Chapter 3 Function/Function Block Program

In this chapter, it will introduce how to create a FCM program in UperLoigc, set FCM parameters and properties.

3-1 Create a new Project

Step 1. Select the【Menu】in the upper left corner of UperLogic. >【New】

mplc-m09-en-03 - 1

Step 2. The PLC module selection window pops up ① Select product Series (Select the ME series in the picture below) ② Select Model (Select ME3C6-1616 in the picture below)

mplc-m09-en-03 - 2

Step 3. Set project information ③ Select programming language (Select the ladder in the picture below) ① Finish

mplc-m09-en-03 - 3

Step 4. After finish, the main program unit editing screen will be displayed.

mplc-m09-en-03 - 4

3-2 Add A New FCM Program

Step 1. Select 【Project Management】in the Uperlogic>【Program Unit】>【FCM Program】>Right click> 【FCM Program Add】

mplc-m09-en-03 - 5

Step 2. Pops up【FCM Property】setting windows > Set【FCM Property】 > After the setting is completed, press [OK] to complete the new FCM program. (Please refer to Chapter 3-4 for FCM properties.)

mplc-m09-en-03 - 6

3-3 FCM Variable

FCM has independent internal relays and internal registers. Internal variables can only be used in FCM program. Some internal relays and internal registers can exchange data with external program unit registers. These are local variables, only valid within the specific FCM. Each time the FCM is executed, it has its own independent variable space, ensuring that the function block can be reused without affecting other logic.

[Note] When encapsulating the FCM function block, it is important to pay attention to the use of global register types, such as R/D/M. Avoid misuse and accessing duplicate register locations in other programs during calls, as this may cause logic malfunctions. To fully encapsulate the FCM, only the following types of variables must be used within the FCM program.

FCM Variable:

ITEM

Bit

VAR_SIG_IN

Input Pin

VAR_SIG_OUT

Output Pin

VAR_TEMP

Internal Variable Temp Bit

VAR_STATIC

Internal Variable Static Bit

WORD

VAR_PARA_IN

Input Parameter

VAR_PARA_OUT

Output Parameter

VAR_PARA_INOUT

Input /Output Parameter / internal Variable Static Word

VAR_TEMP

internal Variable Temp Word

mplc-m09-en-03 - 7

3-4 FCM Property

FCM Property

mplc-m09-en-03 - 8

• Program Unit Name : Function/Function Block Program Name。(English and Number Only)

• Language: Editing Language of Function/Function Block Program, e.g., LD(Ladder),ST, etc.。

• Number of Input : Number of Function/Function Block Program Input Pins。

• Number of output: Number of Function/Function Block Program Output Pins。

• Number of Parameter : Number of Function/Function Block Program Parameters。

• +VAR_STATIC: Add Internal Static Variable

• +VAR_TEMP: Add Internal Temp Variable

• Variable : Set the Name, Data Type, Array, Class, Initial Value of the variable.

3-4-1 Variable Name

All variables can be modified to have names that are a mixture of English and numbers, except for EN, which is used as the Function instruction trigger pin, so it has a fixed name. Use different background colors to distinguish different types of variables.

Variable Name

Variable

Length

Color of Background

EN

20 words by English letters and numbers

Red

Input

20 words by English letters and numbers

Yellow

Output

20 words by English letters and numbers

Green

Parameter

20 words by English letters and numbers

Blue

STATIC Variable

20 words by English letters and numbers

White

TEMP Variable

20 words by English letters and numbers

White

3-4-2 Variable Class

These are local variables, only valid within the specific FCM. Each time the function block is executed, it has its own independent variable space, ensuring that the FCM can be reused without affecting other logic.

Variable Class

Variable

Class

Description

Symbol

EN

VAR_SIG_IN

The pin that triggers FCM execution in the

mplc-m09-en-03 - 9

program unit.

When FCM is executed, it receives the bool status

from the program unit.

