The IO Coupler’s power module has two power sources. The first is a 24VDC power supply dedicated to the CPU (for supplying the CPU module and expansion modules), and the second is a 24VDC power supply for external sensors.
Both the IO Coupler and expansion modules are divided into two types of circuits: internal 24VDC circuits and external 24VDC sensor circuits. The internal 24VDC circuit is powered by the IO Coupler’s power module, while the external sensor circuit can be powered by either an external power supply or by the IO Coupler’s power module using the 24VDC power supply for external sensors.
Both the IO Coupler and expansion modules do not have built-in power supplies and must rely on the power provided by the power module for power supply.
|
⚠Warning |
|
In an industrial environment, there may be non-periodic transient high currents or high voltage pulses caused by the startup or shutdown of other high-power equipment on the main power supply. Users should take necessary measures (such as using isolation transformers or suppression components) to protect the IO Coupler and its peripheral systems. |
1-1 AC Power Module Specifications and Wiring
Power module specifications table
|
Specifications Model |
MPA024-24 |
MPA048-24 |
|
|
Input |
Input Voltage |
100~240VAC |
|
|
Input Frequency |
50/60Hz |
||
|
Maximum Input Current |
1A max. |
||
|
Inrush Current (Cold Start) |
22A/115VAC (44A/230VAC) |
||
|
Surge Voltage Withstand Level |
3,000 VAC(Primary-Secondary)、1,500 VAC(Primary-PE)、500 VAC(Secondary-PE) |
||
|
Insulation Resistance |
>100MΩ/500VDC |
||
|
Fuse Specifications |
2A |
||
|
Maintain Time |
>15ms/ 115VAC,>60ms/ 220VAC |
||
|
Isolation Method |
Transformer/Opto-isolator isolation, 1500VAC/1 minute |
||
|
Power Indicator |
LED (Green) |
||
|
Output |
Rated Output Power |
24W (Internal Power Supply + External Sensor Power Supply) |
24W (Internal Power Supply + External Sensor Power Supply) |
|
Rated Output Current |
1A (Internal Power Supply + External Sensor Power Supply) |
1A (Internal Power Supply + External Sensor Power Supply) |
|
|
External Output Voltage |
24VDC±1% |
||
|
Conversion Efficiency |
86%/110VAC,87%/220VAC |
||
|
Protection |
Overvoltage Protection |
Overvoltage Shutdown (Requires reboot to restore power) |
|
|
Overload Protection |
Foldback Current Limiting (Automatic recovery upon load reduction) |
||
|
Environment |
Operating Temperature |
0℃~55℃ |
|
|
Operating Humidity |
20 ~ 90% (No Condensation) |
||
|
Altitude |
≤ 2000m |
||
|
Vibration Resistance (DIN RAIL Mounting) |
5~8.4Hz Amplitude: 3.5 8.4~150Hz Constant Acceleration:19.6m/s^2(2G) 3-axis direction, 10 times each (IEC61131-2 standard) |
||
|
Impact Resistance |
10G,3-axis direction, 3 times each |
||
|
Interference Resistance |
1500Vp-p,Pulse width 1us |
||
|
Voltage tolerance |
1500VAC,1 minute (between power terminals and input/output terminals, and between all external terminals and the casing) |
||
|
Storage temperature and humidity |
-25 ~ +70℃ |
||
|
Certification |
CE |
||
|
Dimensions |
90mmX33.7mmX90mm |
||
|
⚠Danger |
|
The wiring diagram for the power module, IO Coupler, and expansion modules is as shown in the schematic below. Please note the following points: 1. Please comply with local or national wiring regulations by using a single-pole switch (cutting the live wire “L”) or a double-pole switch (cutting both “L” and “N”) to open or close the AC input power supply. 2. When wiring, the live wire “L” must be connected to the “L” terminal on the machine, while the neutral wire “N” should be connected to the “N” terminal on the machine. Please use wires with a diameter ranging from 1mm² to 2mm² for wiring. The terminals of the IO Coupler or power module must be connected to the protective earth (PE) terminal of the main power supply system, and the wire diameter for these connections should be at least 2mm². |
|
⚠Warning |
|
The 24VDC power supply used for external sensors must not be connected in parallel with other power sources. Doing so would cause conflicts between the two power supply outputs, resulting in a shortened lifespan of the power supplies or immediate damage. This could lead to unpredictable malfunctions of the IO Coupler, resulting in significant harm to individuals or damage to equipment and property. |

▲IO Coupler system wiring

▲Power supply wiring diagram
1-2 Maximum Power Consumption of Expansion Modules
IO Coupler and expansion modules themselves have no power supply and must be powered by the power module (MPA024/48-24). The table below shows the maximum current consumption of each expansion module.
