⚠Danger

  1. When installing or removing the M-series CPU modules and various expansion modules or the equipment connected to it, all power must be turned off, otherwise it may cause electric shock or wrong action, resulting in death or serious personal injury and damage to the machine equipment.
  2. Before the installation and wiring construction is completed, do not tear off the dust-proof paper on the PLC cooling hole, so as to prevent the drilling iron filings or wiring scraps from falling into the PLC during construction, causing fire, failure or malfunction.
  3. After confirming that the installation and wiring are all completed, remember to tear off the above-mentioned dustproof paper to avoid poor heat dissipation of the PLC, resulting in fire, failure or malfunction.

This section describes how to set up the reports, link parameters and command tables. Through the user-friendly interface, it minimizes the complicated procedure when operated by the user. Provided below is the operation method of the respective table.

7-1 Table Management

7-1-1 Adding New Table

To add a table, please select [Table Edit] → [OOOO Table] → [New OOOO Table] in the project window, or select [Project] → [Table Edit] → [New OOOO Table], as shown below:

Fig. 134: Adiing a new table

After clicking [New OOOO Table], the table editing window will pop up allowing users to create table properties.

Item

Description

Type

The subcategory of the table, which varies from data table to data table.

Name

The name of the table

Start Address

The starting address to use for this table, which can be entered as a register or a label.

Length

The length used by the table data; the unit is a word group.

Table Capacity

Choose whether you want to dynamically adjust the table capacity or a fixed capacity limit:

  • Dynamic Allocation: Edit length changes with form content
  • Fixed length: Edit length must not exceed configured length

Load Table From PLC

To load corresponding link tables from PLC.

Load Table From ROR

To load corresponding link tables from ROR.

Description

Provides users the description of editing tables

7-1-2 Table Edit

After adding a table, you will enter the table data window. In addition, you can enter the table editing window from [Table Edit] → [OOOO Table] → [Name] in the project window, or click [Project] → [Table Edit] → [OOOO Table] → [Name].

Users can edit the command details for this form in this window.

Function

Description

Toolbar Section

Calculator

Calling the easy-to-use calculator installed in the Windows.

Setting

Calling the table edit window. It allows the user to rename the table or change the home address of such table.

Monitor

The execution status of form commands can be monitored. The monitoring content depends on different form types, and the content will be described in detail in subsequent chapters.

This function is only supported online and can be used by calling the Zooming function on the ladder diagram.

Table Data Section

Table data editing section, the content depends on different form types, and will be described in detail in subsequent chapters.

Status Section

Allow

The display table property is set to dynamic allocation or fixed length, and the maximum length is marked; the unit is a word group.

Used

Displays the length of the table command currently used, and the unit is a word group.

Position

Displays the address range currently used by table commands.

7-1-3 Rename

To change the name of the table, please select the table [Name] to be modified in [Table Edit] → [OOOO Table] in the project window, select [Rename] from the right-click menu or use the shortcut key “F2” to edit the name. In addition, you can directly enter the form editing window and change the name through editing properties.

7-1-4 Delete Table

To delete a table, please select [Table Edit] → [OOOO Table] in the project window, and select [Delete OOOO Table] from the right-click menu, or [Project] → [Table Edit] → [Delete OOOO Table] in the execution function bar, as shown in the figure below:

After the delete table window appears, select the table you want to delete and confirm. You can delete multiple selections.

7-1-5 Table Configuration Adjustment

Uperlogic provides a table overview function, which can be used to determine whether the addresses used in the tables overlap to avoid misuse during program execution. To use this function, please select [Table Configuration Adjustment] from the right-click menu in [Table Edit] in the project window, or [Project] → [Table Edit] → [Table Setting Adjustment] in the execution function bar.

Item

Description

Table

Display the basic properties of all tables of the current project.

If the start address is marked with [OOO], it means that the address uses a label as the start address.

Configuration

Enter the table editing window to modify the properties of the table.

Edit

Enter the table data window to modify the table data.

Delete

Delete the selected table.

Write to PLC

Write the current project table data to PLC.

Table Comparison

Compare the data in the current project table with the data in the PLC register.

Message

Shows whether the addresses currently used between tables have overlapping ranges.

7-2 Link Table

The main purpose of the link table is to facilitate users to fill in the data content of the communication command FUN151 CLINK. The [General Online Table] category corresponds to MD0. For other descriptions of corresponding commands, please refer to the advanced manual.

