{"id":3175,"date":"2026-11-17T18:37:47","date_gmt":"2026-11-17T10:37:47","guid":{"rendered":"https:\/\/resource.fatek.com\/index.php\/2026\/11\/17\/mplc-m01-en-03\/"},"modified":"2026-11-17T18:37:47","modified_gmt":"2026-11-17T10:37:47","slug":"mplc-m01-en-03","status":"publish","type":"post","link":"https:\/\/resource.fatek.com\/index.php\/2026\/11\/17\/mplc-m01-en-03\/","title":{"rendered":"System Configuration"},"content":{"rendered":"<p><strong>System Configuration<\/strong><\/p>\n<p>This section describes the precautions when installing the basic system as well as the content related to the peripheral devices. <\/p>\n<h3>3-1 Basic System Configuration<\/h3>\n<p>You may add the M-series module at the right-side of the M-Series PLC CPU Module. The available modules shall comprise the digital I\/O module, analog I\/O module, temperature module, network module and Load Cell Module, etc. Indicated below is the system configuration of each area equipped with part of the M-Series module systems. <\/p>\n<ol>\n<li>\t\t\t\t\t\t\u2461\t\t\t\t\t      \u2462\t\t           \t\u2463\t      \t\t   \u2464<\/li>\n<\/ol>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m01-en-03\/mplc-m01-en-03-001.jpg\" \/><\/p>\n<p>System Configuration Schematic Diagram<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>No.<\/p>\n<\/td>\n<td>\n<p>Name<\/p>\n<\/td>\n<td>\n<p>Remarks for installation:<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>1<\/p>\n<\/td>\n<td>\n<p>Power module<\/p>\n<\/td>\n<td>\n<p>Installed in the expansion area on the left-side of the CPU module.<\/p>\n<p>(Advanced Expansion Area)<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>2<\/p>\n<\/td>\n<td>\n<p>CPU module<\/p>\n<\/td>\n<td>\n<p>Main function Area<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>3<\/p>\n<\/td>\n<td>\n<p>Communication module<\/p>\n<\/td>\n<td>\n<p>It is classified as High-Speed Expansion Module.<\/p>\n<p>Installed at the right-side of CPU module.(High-Speed Expansion Area)<\/p>\n<p>(During the installation, it is not allowed to install a Local I\/O Module between the CPU module and the high-speed expansion module; otherwise the high-speed expansion module will become inactive). <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>4<\/p>\n<\/td>\n<td>\n<p>DIO expansion module<\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>It is classified as Local I\/O Expansion module.<\/p>\n<p>Installed at the right-side of the CPU module and high-speed expansion module. (Local I\/O Expansion Area)<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>AIO expansion module<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>5<\/p>\n<\/td>\n<td>\n<p>End module<\/p>\n<\/td>\n<td>\n<p>It should be installed at the rightmost end of each field. If such End module is not installed, then the system will signal an error warning message.<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>Basic system configuration<\/p>\n<h3>3-2  Precautions for System Configuration<\/h3>\n<p>This section describes the content of the precautions that should be followed during the system configuration process. <\/p>\n<ol>\n<li>Number of expansion modules and number of I\/O Bus Extension that can be installed<\/li>\n<\/ol>\n<p>The maximum module expansion number shall vary according to the number of I\/O Bus Extension.<\/p>\n<p>Listed below are the number of I\/O Bus Extension of the CPU module and the number of the module blocks that can be installed.<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>Type of CPU host<\/p>\n<\/td>\n<td>\n<p>Max. number of branch field<\/p>\n<\/td>\n<td>\n<p>Max. number of module allowed for installing in each field *1<\/p>\n<\/td>\n<td>\n<p>Max. number of expansion module to be used<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>M-Series PLC<\/p>\n<\/td>\n<td>\n<p>Max. 6 fields (Rack)<\/p>\n<\/td>\n<td>\n<p>Basic field(Rack):Max. 16 units of modules<\/p>\n<p>Expansion field(Rack): Max. 16 units of modules<\/p>\n<\/td>\n<td>\n<p>64 units of modules.<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>*1: Excluding the power module, CPU module, I\/O Bus Extension and End module.<\/p>\n<p>If the number of the connected modules exceeds the limit, the CPU will detect such \u201cError\u201d. <\/p>\n<p>In the meantime, the number and the position of the module to be installed in the module of each field(Rack) are also limited. Listed below are the restricted module positions and number of modules to be installed.