Input

VAR_SIG_IN

When FCM is executed, it receives the bool status from the program unit.

mplc-m09-en-03 - 10

Output

VAR_SIG_OUT

Output the Bool status of the FCM operation result

to the program unit

mplc-m09-en-03 - 11

Parameter

VAR_PARA_IN

When FCM is executed, it receives the value from

the program unit.

mplc-m09-en-03 - 12

* Mark【I】means IN type

VAR_PARA_OUT

Output the value of the FCM operation result to

the program unit

mplc-m09-en-03 - 13

*Mark【O】means OUT type

VAR_PARA_INOUT

When FCM is executed, it first receives the value

from the program unit.

When the FCM operation is completed, Output the

value of the FCM operation result to the program

unit

mplc-m09-en-03 - 14

* Mark【I】means IN type

*Mark【O】means OUT type

STATIC Variable

VAR_STATIC

The life cycle of VAR_STATIC lasts from the moment

the FCM is called, which means the result from the

last call will remain and be available in the next call.

TEMP Variable

VAR_TEMP

The life cycle of VAR_TEMP ends at the time the

FCM returns.

[Note] When encapsulating the FCM function block, it is important to pay attention to the use of global register types, such as R/D/M. Avoid misuse and operations that access duplicate register locations in other programs during calls, as this may cause logic malfunctions. To fully encapsulate the FCM, only the aforementioned types of variables must be used within the FCM program.

STATIC BIT:

• The life cycle of VAR_STATIC lasts from the moment the FCM is called, which means the result from the last call will remain and be available in the next call.

• Static bit is only initialized once at the first call of the FCM

VAR_STATIC BIT : VAR_STATIC (Bool) VAR_ STATIC WORD : VAR_PARA_INOUT

TEMP BIT:

• The life cycle of VAR_TEMP ends at the time the FCM returns.

• Temp bit is re-initialized at each cycle

VAR_TEMP BIT : VAR_TEMP (Bool) VAR_TEMP WORD : VAR_TEMP (16Bit-Int, 16Bit-Uint, 32Bit-Int, 32Bit-Uint, Float)

mplc-m09-en-03 - 15

STATIC BIT & TEMP BIT initialization timing diagram

3-4-3 Variable Data Type

Variable Data Type

Variable

Data Type

Description

EN

Bool

High Level Trigger

Bool, Pulse Rising

Rising Edge Trigger

Input

Bool

Output

Bool

Parameter

16Bit-Int, 16Bit-Uint, 32Bit-Int, 32Bit-Uint, Float

Pointer

Class must be VAR_PARA_INOUT

STATIC Variable

Bool

TEMP Variable

Bool, 16Bit-Int, 16Bit-Uint, 32Bit-Int, 32Bit-Uint, Float

Trigger type of EN

High Level Trigger (Bool): Which runs a particular FCM when EN is ON. Rising Edge Trigger (Bool, Pulse Rising): Which runs a particular FCM at the moment when EN changes

the status from OFF to ON. Edge trigger function is more efficient than Level trigger function because Edge trigger function is only executed at the rising edge of EN signal. This can significantly reduce system loading.

Example: In chapters 3-5, If the user wants to calculate the water level depth, the rising edge only needs to trigger the execution of the Container function once. If high level trigger, the Container function will be executed once in each scan cycle.

Pointer parameter vs Regular parameter

【Pointer parameter】 VAR_PARA_INOUT (Pointer) 1. The memory address of the parameter is passed into the FCM. (Call by Reference)

2. Pointer parameter doesn't need to have an initial value as FCM always reads value from the memory address. 3. the FCM program changes the value of parameter directly.

*Only when the parameter is used as VAR_PARA_INOUT can select the【Pointer parameter】.

【Regular parameter】 VAR_PARA_INOUT (16Bit-Int, 16Bit-Uint, 32Bit-Int, 32Bit-Uint, Float)

1. Only the value of parameter is copied to the temp memory of FCM. (Call by Value) 2. Regular parameter can be initialized either with an initial value or the value passed from main

program

3. The FCM program changes the value passed from the parameter doesn’t affect the value of parameter. (Ex. If R0 is regular parameter, R0 value is not changed during the FCM life.)

【Multi-cycle instruction】

Multi-cycle instructions run in the background and don't end with scan cycle. INOUT type parameter will then get unexpected value from unmanaged memory. So multi-cycle instructions must use 【Pointer parameter】to run.

