Required Software & Firmware
Ensure all PLC and module versions meet or exceed these baselines before setup.
Data Share can communicate with FBs and HMI.
Network Configuration Example
| PLC Software | Uperlogic_v1.0.19_installer |
| PLC OS Version | 1_0_62 or later |
| CBEX OS Version | CBEH2_CBES(G02)_CMES_V0302 |
Match subnet mask and gateway across PC and PLCs with unique host octets.
| PC Ethernet Settings |
| IP Assignment | Manual (Static) |
| IPv4 Address | 192.168.2.100 |
| Subnet Mask | 255.255.255.0 |
| Default Gateway | 192.168.2.1 |
| M PLC Ethernet Settings |
| DHCP | Disabled |
| IPv4 Address | 192.168.2.4 (Unique X) |
| Subnet Mask | 255.255.255.0 |
Multi-PLC Communication Setup
Each PLC on the network must be assigned a distinct IPv4 address.
| Parameter | 1st PLC (Station 0) | 2nd PLC (Station 1) | Rule |
| DHCP | Disabled | Disabled | Static IP required |
| IP Address | 192.168.2.4 | 192.168.2.5 | Must be unique per PLC |
| Subnet Mask | 255.255.255.0 | 255.255.255.0 | Identical across network |
| Gateway | 192.168.2.1 | 192.168.2.1 | Identical across network |
Data Sharer Configuration
Double-click Server Configuration in UperLogic Project Management to open Data Sharer.


| Parameter | Description |
| Enable / Disable | Enable or disable the Data Sharer service |
| Port | Set UDP communication port (e.g., 9000; must match across all stations) |
| Local Station ID | Assign local station ID from 0 to 15 (unique per node) |
| Command Interval (ms) | Set register value broadcast interval in milliseconds (e.g., 1000 ms) |
| Receive Timeout (ms) | Set timeout threshold for incoming station packets (e.g., 1500 ms) |
| Sync Method | Select Period Sharer (cyclic) or Write Sharer (event-driven) |
Data Mapping Parameters

| Field | Function & Register Range |
| Station ID | Select target station 0 ~ 15 (hover input boxes to view valid register ranges) |
| Enable Address | Control bit to start/stop station communication (e.g., M0) |
| Status Address | Register storing status code: 0 = Normal, 1 = Duplicate ID, 2 = Timeout |
| Share Length Address | Set communication index length (maximum 512 words) |
| Timeout Count Address | Double register recording cumulative receive timeouts (e.g., DR4) |
| Send/Receive Count | Double register tracking heartbeat packet counter (e.g., DR6) |
Data Block & Register Alignment
Data mapping register offsets and lengths must match across communicating PLC.




Setting Example

Shared Memory Map ExampIe
Each station broadcasts its assigned register block across the LAN to form a unified memory image.
| PLC Station A (Satation 0) | PLC Station B (Satation 1 〕 | PLC Station C (Satation 2〕 |
| Shares D0~D9 | Shares D10~D19 | Shares D20~D29 |