Posted in

By

6 of 24Updated 2026-11-175 min read中文版

The FBS-PLC provides the ultra high speed differential double end 5VDC inputs (i.e., single input with two terminals without common) and the single-end 24VDC inputs which use the common terminal to save terminals. The response speeds of single-end common input circuits are available in high, medium and low. Because the double end input circuit has two independent terminals, it can be connected either in SINK or SOURCE for input or in differential input wiring for line driver source. The single-end input circuit can be set to SINK or SOURCE type by varying the wiring of the common terminals S/S inside PLC and external common wire of input circuits (see Sec. 6.3 for details).

6.1Specifications of Digital Input (DI) Circuit

Item

5VDC

High Speed

24VDC Single-end Input

Mid/Low Speed

Low Speed

Note

Differential

Specifications

Input

Medium Speed(HSC)

Ultra High

Speed(HSC)

(HSC)

Maximum input

920KHz

200KHz

20KHz (HHSC)

Total 5KHz (SHSC)

1 0.47 mS*

4.7 mS

frequency*/

accumulated time

Input Signal Voltage

5VDC±10%

24VDC±10%

*: Half of

Input
Current
Threshold

ON
Current OFF
Current

>11 mA

>8 mA

>4mA

>2.3mA

<2 mA

<1.5mA

<0.9mA

maximum

frequency while

Maximum Input

20mA

10.5mA

7.6mA

4.5 mA

A/B phase input

current

Input Status

Displayed by LED: Lit when “ON”, dark when “OFF”

* 1:Limit of input

Indication

Photocoupler signal isolation

Isolation Type

SINK/SOURCE

Independent Wiring

Via variation of internal common terminal S/S and external common wiring

Wiring

FBS-20MNR/T/J

X0,1

X4, 5, 8, 9

X2,3,6,7,10,11

FBS-32MNR/T/J

X0,1,4,5

X8, 9, 12, 13

X2,3,6,7,10,11,14,15

X16~19

X0,1,4,5,8,9,

X2,3,6,7,10,11,14,15

X16~27

FBS-44MNR/T/J

12,13

FBS-10MCR/T/J

X0,1

X4,5

X2,3

FBS-14MCR/T/J

X0,1

X4,5

X2,3,6,7

FBS-20MCR/T/J

X0,1,4,5

X8,9

X2,3,6,7,10,11

FBS-24MCR/T/J

X0,1,4,5

X8,9.12,13

X2,3,6,7,10,11

FBS-32MCR/T/J

X0,1,4,5,8,9

X12,13

X2,3,6,7,10,11,14,15

X16~19

FBS-40MCR/T/J

X0,1,4,5,8,9

X12,13

X2,3,6,7,10,11,14,15

X16~23

speed in MA

model is

FBS-60MCR/T/J

X0,1,4,5,8,9,12,13

X2,3,6,7,10,11,14,15

X16~35

10KHz

DHF:Digital

FBS-10MAR/T/J

X0,1,4,5

X2,3

FBS-14MAR/T/J

X0,1,4,5

X2,3,6,7

FBS-20MAR/T/J

X0,1,4,5,8,9

X2,3,6,7,10,11

FBS-24MAR/T/J

X0,1,4,5,8,9,12,13X2,3,6,7,10,11

FBS-32MAR/T/J

X0,1,4,5,8,9,12,13X2,3,6,7,10,11,14,15

X16~19

FBS-40MAR/T/J

X0,1,4,5,8,9,12,13X2,3,6,7,10,11,14,15

X16~23

FBS-60MAR/T/J

X0,1,4,5,8,9,12,13X2,3,6,7,10,11,14,15

X16~35

Expansion

All Input

Unit/Module

Points

R/T/J

Noise Filtering Time

DHF(0 ~ 15mS)

DHF(0 ~ 15mS)

DHF(0 ~

AHF(4.7ms)

Hardware Filter

15mS)

3
Constant*

+AHF(0.47µs)

+AHF(4.7µs)