*Please refer to Appendix 1 Multi-cycle Instruction

3-4-4 Variable Array

Array serves as a way to pass a list of registers into and out of the FCM memory.

Array

Variable

Class

Array

Description

Number of

VAR_PARA_INOUT

PAR [0…199]

Maximum length is 200.

Parameter

*Array INOUT parameter behavior is the same as Pointer INOUT parameter (Please refer to 3-4-3 Variable Data Type)

Example:

Set a VAR_PARA_INOUT parameter and set 5 lengths of Array. Fill in R0 in the FCM instruction PAR.

mplc-m09-en-03 - 16

mplc-m09-en-03 - 17

When EN triggers the FCM Function Instruction, pass ARRAY into the FCM Function Instruction

Main Unit Function Instruction

R0 → PAR[0]

R0

→

PAR[0]

R1

→

PAR[1]

R2

→

PAR[2]

R3

→

PAR[3]

R4

→

PAR[4]

When the FCM Function Instruction operation is completed, ARRAY is passed out of the FCM Function Instruction.

Main Unit

Function Instruction

R0

R1

R2

R3

R4

← PAR[0]

← PAR[1]

← PAR[2]

← PAR[3]

← PAR[4]

3-4-5 Variable Initial Value

Setting the initial value of FCM variables

• IN parameters don’t need to have an initial value as the main program always pass a value to IN parameter (Register or constant)

• OUT parameters has to be initialized with an initial value

• INOUT parameters can be initialized either with an initial value or with a value passed from main program

• Static variables are only initialized with initial values when FCM is executed for the first time.

Variable Initial Value

Variable

Class

symbol

Value

EN

VAR_SIG_IN

—

Input

VAR_SIG_IN

—

Output

VAR_SIG_OUT

Initialized every time when

mplc-m09-en-03 - 18

Determine the data type of the initial value based on the data type of the variable

FCM is executed

Parameter

VAR_PARA_IN

—

VAR_PARA_OUT

Initialized every time when

mplc-m09-en-03 - 19

Determine the data type of the initial value based on the data type of the variable

FCM is executed

VAR_PARA_INOUT

Initialized every time when FCM is executed

mplc-m09-en-03 - 20

Determine the data type of the initial value based

on the data type of the variable or turn off the

initialization function and initialize it with the

value passed by the main program unit.

*Fill in the blank value to indicate [DISABLE],

without initialization.

STATIC Variable

VAR_STATIC

Only initialized the first time

mplc-m09-en-03 - 21

Determine the data type of the initial value based on the data type of the variable

when FCM is executed

TEMP Variable

VAR_TEMP

Initialized every time when

mplc-m09-en-03 - 22

Determine the data type of the initial value based

on the data type of the variable

FCM is executed

3-5 Function/Function Block Instruction (Using FCM)

F The FCM instruction is the same as the general Function instruction. Trigger the EN pin by different conditions to execute the FCM instruction. The FCM instruction will execute the ladder program of the FCM based on the input pin status and input parameter value, and then put the operation results into the output parameters and output pins to provide subsequent control to the program unit.

mplc-m09-en-03 - 23

Trigger the EN of FMC Function Instruction

FCM reads input pin status and input parameter values

FCM puts the value into the FCM internal register

FCM operation execution

FCM outputs the internal register of the operation result to the output pin and output parameter

Wait for next trigger

3-5-1 Function Block vs Function

Function Functions are code blocks or subroutines without dedicated memory. Each starts from the initial value.

Trigger the EN of Function (Using FCM)

Function reads input pin status and input parameter values

Function puts the value into the FCM internal register

FCM operation execution

Function outputs the internal register of the operation result to the output pin and output parameter

Wait for next trigger

Function Block Function block are code blocks that store their values permanently in instance code blocks, so they remain available after the block has been executed. The next execution can continue with the previous results.