<\/p>\n<p>(Maximum number of connection modules will vary depending on the number of AIO and DIO points that can be supported by different models)<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>Product name<\/p>\n<\/td>\n<td>\n<p>Number of module that can be installed<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>CPU module<\/p>\n<\/td>\n<td>\n<p>Only one set in basic field(Rack). <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>#Branch module <\/p>\n<\/td>\n<td>\n<p>Only one set in basic field(Rack).<\/p>\n<p>Inactive when installing in the expansion field(Rack).<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>#Gateway module<\/p>\n<\/td>\n<td>\n<p>Only one set in the expansion field(Rack).<\/p>\n<p>Inactive when installing in the basic field(Rack).<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>RS232 expansion \/ RS485 expansion<\/p>\n<\/td>\n<td>\n<p>Being the high-speed module, it can only be installed in the basic field(Rack) and maximum 6 units can be installed. Besides, it can only be connected to the right- side of the CPU module and cannot be connected to the right-side of the local I\/O modules. <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>DIO modula<\/p>\n<\/td>\n<td>\n<p>Used in conjunction with the I\/O Bus Extension module, maximum limit of 64 units.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>AIO modula<\/p>\n<\/td>\n<td>\n<p>Used in conjunction with the I\/O Bus Extension module, maximum limit of 64 units.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Load Cell module<\/p>\n<\/td>\n<td>\n<p>Used in conjunction with the I\/O Bus Extension module, maximum limit of 64 units.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Temperature Measurement module<\/p>\n<\/td>\n<td>\n<p>Used in conjunction with the I\/O Bus Extension module, maximum limit of 64 units.<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>To avoid interference, the PLC should be installed to keep from noise sources such as high- voltage or high- current and high-power switches. Other precautions are:<\/p>\n<p>The installation that the safety of any system incorporating the equipment is the responsibility of the assembler of the system.<\/p>\n<p>L&#8217;installation ainsi que la s\u00e9curit\u00e9 de tout syst\u00e8me int\u00e9grant l&#8217;\u00e9quipement rel\u00e8vent de la responsabilit\u00e9 de l&#8217;assembleur du syst\u00e8me.<\/p>\n<p>If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.<\/p>\n<p>Si l&#8217;\u00e9quipement est utilis\u00e9 d&#8217;une mani\u00e8re non sp\u00e9cifi\u00e9e par le fabricant, la protection fournie par l&#8217;\u00e9quipement peut \u00eatre alt\u00e9r\u00e9e.<\/p>\n<h4>3-2-1 Placement of PLC                                                           <\/h4>\n<p>Fixation of M Series PLC, which can be fixed by DIN RAIL, should place vertically and start from the CPU module on the left to the expansion module on the right.<\/p>\n<p>The high-speed expansion module requires two communication ports, so the high-speed expansion modules must be connected to the CPU module (Main unit) before the local I\/O modules. A maximum of six high-speed modules can be connected, and without an I\/O bus extension module, each CPU module can support up to 16 expansion modules. It should be noted that the number and types of modules that can be connected may vary slightly depending on the CPU model.<\/p>\n<p>A typical figure of placement is shown below:<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m01-en-03\/mplc-m01-en-03-002.png\" \/><\/p>\n<p>Placement of M series PLC installation<\/p>\n<h4>3-2-2 Placement of I\/O Bus Extension Module(Repeater, MRPWE)                      <\/h4>\n<p>When the power module can&#8217;t provide enough power for all the expansion modules, a\u201cRepeater When the power module can&#8217;t provide enough power for all the expansion modules, a \u201cRepeater module&quot; can be appropriately added to share the load of the power module. The repeater module is equivalent to the 48W power module. A maximum of 16 Local I\/O expansion modules can be installed between a power module and a repeater module. A maximum of 16 Local I\/O expansion modules can be installed between the repeater module and the next repeater module. A total of 64 expansion modules (Local I\/O expansion plus High-speed expansion modules) can be installed.