FUN 13(WRITE PROTECT):Information write in
Aimed for monitored items (T, C, R, D, Y, M, S), set the information in write-in protection separately. Just fill in the corresponding place with 1, and then the item is write-in protected and can be read values only.
FUN 14(RF CARD MODE):Wireless card reading options
MODE=〝0〞 When reading a RF card, it will display whether this card is OK or Error. When the RF card is out of sensing distance, it will pop up 〝NEXT〞, indicating another RF card is available now.
MODE=〝1〞 once a RF card is read, it will beep once and will not display any information so the
sensing speed can be faster. But when many DAPs are connected, this mode will increase
by about 60mS to each set for monitored item information.
FUN 15(RF CARD START ADDR.):Start addresses storing the wireless RF card numbers
Store a card number’s address can be set through the function, ranging from D0~D2860 (preset to D2860). Please refer to the Wireless Card Reading Functions in 1.6 for detailed description.
FUN 16(ENABLE KEYS MAPPING):Corresponding special contact of Enable key
After this function is set to 〝Enable〞 and enter SOFTKEYMODE(8KEYS and 16KEYS), pressing a definable soft key will force ON some contact of a corresponding contact under its number and the other contacts become OFF. When set to “Disable”, the corresponding special contact of this DAP will not be effected.


The following is corresponding special contacts to different DAP keys when in 16 KEYS MODE:
KEY
T C D R 7 4 1 0 8 5 2 SHIFT 9 6 3
No. (↑) (↓)
1 M1784M1785M1786M1787M1788M1789M1790M1791M1792M1793M1794M1795M1796M1797M1798M1799
2 M1768M1769M1770M1771M1772M1773M1774M1775M1776M1777M1778M1779M1780M1781M1782M1783
3 M1752M1753M1754M1755M1756M1757M1758M1759M1760M1761M1762M1763M1764M1765M1766M1767
4 M1736M1737M1738M1739M1740M1741M1742M1743M1744M1745M1746M1747M1748M1749M1750M1751
5 M1720M1721M1722M1723M1724M1725M1726M1727M1728M1729M1730M1731M1732M1733M1734M1735
6 M1704M1705M1706M1707M1708M1709M1710M1711M1712M1713M1714M1715M1716M1717M1718M1719
7 M1688M1689M1690M1691M1692M1693M1694M1695M1696M1697M1698M1699M1700M1701M1702M1703
8 M1672M1673M1674M1675M1676M1677M1678M1679M1680M1681M1682M1683M1684M1685M1686M1687
9 M1656M1657M1658M1659M1660M1661M1662M1663M1664M1665M1666M1667M1668M1669M1670M1671
10 M1640M1641M1642M1643M1644M1645M1646M1647M1648M1649M1650M1651M1652M1653M1654M1655
11 M1624M1625M1626M1627M1628M1629M1630M1631M1632M1633M1634M1635M1636M1637M1638M1639
12 M1608M1609M1610M1611M1612M1613M1614M1615M1616M1617M1618M1619M1620M1621M1622M1623
13 M1592M1593M1594M1595M1596M1597M1598M1599M1600M1601M1602M1603M1604M1605M1606M1607
14 M1576M1577M1578M1579M1580M1581M1582M1583M1584M1585M1586M1587M1588M1589M1590M1591
15 M1560M1561M1562M1563M1564M1565M1566M1567M1568M1569M1570M1571M1572M1573M1574M1575
16 M1544M1545M1546M1547M1548M1549M1550M1551M1552M1553M1554M1555M1556M1557M1558M1559
In 8KEYS MODE, only 8 keys 、 、、 、 、 、 、 are effective, i.e.
number keys ineffective. And
take the positions of
and
, but it must be when both
keys are defined as soft keys so that the corresponding special contacts are effective.
|
〈Example〉 No.2:Pressing |
|
, M1768 is ON and M1769~M1783 OFF. |
|
No. 5:Pressing |
|
, M1722 is ON and other contacts M1720~M1735 OFF. |
1.6Wireless card reading functions
An applicable RF card is an exclusive read-only card (RF-CARD-1) or readable/writable card (RF-CARD-2),
in which the card number of the read-only card is unique ( with 16 0~F digits), not repeatable and copyable.
