Required Software & Firmware

Ensure all PLC and module versions meet or exceed these baselines before setup.

Data Share can communicate with FBs and HMI.

Network Configuration Example

PLC Software Uperlogic_v1.0.19_installer
PLC OS Version 1_0_62 or later
CBEX OS Version CBEH2_CBES(G02)_CMES_V0302

Match subnet mask and gateway across PC and PLCs with unique host octets.

PC Ethernet Settings
IP Assignment Manual (Static)
IPv4 Address 192.168.2.100
Subnet Mask 255.255.255.0
Default Gateway 192.168.2.1
M PLC Ethernet Settings
DHCP Disabled
IPv4 Address 192.168.2.4 (Unique X)
Subnet Mask 255.255.255.0

Multi-PLC Communication Setup

Each PLC on the network must be assigned a distinct IPv4 address.

Parameter 1st PLC (Station 0) 2nd PLC (Station 1) Rule
DHCP Disabled Disabled Static IP required
IP Address 192.168.2.4 192.168.2.5 Must be unique per PLC
Subnet Mask 255.255.255.0 255.255.255.0 Identical across network
Gateway 192.168.2.1 192.168.2.1 Identical across network

Data Sharer Configuration

Double-click Server Configuration in UperLogic Project Management to open Data Sharer.

Parameter Description
Enable / Disable Enable or disable the Data Sharer service
Port Set UDP communication port (e.g., 9000; must match across all stations)
Local Station ID Assign local station ID from 0 to 15 (unique per node)
Command Interval (ms) Set register value broadcast interval in milliseconds (e.g., 1000 ms)
Receive Timeout (ms) Set timeout threshold for incoming station packets (e.g., 1500 ms)
Sync Method Select Period Sharer (cyclic) or Write Sharer (event-driven)

Data Mapping Parameters

Field Function & Register Range
Station ID Select target station 0 ~ 15 (hover input boxes to view valid register ranges)
Enable Address Control bit to start/stop station communication (e.g., M0)
Status Address Register storing status code: 0 = Normal, 1 = Duplicate ID, 2 = Timeout
Share Length Address Set communication index length (maximum 512 words)
Timeout Count Address Double register recording cumulative receive timeouts (e.g., DR4)
Send/Receive Count Double register tracking heartbeat packet counter (e.g., DR6)

Data Block & Register Alignment

Data mapping register offsets and lengths must match across communicating PLC.

Add: create new data group
DeIete: Remove selected group
Edit: Modify group registers
Distribution: View allocated map

Setting Example

Shared Memory Map ExampIe

Each station broadcasts its assigned register block across the LAN to form a unified memory image.

PLC Station A (Satation 0) PLC Station B (Satation 1 〕 PLC Station C (Satation 2〕
Shares D0~D9 Shares D10~D19 Shares D20~D29