7-2-1 Table Value

The table data section of ​​[General Online Table] is as shown in the figure below. Users can edit individual commands of [General Online Table] through simple operations, and the content corresponds to the command Start Register (SR) on FUN151.

The operation description is shown as below:

Item

Description

Operation

New

After clicking, a row of commands will be added in the editing section for users to edit.

Delete

After clicking, delete the command currently selected by the user, and multiple selections can be deleted.

Move Up

After clicking, move the command currently selected by the user up one column.

Move Down

After clicking, move the command currently selected by the user down one column.

Right-Click Menu

Cut

After clicking, cut the command currently selected by the user, and multiple selections can be cut.

Copy

After clicking, copy the command currently selected by the user, multiple selections can be copied。

Paste

After clicking, paste the command previously copied or cut by the user.

Insert

After clicking, insert a row of commands at the selected position in the editor for users to edit.

Delete

After clicking, delete the command currently selected by the user, and multiple selections can be deleted.

Move Up

After clicking, move the command currently selected by the user up one column.

Move Down

After clicking, move the command currently selected by the user down one column.

The command data content is shown as below:

Item

Description

Data

No.

Display the command information of the Nth.

Command

Edit this command action as [Read] or [Write]

Slave

Edit the station number of the slave station to communicate.

Master Data

Edit the data starting address of the Master station.

Slave Data

Edit the data starting address of the Slave station.

Data Size

The data size of such command

Operation

Display this command as [Bit Operation] or [Word Group Operation]

7-2-2 Table Monitoring

The monitoring of [General Online Table] is as shown in the figure below. Users need to be online and call the Zooming function on FUN151 to use it. The content corresponds to the command operation start register (WR) on FUN151.

Item

Description

Result Code

Shows the operating result.

00H: Normal

Other values: Error

Operation No.

Indicates that the Nth transaction is in operation.

Station No.

Indicates the station number of the slave station currently in communication.

Command Code

40H: Read slave PLC system status.

44H: Read the status of multiple consecutive single points of the slave PLC.

45H: Write the state of multiple consecutive single points of the slave PLC.

46H: Read the status of multiple consecutive registers of the slave PLC.

47H: Write the status of multiple registers in the slave PLC.

7-3 Servo Parameter Table

The main purpose of the servo parameter table is to facilitate the user to fill in the data content of the positioning program parameter setting command FUN141 MPARA. For the description of the corresponding command, please refer to the advanced manual.

7-3-1 Table Value

The table data section of ​​[Servo Parameter Table] is as shown in the figure below, users can edit individual parameters of [Servo Parameter Table] through simple operations, and the content corresponds to the command start register (SR) on FUN141.

Fig. 135: Editing Servo Parameter Table

Parameter

Item

Description

0

Unit Setting

The unit used for the travel and speed settings used in the program.

When the setting value is 0, the unit is mm, Deg, Inch, which is called the mechanical unit.

When the setting value is 1, the unit is Pulse, which is called the motor unit.

When the setting value is 2, the setting value is in mm, Deg, Inch, and the speed setting is in Pulse, which is called compound unit.

1

Ps/Rev

The number of pulses (A) required for one revolution of the motor.

The range is 1~65535 Ps/Rev (when it is above 32767, set it with decimal positive number)

When parameter 14 = 0, take parameter 1 as Ps/Rev.

When parameter 14 ≠ 0, take parameter 14 as Ps/Rev.

2

μM/Rev

The distance (B) driven by the motor for one revolution.

The range is 1~999999 μM/Rev (mDeg/Rev, 0.1 mInch/Rev).

3

Min. Setting Unit

Setting Value

Mechanical/Compound Unit

Motor Unit

mm

Deg

Inch

Ps

0

x1

x1

x0.1

x1000

1

x0.1

x0.1

x0.01

x100

2

x0.01

x0.01

x0.001

x10

3

x0.001

x0.001

x0.0001

x1

4

Max. Speed Setting

Motor and compound unit: 1-921600 Ps/Sec

Mechanical unit: 1-153000 (cm/Min, x10 Deg/Min, Inch/Min),

but the maximum frequency can not be greater than 921600 Ps/Sec.

5

Start/Stop Speed

Motor and compound unit: 1-921600 Ps/Sec。

Mechanical unit: 1-15300 (cm/Min, ×10 Deg/Min, Inch/Min), but the maximum frequency can not be greater than 921600 Ps/Sec。

6

Return-to-origin Deceleration Speed

Motor and compound unit: 1-65535 Ps/Sec

Mechanical unit: 1-15300 (Cm/Min, x10 Deg/Min, Inch/Min)

7

Gear Backlash Correction Value

Setting scope: 0-32767 Ps

When walking in reverse, the walking distance will automatically add this value。

8

Acceleration and Deceleration Time Setting

Setting scope: 0-30000 ms。

The time represents the one required to accelerate from rest to maximum speed (parameter 4), or decelerate from maximum speed to rest. When parameter 12=0, this parameter is used as the deceleration time.