And card numbers read by FB-DAP-AR(BR) shall be encoded with high security.
The sensing distance of a RF card generally is 12~18cm, but shall be kept away from electromagnetic
wave interference source or high voltage power line.
Readable/Writable cards (RF-CARD-2)can use Fatek’s FB-DAP-W in special sequence numbers to write in
card numbers. The card numbers are all encoded and relate to machine sequence numbers (the first 4
codes are the machine’s sequence number, the last 12 codes defined by the client). Only through Fatek’s
FB-DAP-A(B)R can a correct numbers be read. Under FUN function 17, FB-DAP-W can be input 12 0~F
digits or use
to change the card number. Finally, only place the distance of RF-CARD-2
within FB-DAP-W 12cm and then press
, so that the card number can be written into RF-CARD-2.
Locations and application of the card number storage
FB-DAP saves RF card numbers within sensing distance into two places in PLC. The places and application are described as follows:
4、Fixed in R3835~R3839(totaling 5 registers):During operation, M1910 shall be controlled.
Card number
format
|
R3835 |
|
N1:DAP number 1~16(i.e. 1H~10H) |
||||||||||
|
R3836 |
N2:52H(R:read-only card) or 57H(W:readable/writable card) |
|||||||||||
|
R3837 |
R3836~R3839 store 16 0~F card numbers |
|||||||||||
|
R3838 |
||||||||||||
|
R3839 |
||||||||||||
Application:
Only in monitoring (or8/16 soft keys) mode (non-FUN functions) and the RF card in sensing distance, FB-DAP(−AR or −BR)will send the RF card number together with DAP number to PLC R3835~R3839. In mode 0 of function 14 (RF CARD MODE), all the client needs to do is compare the card number. If it is OK, only set M1910 to 1 and then DAP will indicate “OK”, or “ERROR”. When the RF card is out of sensing distance, DAP will pop up “NEXT” and clear the content of PLC R3838~R3839 to 0, which means available for another RF card. In mode 1 of function 14, as soon as DAP reads a card number, it will save it to R3835~R3839 with a beep. After the RF card exits, the 5 registers remain unchanged.
Applicable occasions:
Where one set or multiple sets are connected but RF cards are not used frequently, the program to be applied will be a lot easier. But in the event of a card number read from different DAPs at the same time, it will be difficult for PLC to identify the information correctly.
5、Preset D2860~D2939 (16 differently-located DAP take on 5 registers individually, i.e. 80 registers in all, but the locations can be changed through function 15) control one point of M1880~M1895 separately when in use.
|
D2860 |
Card number |
D2865 |
Card number |
D2870 |
Card number |
D2935 |
Card number |
||||||||||||||||||||||||||||||||||||
|
format |
format |
format |
format |
||||||||||||||||||||||||||||||||||||||||
|
|
|
|
||||||||||||||||||||||||||||||||||||||||
|
D2861 |
D2866 |
D2871 |
D2936 |
||||||||||||||||||||||||||||||||||||||||
|
D2862 |
D2867 |
D2872 |
D2937 |
||||||||||||||||||||||||||||||||||||||||
|
D2863 |
D2868 |
D2873 |
D2938 |
||||||||||||||||||||||||||||||||||||||||
|
D2864 |
D2869 |
D3974 |
D2939 |
||||||||||||||||||||||||||||||||||||||||
|
No. 1 |
No. 2 |
No. 3 |
No. 16 |
||||||||||||||||||||||||||||||||||||||||
|
⇓ |
⇓ |
⇓ |
⇓ |
||||||||||||||||||||||||||||||||||||||||
|
M1880 |
M1881 |
M1882 |
M1895 |
||||||||||||||||||||||||||||||||||||||||
Application measures:
The application measures are all described as the above-mentioned but that the storage places of card numbers and corresponding contacts for control are different. For example, in mode 0 of function 14, from No. 2 DAP sensing to the RF card, now no. 2 will send same card numbers to two different places in R3835~R3839 and D2865~D2869 (the content of the other registers remains unchanged), and all the client needs to do is control M1881 for the DAP to display “OK” or “ERROR”. After the RF card exits, the content of the 10 registers R3835~R3839 and D2865~D2869 will be cleared to 0 (but remains unchanged in mode 1).