* Please refer to Chapter 3-4-2

Trigger the EN of Function Block (Using FCM)

Function Block reads input pin status, input parameter values, in/output parameter values(Inculde Pointer and

Array), Static Bit

Function Block puts the value into the FCM internal register

FCM operation execution

Function Block outputs the internal register of the operation result to the output pin, output parameter,

in/output parameter values(Inculde Pointer and Array), Static Bit

Wait for next trigger

3-6 Function Program Sample

3-6-1 Water Container

Application A cube-like water container with fixed inside length and width. Make a function which be able to calculate the depth of water according to the water volume parameter. If the volume is over 6000ml, high limit alarm is ON. If the volume is less than 1000ml, low limit alarm is ON.

Function Instruction

mplc-m09-en-03 - 24

Input/Output Pins and Parameters

Parameter

Name

Description

Input Pins

EN.P

Rising edge trigger

Output Pins

HLMT

High limit alert

LLMT

Low limit alarm

Input Parameters

Lvol

Water Level volume

Output Parameters

LDep

Water Level depth

Function Property 1 number of input (input pin), 2 numbers of output (output pin), 2 numbers of parameter, 3 VAR_TEMPs.

mplc-m09-en-03 - 25

Varialbe

Name

Data Type

Array

Class

Initial Value

Description

EN.P

Bool; Pulse Rising

—

VAR_SIG_IN

—

Rising edge trigger

HLMT

Bool

—

VAR_SIG_OUT

Initialized to 0 every time

High limit alert

LLMT

Bool

—

VAR_SIG_OUT

Initialized to 0 every time

Low limit alarm

Lvol

16Bit-Int

DISABLE

VAR_PARA_IN

—

Water Level volume

LDep

16Bit-Int

DISABLE

VAR_PARA_OUT

Initialized to 0 every time

Water Level depth

BoxW

16Bit-Int

—

VAR_TEMP

Initialized to 20 every time

The width of the box is fixed at

20 units

BoxL

16Bit-Int

—

VAR_TEMP

Initialized to 50 every time

The length of the box is fixed at

50 units

TP0

16Bit-Int

—

VAR_TEMP

Initialized to 0 every time

For calculation

Function Internal Program 【Container】

mplc-m09-en-03 - 26

N000 Use Fun171 to compare the input Lvol (water level volume) and trigger HLMT (output upper

limit alarm) when it exceeds 6000 units.

N001 Use Fun172 to compare the input Lvol (water level volume) and trigger the LLMT (output lower

limit alarm) when it is lower than 1000 units.

N002 If the input Lvol (water level volume) does not exceed HLMT (high limit alarm) and is lower than

LLMT (lower limit alarm), divide Lvol (water level volume) by the width and length of the container to calculate LDep (water level depth), and output it to the outside.

Function Internal Program in ST Language

IF Lvol > 6000 THEN HLMT := TRUE; END_IF

IF Lvol < 1000 THEN LLMT := TRUE; END_IF

IF NOT HLMT AND NOT LLMT THEN TP0:= Lvol / BoxW; LDep:= TP0 / BoxL; END_IF

behavioral description 【Container】

mplc-m09-en-03 - 27

Step 1. Enter Lvol (water level volume) in R0

Step 2. Trigger EN.P of the Function instruction with M0 (Rising edge trigger)

Step 3. R10 will display the calculated LDep (water level depth) or High and low limit alarm

(HLMT/LLMT) output alarm

Multiple use Multiple use of Function instructions in the main program

mplc-m09-en-03 - 28

N000 Input 1000 units of water volume and output 1 unit of water depth. N001 Input 2000 units of water volume and output 2 units of water depth.

The result of 2 FCMs not interfering with each other.

3-7 Function Block Program Sample

3-7-1 TV Remote

Application A TV remote controls the sound volume of TV and can be adjusted based on its previous volume. The volume value ranges from 0~10.