9-0

Direction of Operation

When the setting value=0, forward pulse output, the current Ps value will increase; the reverse pulse output, and the current Ps value will decrease.

When the set value=1, the forward pulse output and the current Ps value will decrease; the reverse pulse output and current Ps value will increase.

9-1

Return-to-origin Direction

When the set value=0, the return-to-origin direction is the current Ps value plus the upward direction (the origin is on the right).

When the setting value=1, the return-to-origin direction is the current Ps value minus downward direction (the origin is on the left).

10

Forward Revolution Movement Correction Value

When outputting forward revolution pulse, this value will be automatically added as the moving distance; the range is −32768 – 32767 Ps.

11

Compensation Value of Reverse Movement Value

When switching to pulse wave output, this value will be automatically added as the moving distance; the range is −32768 – 32767 Ps.

12

Deceleration Time Setting

The range is 0-30000 ms.

When parameter 12=0, parameter 8 is used as the deceleration time.

When parameter 12≠0, parameter 12 is used as the deceleration time.

13

Interpolation Acceleration/Deceleration Time Setting

It is used to set the time required to accelerate from stillness (speed = 0) to the working frequency during linear interpolation motion; this time is also used for deceleration and stop control; the range is 0-30000 ms.

14

Ps/Rev

The range is 0 to 1999999.

y as parameter 14 = 0, take parameter 1 as Ps/Rev.

y as parameter 14 ≠ 0, take parameter 14 as Ps/Rev.

15-0

Proximity DOG Input Contact Setting

Can set [Normally Open], [Normally Closed] or [Not Used] input contact; contact number is X0-X15.

15-1

Stroke Limit Input Contact Setting

Can set [Normally Open], [Normally Closed] or [Not Used] input contact; contact number is X0-X125.

15-2

Zero-Point Signal PG0 Input Contact Setting

You can set [Upper Edge Count], [Lower Edge Count] or [Not Used] input contact; the contact number is X0-X15.

15-3

Zero-Clear Signal CLR Output Contact Setting

You can set [Use] or [Not Used] output contact; the contact number is Y0-Y23.

16

Mechanic Original-Point Position Value

The range is -999999-999999 Ps.

17

Zero-Point Signal Numbers

The range is 0-255 Count.

7-3-2 Table Monitoring

No monitoring function is provided to [Servo Parameter Table].

7-4 Servo Program Table

The main purpose of [Servo Program Table] is to facilitate the user to fill in the data content of the single-axis high-speed pulse output command FUN140 HSPSO. For the description of the corresponding command, please refer to the advanced manual.

7-4-1 Table Value

The table data section of ​​[Servo Program Table] is as shown in the figure below, users can edit individual commands of [Servo Program Table] through simple operations, and the content corresponds to the command start register (SR) on the FUN140.

Fig. 136: Setting Servo Program Table

The operation description is shown as below:

Item

Description

Operation

New

After clicking, a row of commands will be added in the editing section for users to edit.

Delete

After clicking, delete the command currently selected by the user, and multiple selections can be deleted.

Move Up

After clicking, move the command currently selected by the user up one column.

Move Down

After clicking, move the command currently selected by the user down one column.

Right-Click Menu

Cut

After clicking, cut the command currently selected by the user, and multiple selections can be cut.

Copy

After clicking, copy the command currently selected by the user, multiple selections can be copied。

Paste

After clicking, paste the command previously copied or cut by the user.

Insert

After clicking, insert a row of commands at the selected position in the editor for users to edit.

Delete

After clicking, delete the command currently selected by the user, and multiple selections can be deleted.

Move Up

After clicking, move the command currently selected by the user up one column.

Move Down

After clicking, move the command currently selected by the user down one column.

Command data description is shown as below:

Item

Description

Command

Speed

SPD

The frequency or speed of the pulse output can be directly input to a constant or register (R/D).

When FUN141 parameter 0=0, it is the speed;

When FUN141 parameter 0=1 or 2, it is the frequency.

Operation

DRV

Pulse Output amount.

When FUN141 parameter 0=1, the unit is Ps;

When FUN141 parameter 0=0 or 2, the unit is mm, Deg, Inch.