Applicable occasions:
When several DAPs are connected, the RF card can be read in from different DAPs and each DAP has its independent card numbers storage places and control points so that no PLC misjudgment case occurs, but the programming will be more troublesome.
※ If you do not want R3835~R3839 to display a card number value, you can use the Ladder program to fill in these registers with other fixed values.
|
1.7Special message display function |
In general monitoring mode and soft key mode (16 KEYS or 8 KEYS), the user can configure the DAP to display every kind of message under some circumstances, and the two-line display on the LCD can be c ontrolled separately to simultaneously display different messages. Every message is 1~511 words and numbers (ASCII code) long, in which a maximum of 16 variables (if variables with 32-digit are not used, then it can use up to 25) can be included. When a message has more than 16 words, the message will be displaced left for display, in whic h the moving s peed or pause time can be configured flexibly.
|
1.7.1Message display application |
The FB-DAPB(R) can be connected up to 16 sets (Number 1~16). Each DAP not only can display different messages individually but make all the DAPs connected display the same message simultaneously. If you go to a special contact (R3780~M3813) set by Enable, the DAP will display the message ASCII Code) indicated by the corresponding indication register (R3780~M3813). The content of the indication register is the start register of messages, i.e. start of ASCII Code. The indication register content can be changed anytime in order to change and display different messages.
The following is a list of corresponding special c ontacts and indication registers when each DAP is displaying a message for control.
|
Number of a message displayed |
LCD line 1 |
LCD line 2 |
||
|
Special contact |
Indication register |
Special contact |
Indication register |
|
|
1~16 |
M1800 |
R3780 |
M1801 |
R3781 |
|
1 |
M1802 |
R3782 |
M1803 |
R3783 |
|
2 |
M1804 |
R3784 |
M1805 |
R3785 |
|
3 |
M1806 |
R3786 |
M1807 |
R3787 |
|
4 |
M1808 |
R3788 |
M1809 |
R3789 |
|
5 |
M1810 |
R3790 |
M1811 |
R3791 |
|
6 |
M1812 |
R3792 |
M1813 |
R3793 |
|
7 |
M1814 |
R3794 |
M1815 |
R3795 |
|
8 |
M1816 |
R3796 |
M1817 |
R3797 |
|
9 |
M1818 |
R3798 |
M1819 |
R3799 |
|
10 |
M1820 |
R3800 |
M1821 |
R3801 |
|
11 |
M1822 |
R3802 |
M1823 |
R3803 |
|
12 |
M1824 |
R3804 |
M1825 |
R3805 |
|
13 |
M1826 |
R3806 |
M1827 |
R3807 |
|
14 |
M1828 |
R3808 |
M1829 |
R3809 |
|
15 |
M1830 |
R3810 |
M1831 |
R3811 |
|
16 |
M1832 |
R3812 |
M1833 |
R3813 |
〈Example〉Assume M1803 from 0→1, R3783=100
※ The start register of a message
indicated by an indication register
means:
0~8070:indicating R0~R8070
10000~13070:indicating D0~D3070
※ Special contacts M1800 and M1801 have a priority display function.
※ M1911 can control an alarm buzzer whether to sound or not. If M1911=0(preset), it shall be activated.
Result:Line 2 of No. 1 of the LCD will display messages in ASCII Code with R100 start.