|
⚠Warning |
|
The total current consumption of any one set of output power from the power module (MPA024/48-24) must not exceed the maximum current of the power module (MPA024/48-24). Otherwise, it may cause the power module to overload, resulting in voltage drop or intermittent power supply protection mode, which may cause unexpected actions of the IO Coupler, leading to personal injury or equipment damage. |
Expansion Module Maximum Current Consumption Table
|
Model Number Current Consumption |
Internal 24VDC circuit |
External 24VDC sensor circuit |
||
|
Advanced and power expansion Module |
Power Module |
MPA024-24 |
– |
– |
|
MPA048-24 |
– |
– |
||
|
IO Coupler |
Network type IO Coupler |
MC0EN |
80mA |
– |
|
Local I/O expansion Module |
Digital input Module |
M16X |
70mA |
7.5mA/point |
|
Digital output Module |
M16YT |
150mA |
Max.0.5A/point |
|
|
M16YJ |
163mA |
Max.0.5A/point |
||
|
M16YR |
190mA |
Max.2A/point |
||
|
Mixed digital input/output Module |
M1616XYT |
202mA |
X :7.5mA |
|
|
M1616XYJ |
222mA |
Y:0.5A/point |
||
|
Analog input Module |
M04AD |
78.2mA |
– |
|
|
M04ADR |
78.2mA |
– |
||
|
Analog output Module |
M04DA |
14.2mA |
107mA |
|
|
M04DAR |
14.2mA |
107mA |
||
|
AIO Combo Modules |
M0202AH |
22.58mA |
39.85mA |
|
|
Temperature measurement Module |
M04TC |
30.7mA |
– |
|
|
M04TCR |
30.7mA |
– |
||
|
M04RTD |
30mA |
– |
||
|
Temperature Measurement Combo Modules |
M0202TH |
30mA |
– |
|
|
Load cell Module |
M02LC |
40.64mA |
– |
|
|
M02LCR |
56.1mA |
– |
||
|
End Module |
MRE |
– |
– |
|
|
I/O Bus Extension Modules |
Repeater Modules |
MRPWE-AC |
– |
– |
|
I/O Bus Extension module(Head) |
MRGH |
– |
– |
|
|
I/O Bus Extension module(Tail) |
MRGT |
– |
– |
|
▲Module Power Consumption Table
1-3 Example of Power Capacity Calculation
The selection of the power module depends on the total current consumption of all modules that need to be powered. Therefore, it’s necessary to first determine the current consumption of each module. Referencing the table provided earlier, you can find the maximum current consumption for each expansion module. Before selecting a power module, calculate the total current consumption of all the modules you intend to use. When using them together, it’s essential to ensure that neither the power module nor any of the expansion modules are overloaded.
The table below presents the modules adopted by a system. Attempt to calculate the required power supply module for the system.
|
Type |
Power module |
CPU module |
Expansion module |
Expansion module |
Expansion module |
End module |
Spare capacity |
|
Name |
MPA024-24 |
MC0EN |
M16XX |
M16YT |
M04AD |
MRE |
|
|
Internal 24V circuit |
+1000mA |
-80mA |
-70mA |
-150mA |
-78.2mA |
– |
501.8mA |
|
External 24V sensor circuit |
-7.5mA*16point |
– |
– |
– |
➢ Power module – Internal 24V power supply – External 24V sensor power supply
【1000mA】–【80mA+70mA+150mA+78.2mA】-【(7.5mA*16)】=501.8mA
1-4 Power Sequencing Requirements for IO Coupler Power and Expansion
After the power is turned on, the IO Coupler detects the type and number of expansion modules connected to it to determine the configuration of the expanded I/O.
Therefore, during IO Coupler detection, the power to the expansion modules must be turned on and stable, otherwise incorrect I/O configuration results may be detected. In other words, the power to the expansion modules must be turned on simultaneously or earlier than the power to the IO Coupler.
When connecting the IO Coupler and expansion modules to the same power source, there won’t be any timing issues. However, if the power source for the expansion modules is different from that of the IO Coupler (or if they are controlled by different switches on the same power source), it’s important to pay attention to the timing of both power sources.