Function Block Instruction

mplc-m09-en-03 - 29

Input/Output Pins and Parameters

Parameter

Name

Description

Input Pins

EN

High Level Trigger

VolUp

Volume Up

VolDn

Volume Down

Output Pins

Max

Volume is Max

Mute

Volume is Mute

Input/Output Parameters

Volume

Volume

Function Block Property 3 numbers of input (input pins), 2 numbers of output (output pins), and 1 number of parameter.

mplc-m09-en-03 - 30

Variable

Name

Data Type

Array

Class

Initial Value

Description

EN

Bool

—

VAR_SIG_IN

—

High Level Trigger

VolUp

Bool

—

VAR_SIG_IN

—

Volume Up

VolDn

Bool

—

VAR_SIG_IN

—

Volume Down

Max

Bool

—

VAR_SIG_OUT

Initialized to 0 every time

Volume is Max

Mute

Bool

—

VAR_SIG_OUT

Initialized to 0 every time

Volume is Mute

Volume

16Bit-Int

DISABLE

VAR_PARA_INOUT

DISABLE

Volume

*The volume here uses VAR_PARA_INOUT to remember the last volume. Input the last volume from the external register to the Function Block when executing the Function Block. At the end of the Function Block, the volume is output to the external register for use when the Function Block is executed next time.

Function Block Internal Program 【TV Remote】

mplc-m09-en-03 - 31

N000 When VolUp is triggered at rising-edge, we use Fun15 to increase volume. N001 When VolDn is triggered at rising-edge, we use Fun16 to decrease volume.

The above operations work shall work exclusively in this case.

N002 With the use of Fun171, the volume will remain at 10 and set Max as ON at the same time when

over 9

N003 With the use of Fun172, the volume will remain at 0 and set Mute as ON at the same time when

under 1.

Function Block Internal Program in ST Language

IF R_TRIG( S:=VolUp ) THEN IF NOT VolDn THEN Volume:= Volume+1; END_IF END_IF

IF R_TRIG( S:=VolDn ) THEN IF NOT VolUp THEN Volume:= Volume-1; END_IF END_IF

if Volume > 9 THEN Max:=TRUE; Volume:=10; ELSEIF Volume < 1 THEN Mute:=FALSE; Volume:=0; END_IF

Action Description

mplc-m09-en-03 - 32

Step 1. Trigger VolUp (volume up) or VolDn (volume down) to increase/decrease the volume.

Step 2. The Volume up to 10 and can't continue to increase.

Step 3. The Volume down to 0 and can't continue to decrease.

Multiple use Multiple use of Function Block instructions in the main program

mplc-m09-en-03 - 33

N000 Control the R10 of volume N001 Control the R110 of volume The result of 2 FCMs not interfering with each other.

3-7-2 TV Remote Timer

Application The TV remote example can only be increase/decrease volume one unit per time. The real TV remote allows user to increase volume faster as the button pressed longer. Volume value range from 0~500.

Function Block Instruction

mplc-m09-en-03 - 34

Input/Output Pins and Parameters

Parameter

Name

Description

Input Pins

EN

High Level Trigger

VolUp

Volume Up

VolDn

Volume Down

Output Pins

Max

Volume is Max

Mute

Volume is Mute

Input/Output Parameters

Volume

Volume

TCv1

For Fun87 Timer

TCv2

For Fun87 Timer

Function Property 3 numbers of input (input pins), 2 numbers of output (output pins), and 3 numbers of parameter.

mplc-m09-en-03 - 35

Variable

Name

Data Type

Array

Class

Initial Value

Description

EN

Bool

—

VAR_SIG_IN

—

High Level Trigger

VolUp

Bool

—

VAR_SIG_IN

—

Volume Up

VolDn

Bool

—

VAR_SIG_IN

—

Volume Down

Max

Bool

—

VAR_SIG_OUT

Initialized to 0 every time

Volume is Max

Mute

Bool

—

VAR_SIG_OUT

Initialized to 0 every time

Volume is Mute

Volume

16Bit-Int

DISABLE

VAR_PARA_INOUT

DISABLE

Volume

TCv1

Pointer

—

VAR_PARA_INOUT

—

For Fun87 Timer CV

TCv2

Pointer

—

VAR_PARA_INOUT

—

For Fun87 Timer CV

BtnP

Bool

—

VAR_TEMP

Initialized to 0 every time

Add_S

Bool

—

VAR_TEMP

Initialized to 0 every time

Add_M

Bool

—

VAR_TEMP

Initialized to 0 every time

Add_L

Bool

—

VAR_TEMP

Initialized to 0 every time

T_200ms

Bool

—

VAR_STATIC

Initialized to 0 on the first time

For Fun87 Timer out

*The volume here uses VAR_PARA_INOUT to remember the last volume. Input the last volume from the external register to the Function Block when executing the Function Block. At the end of the Function Block, the volume is output to the external register for use when the Function Block is executed next time.