〈Example〉 Assume M1828 from 0→1, R3808=10000
Result:Line 1 of No. 14 of the LCD will display messages in ASCII Code with D0 start.
〈Example〉 Assume M1801 from 0→1, R3781=0
Result:Line 2 of all the DAPs will display messages in ASCII Code with R0 start.
1.7.2The Information formats of messages(ASCII Table)
The information formats of messages are very similar to the file information in ASCII in chapter 15 in the Advanced Manual that are all categorized as fixed background information and dynamic variable information. The first can be words in English, numbers, or signs, and the second binary, decimal or hexadecimal system.
Length of a message is 1~511 digits (including blank spaces), but because there are only 16 digits a line in a DAP LCD, if a message has more than 16 digits, it will be displayed automatically toward the left (preset moving one time a second); if less than 16 digits, the tail will be filled in with blank digits and no moving occurs.
To edit a message, the WinProladder ASCII Editor can be applied. The editing command formats are as follows:
1 Background information format
Any ASCII Code digits quoted with ‘ ‘ can be background information. To display a single quotation mark as
such, two continuous quotation marks are a must. Example:
‘ I ‘ ‘M A BOY’ will be displayed I’M A BOY
|
2Variable information format |
|
,"8 .2R0 D",↗↑ ↑↖
displayed |
Description information in a pair of dual quotation marks 〝 〞is used to indicate the register address (number)
storing the variable information and in what format and carry code to display.
Total variable count displayed:In this case, the value (including minus) of the variable R0 is displayed in a field with 8 digits. If the variable value is bigger than the total variable count displayed, the digits further from the point will be cut. If not enough, blank spaces will fill in.
Decimal point count:the decimal point count in the total digits. In this case, with a total count of 8 digits, the decimal point count is 2. The decimal point sign 〝.〞 as such possesses one digit and there are 5 digits left in the integral part.
Contacts:generally displayed as ON or OFF (total digit count displayed is set to a fixed 3), but if added with binary system B in the tail, 0/1 will be displayed (total digit count fixed 1)
Carry code:can be hexadecimal H, decimal D (the carry code will use decimal if without indication, so D can be omitted.), or binary B, etc., but a 32 digit variable can not be displayed with binary system.
In this case, R0’s content value is 32768. In 8.2 format the result is displayed as:
|
2 |
3 |
2 |
7 |
. |
6 |
8 |
If the format is changed from 8.2 to 5.1, then the result becomes:

|
2 |
7 |
6 |
. |
8 |
3Basic command signs
|
nS |
Left move speed (repeatable) |
Message displayed at a left LCD move per n(1~255)× 0.1s。
|
nP |
Stop move (repeatable) |
Message stop in(1~255)× 0.1s,and then move left at a configured speed.
|
, |
Comma |
Used as a statement to divide the file information. Information between two neighboring commas is a complete and executable statement (unnecessary for the start and end of a file).
|
END |
End of a file |
※ nS and nP commands will not be activated until after the information following them moves to the left first place on the LCD display. They can have a repeatable arrangement of any place in ASCII, but the same command cannot be connected together.
〈Example〉 Information edited with WinProladder ASCII file editor. R0 is a start register of an ASCII file and the file information is shown as follows:
5S,20P,’A=’,〝6.2R3840〞,’B=’,〝6.2R3841〞,30P,’C: ’,〝1M0B〞,’D: ’,〝1M1B〞,’E: ’,〝1M2B〞, ’ ’,END
If M1800 from 0→1 and R3780=0(i.e. R0), Line 1 of the LCD of DAPs of all numbers is shown as follows:
•••••• •••••••
Move a place left after stopping 2 seconds
••••• ••••••• • ︵ when
|
Move a place left per 0.5s ••••••• •• • •• |
M1800 |
Not changed ︶•• • •• • •• •
After stopping 3s and then move a place left• • •• • •• • •
Return to display again after reaching the end of the ASCII
Variable information is renewable anytime.
To display another message, just change R3780 value and not for M1800.
MEMO