There are four instruction operands:

  • Select ADR or ABS for positioning coordinates:

A. ADR, relative value coordinate positioning.

B. ABS, absolute value coordinate positioning.

  • Select ‘+’ or ‘−’ for the operating direction:

A. ‘ + ‘, forward revolution or count up.

B. ‘ − ‘, reverse or count down.

  • The stroke setting value (pulse output value) can be directly input to a constant or a temporary register (R/D).
  • Stroke setting value resolution Ut or Ps:

A. For Ut, the resolution is determined by FUN141 parameter 0, 3.

B. For Ps, the mandatory resolution is one Ps.

DRVC

The usage is the same as DRV command.

DRVZ

As a convenient command for return-to-origin, three different methods of return-to-origin, MD0-MD2, are provided in total.

Wait

WAIT TIME

WAIT TIME (unit is 0.01 second) when the pulse output is completed. When the time is up, the number of steps indicated by GOTO will be executed; constants or registers (R/D) can be input directly.

WAIT

WAIT for input contact signal when pulse output is completed. When the input contact signal is ON, execute the steps indicated by GOTO.

ACT

After the action time described by the pulse output ACT, immediately execute the number of steps indicated by GOTO; the action time (unit: 0.01 second) can be directly input into a constant or register (R/D).

EXT

External trigger command, when the pulse is being output (the number of pulse waves has not been sent), if the external trigger signal is activated (ON), it will immediately execute the steps indicated by GOTO.

Go To

GOTO

When the condition of WAIT/ACT/EXT instruction is met, use GOTO instruction to describe the number of steps to be executed.

  • NEXT: To execute the next step.
  • A constant: The number of steps to execute.
  • Register (R/D): The number of steps to be executed is stored in the temporary register.

MEND

Positioning program finished.

7-4-2 Table Monitoring

The monitoring of [Servo Program Table] is shown in the figure below. Users need to be online and call the Zooming function on FUN140 to use it. The content corresponds to the command operation start register (WR) on FUN140.

Item

Description

Currently Working/Stopping Steps

If the command is being executed, the content value is the number of steps being executed (1~N);

If the instruction is not being executed, the content value represents the number of steps currently stopped.

Total Steps

Steps in total

Working Flag

Corresponds to flag of WR+1

B8 =ON, suspend output.

B9 =ON, wait for transition condition.

B10=ON, continuous operation (total output stroke is set to 0).

B12=ON, pulse output (output indication “ACT”).

B13=ON, command execution error (output indication “ERR”).

B14=ON, one-step positioning is completed (output indication “DN”).

Error Code

Error Codes of PSO 0-4

7-5 General Purpose Link Table

The main purpose of the [General Purpose Link Table] is to facilitate the user to fill in the data content of the communication command FUN151 CLINK, which corresponds to MD1/MD2. For the description of the corresponding command, please refer to the advanced manual.

7-5-1 Table Value

The table data section of ​​[General Purpose Link Table] is as shown in the figure below. Users can edit individual commands of [General Purpose Link Table] through simple operations, and the content corresponds to the command start register (SR) on FUN151.

The data content description is shown as below:

Item

Description

Parameter

Communication Mode

[Only sending/receiving messages]

When MD1 is only sending out messages, the other party does not respond; when MD2 is only receiving messages, there is no response.

[Receive message after sending or Send message after accepting]

MD1 is sending out a message, and then waiting to receive a response message from the other party; MD2 is receiving a message, and then sending out a response message.

Receive even if a communication error occurs

When checked, the receiving action will be performed whether there is a communication error or not.

The register uses only one bit of data

When checked, one data occupies one register; otherwise, two data temporarily occupy one register.

Start Code

Start code describing the message.

Finish Code

Finish code describing the message.

Command

Edit the content of the sent or received message.

The editing content can use decimal, hexadecimal and character strings, and the data must be separated by commas or blanks.

Preview

Preview the message content to be sent or received.

7-5-2 Table Monitoring

The monitoring of [General Purpose Link Table] is as shown in the figure below. Users need to be online and call the Zooming function on FUN151 to use it. The content corresponds to the command operation start register (WR) on FUN151.

Item

Description

Result Code

Shows the operating result.

00H: Normal

Other values: Error

7-6 Register Table

The register table function is mainly to provide users with fast batch writing of register values. Users can pre-plan the register table in the project, write in batches during the download process, or directly write in the new register table through online editing.