*The example uses the multi-cycle instruction Fun87. In order to allow TIMER's timing and output status to span multiple scan times in the Function Block, Fun87's CV uses Pointer(VAR_PARA_INOUT),Fun87's out pin uses VAR_STATIC BIT.

Function Internal Program 【TV Remote_Timer】

mplc-m09-en-03 - 36

mplc-m09-en-03 - 37

N000 Connect VolUp and VolDn in parallel into a BtnP signal N001 In VolUp or VolDn is ON, Fun87 is used to generate a 200ms pulse. N002 In VolUp or VolDnON, use Fun87 timing. N003 Fun87_TCv2 outputs Add_S when the timer reaches 1 second N004 F Fun87_TCv2 outputs Add_M when the timer reaches 1.5 seconds N005 Fun87_TCv2 outputs Add_L when the timer reaches 2 seconds N006 VolUp ON. Rising edge increases volume. N007 Keep pressing VolUp for more than 1 second, and use 200ms pulses to increase differently

according to Fun87_TCv2.

N008 VolDn ON, Rising edge lowers the volume. N009 Keep pressing VolDn for more than 1 second, and use 200ms pulses to increase differently

according to Fun87_TCv2.

N0010 With the use of Fun171, the volume will remain at 500 and set Max as ON at the same time

when over 499.

N0011 With the use of Fun172, the volume will remain at 0 and set Mute as ON at the same time when

under 1.

Function Internal Program in ST Language

BtnP:=VolUp or VolDn;

ACTimer_10MS( TIM:= true, EN:=BtnP AND NOT T_200ms , CV:=TCv1 , PV:=20 , TUP=>T_200ms , NUP=>InZone); ACTimer_10MS( TIM:= true, EN:=BtnP , CV:=TCv2 , PV:=200 , TUP=>InZone , NUP=>InZone);

IF TCv2>=200 Then Add_L:=true; elseIF TCv2>=150 Then Add_M:=true; elseIF TCv2>=100 Then Add_S:=true; END_IF

IF R_TRIG( S:=VolUp ) THEN Volume:= Volume+1; END_IF

IF VolUp and T_200ms THEN IF Add_S THEN Volume:= Volume+5; ELSEIF Add_M THEN

Volume:= Volume+12; ELSEIF Add_L THEN Volume:= Volume+20; END_IF END_IF

IF R_TRIG( S:=VolDn ) THEN Volume:= Volume-1; END_IF

IF VolDn and T_200ms THEN IF Add_S THEN Volume:= Volume-5; ELSEIF Add_M THEN Volume:= Volume-12; ELSEIF Add_L THEN Volume:= Volume-20; END_IF END_IF

if Volume > 499 THEN Max:=TRUE; Volume:=500; ELSEIF Volume < 1 THEN Mute:=TRUE; Volume:=0; END_IF

動作說明

mplc-m09-en-03 - 38

Step 1. Trigger VolUp (volume up) or VolDn (volume down) to increase/decrease the volume.

Step 2. Press to increase or decrease the volume by 1 level within 1 second. Press for 1 to 1.5 seconds

to increase or decrease the volume by 5 levels every 0.2 seconds. Press for 1.5 to 2 seconds to increase or decrease the volume by 12 levels every 0.2 seconds. Press for more than 2 seconds to increase or decrease the volume every 0.2 seconds. Reduce the volume by 20 bars.

Step 3. The Volume up to 500 and can't continue to increase.

Step 4. The Volume down to 0 and can't continue to decrease. Multiple use Multiple use of Function Block instructions in the main program

mplc-m09-en-03 - 39

N002 Control the R0 of volume N003 Control the R100 of volume The result of 2 FCMs not interfering with each other.