<\/p>\n<p>The following figure shows the placement of repeater modules:<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m01-en-03\/mplc-m01-en-03-003.png\" \/><\/p>\n<p>Placement of Repeater Module<\/p>\n<h4>3-2-3 Placement of I\/O Bus Extension Module (Head &amp;Tail, MRGH &amp;MRGT)              <\/h4>\n<p>When the control cabinet is not wide enough to accommodate the right expansion module, an I\/O Bus extension module (Head and Tail module) can be installed to extend the Local I\/O modules to the next row. Only a maximum of 16 Local I\/O modules expansion modules can be installed in the right side of the Head module, with maximum of 5 Tail modules in a total of 6 rows. A total of 64 expansion modules (Local I\/O expansion plus High-speed expansion modules) can be installed<\/p>\n<p><strong>*The Head module itself does not have the power supply function and only has the function of I\/O<\/strong> <strong>Bus Extension, so the power module must be installed in the left side of Head module.<\/strong><\/p>\n<p>The following figure shows the placement of Head\/Tail modules:<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m01-en-03\/mplc-m01-en-03-004.png\" \/><\/p>\n<p>Placement of Head\/Tail Module installation<\/p>\n<h3>3-3  Motion Control Configuration<\/h3>\n<p>Through the standard commercial RJ-45 (Ethernet) connector rated with the shielding class above CAT6, it connects the EtherCAT port of the M-Series CPU Module with the servo actuator supporting the EtherCAT communication protocol. The servo actuator being firstly connected is pre-set as Axis -1. For detailed online method that will be established with the UperLogic and servo actuator, please refer to the M-Series PLC Motion Control Software Manual.<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m01-en-03\/mplc-m01-en-03-005.png\" \/><\/p>\n<p>Motion control connection schematic diagram<\/p>\n<p>It is recommended to use CAT6 shielded network cables, which can effectively reduce network noise interference problems. For more anti-interference countermeasures, please refer to Chapter 10-2 Wiring.<\/p>\n<h3>3-4  Configuration in Connecting with System Bus<\/h3>\n<p>To connect with the M-Series PLC, the aforesaid device or other system may select either USB, RS-485 or EtherNET port for executing the intended connection. Further, the aforesaid device or other system may also connect with the M-Series PLC through the UperLogic software. For detailed connection and setting method, please refer to the M-Series Software Manual. <\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m01-en-03\/mplc-m01-en-03-006.jpg\" \/><\/p>\n<p>Connection Layout between other systems and the M-Series Module<\/p>\n<h3>3-5  Connection configuration of MQ Compact PLC<\/h3>\n<p>The Compact PLC model is designed to meet various usage scenarios and functional requirements. Users can customize it with the necessary plug-in expansion boards, with a maximum of two plug-in expansion boards installable on the CPU unit. This flexibility allows users to configure a compact PLC that best meets their specific needs. This section will cover important considerations when configuring the MQ Compact PLC.<\/p>\n<ol>\n<li>MQ models cannot connect high-speed expansion modules.<\/li>\n<\/ol>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m01-en-03\/mplc-m01-en-03-007.jpg\" \/><\/p>\n<ol>\n<li>It can\u2019t connect advanced expansion module in the left.<\/li>\n<\/ol>\n","protected":false},"excerpt":{"rendered":"<p>System Configuration This section describes the precaut [&hellip;]<\/p>\n","protected":false},"author":1,"featured_media":0,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[45],"tags":[],"class_list":["post-3175","post","type-post","status-publish","format-standard","hentry","category-en-mplc-m01"],"_links":{"self":[{"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/posts\/3175","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/comments?post=3175"}],"version-history":[{"count":0,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/posts\/3175\/revisions"}],"wp:attachment":[{"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/media?parent=3175"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/categories?post=3175"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/tags?post=3175"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}