7-6-1 Table Value

The table data section of ​​[Register Table] is as shown in the figure below, users can edit individual commands of [Register Table] through simple operations, and plan the register values ​​in advance.

Fig. 137: Setting Register Table

The operation description is shown as below:

Item

Description

Operation

New

After clicking, a row of commands will be added in the editing section for users to edit.

Delete

After clicking, delete the command currently selected by the user, and multiple selections can be deleted.

Move Up

After clicking, move the command currently selected by the user up one column.

Move Down

After clicking, move the command currently selected by the user down one column.

Right-Click Menu

Cut

After clicking, cut the command currently selected by the user, and multiple selections can be cut.

Copy

After clicking, copy the command currently selected by the user, multiple selections can be copied。

Paste

After clicking, paste the command previously copied or cut by the user.

Insert

After clicking, insert a row of commands at the selected position in the editor for users to edit.

Delete

After clicking, delete the command currently selected by the user, and multiple selections can be deleted.

Move Up

After clicking, move the command currently selected by the user up one column.

Move Down

After clicking, move the command currently selected by the user down one column.

The command data description is shown as below:

Item

Description

Command

No.

The address of the register to be written in batches.
Counting from the start address of the table, the No. will be automatically adjusted as the data type is word group or double word-group.

Data Type

Divided into word group (16Bits) and double word-group (32Bits).

Data

The data to be written into the register can be filled in decimal, hexadecimal or string.

In decimal, just fill in the decimal number, EX: 1234.

For hexadecimal, fill in the hexadecimal number, and fill in ‘H’ at the last character. EX: 1234H.

String, just fill in ASCII characters in the quotation marks, EX: ‘By’.

Description

Optionally fill in a description for the command.

7-6-2 Table Monitoring

No monitoring function is provided to [Register Table].

7-7 Modbus Master Table

The main purpose of the [Modbus Master Table] is to facilitate the user to fill in the data content of the communication command FUN150 M-BUS. For the description of the corresponding command, please refer to the advanced manual.

7-7-1 Table Value

The table data section of ​​[Modbus Master Table] is as shown in the figure below, users can edit individual commands of [Modbus Master Table] through simple operations, and the content corresponds to the command start register (SR) on the FUN150.

Fig. 138: Setting Modbus Master Table

The operation description is shown as below:

Item

Description

Operation

New

After clicking, a row of commands will be added in the editing section for users to edit.

Delete

After clicking, delete the command currently selected by the user, and multiple selections can be deleted.

Move Up

After clicking, move the command currently selected by the user up one column.

Move Down

After clicking, move the command currently selected by the user down one column.

Right-Click Menu

Cut

After clicking, cut the command currently selected by the user, and multiple selections can be cut.

Copy

After clicking, copy the command currently selected by the user, multiple selections can be copied。

Paste

After clicking, paste the command previously copied or cut by the user.

Insert

After clicking, insert a row of commands at the selected position in the editor for users to edit.

Delete

After clicking, delete the command currently selected by the user, and multiple selections can be deleted.

Move Up

After clicking, move the command currently selected by the user up one column.

Move Down

After clicking, move the command currently selected by the user down one column.

The command data content is shown as below:

Item

Description

Data

No.

Display the command information of the Nth.

Command

Edit this command action as [Read] or [Write]

Slave

Edit the station number of the slave station to communicate.

Master Data

Edit the data starting address of the Master station.

Slave Data

Edit the data starting address of the Slave station.

Data Size

The data size of such command

Operation

Display this command as [Bit Operation] or [Word Group Operation]

7-7-2 Table Monitoring

The monitoring of [Modbus Master Table] is as shown in the figure below. Users need to be online and call the Zooming function on FUN150 to use it. The content corresponds to the command operation start register (WR) on FUN150.

Item

Description

Result Code

Shows the operating result.

00H: Normal

Other values: Error

Operation No.

Indicates that the Nth transaction is in operation.

Station No.

Indicates the station number of the slave station currently in communication.

Command Code

01H: Read the status of multiple consecutive single points 0xxxxx of the slave station.

02H: Read the status of multiple consecutive single points 1xxxxx of the slave station.

03H: Read the status of multiple consecutive registers 4xxxxx of the slave station.

04H: Read the status of multiple consecutive registers 3xxxxx of the slave station.

05H: Write a single-point 0xxxxx status to the slave.

06H: Write single register 4xxxxx data to the slave station.

0FH: Write consecutive multiple single points 0xxxxx status to the slave station

10H: Write consecutive multiple registers 4xxxxx data