AHF:Analog

+AHF(0.47µs)

Hardware Filter

6.2Structure and Wiring of 5VDC Ultra High Speed Differential Input Circuit

Only the MN main unit of FBs provides the 5VDC ultra high speed differential input circuit, which is mainly used for the input of hardware high speed counter (HHSC) with a maximum working frequency up to 920 KHz. In practice, to ensure the high speed and high noise immunity, please use Line-Driver for differential line driving. In environments with small noise and medium working frequency (<200KHz), however, it can be changed to the 5VDC single-end SINK or SOURCE input or to the 24VDC single-end SINK or SOURCE input by connecting a 3KΩ/0.5W resistor in series, as shown in the figure below.

(A) Wiring of 5VDC differential input for Line-Driver driving(with frequency up to 920KHz for high speed and environments with large noise)

FBs-MN main unit External differential output

A

Dual-end input

Twisted-pair

(Encoder) Line-Driver輸出

B

(B) Wiring of 5VDC differential input to 5VDC single SINK or SOURCE input

FBS-MN main unit

R1
X0+

R2

SINK input

NPN

SENSOR
X0

R1

5VDC

X1+

R2

SOURCE SOURCE輸入input

PNP

SENSOR

X1

(C) Method of converting 5VDC differential input to 24VDC single-end SOURCE input

FBS-MN主機FBs-MN main unit

R1
X0+

R2

SINK input SINK 輸入

NPN

SENSOR

X0
3KΩ/0.5W
R1:100Ω

R2:1.2KΩ

R1

3KΩ/0.5W

24VDC

X1+

R2

SOURCE

PNP

SENSOR

SOURCE輸入input

X1

6.324VDC Single-End Input Circuit and Wiring for SINK/SOURCE Input

The 24VDC single-end digital input circuits of FBS-PLC are available for high, medium and low speed. They all have the similar circuit structures but with different response speeds. To save input terminals, the circuit of single-end input is implemented by connecting one end of all input points (photo coupler) inside the PLC to the same internal common point labeled as S/S. The other end of each input circuit is connected to corresponding terminals such as X0, X1, X2, etc. The S/S common terminal and N single-end inputs comprise of N digital inputs (i.e., only N+1 terminals are used for N terminals). Therefore, we call this type of input structure the single-end input. The user also needs to do the same thing when making the connection of external digital input devices. Namely, the one end of all input devices (e.g., buttons, switches) are connected together and called the external common wire, while the other ends of input circuits are connected to the input terminals X0, X1, X2, etc., of PLC. Then finish it by connecting the external common wiring and internal common terminal S/S to the positive/negative terminals of the 24VDC power. When connect the internal common terminal S/S to 24V+(positive) and the external common wire to 24V- (negative), then the circuit serve as SINK input. On the contrary, while exchange the wiring of the above internal and external common will serve as a SOURCE input. The above wiring schemes can illustrated below:

z

Wiring of single-end common SINK input

X0

R1

R2

X1

R1

R2

X2

R1

R2

X3

R1

輸入元件Input devices

Low speed

External Common Wiring外部共線

External 外部

Power 電源

24VDC

NPN

Sensor

24V+

24V-

S/S

FBS
|

內部共點Internal

Common

Terminal 端子

R2

R1:5.6K

R2:1KΩ

PLC

24VDC

Middle speed

(not available in

expansion modules)

R1:3.3KΩ

R2:1.2KΩ

X0

X1

X2

X3

z Wiring of single-end common SOURCE input

External Common Wiring

External 外部

24VDC

24V+

24V-

PNP

X0

R1

R2

X1

R1

R2

X2

R1

R2

X3

R1

輸入元件Input Circuit

Power

Sensor

S/S

FBS

24VDC

Internal
內部共點Common

Terminal 端子

R2

|

PLC

(not available in (擴充模組無)

expansion modules)

X0

X1

X2

X3

Was this page helpful?

Tip: press ← → to switch chapters, Ctrl+K to search