{"id":3179,"date":"2026-11-17T18:37:50","date_gmt":"2026-11-17T10:37:50","guid":{"rendered":"https:\/\/resource.fatek.com\/index.php\/2026\/11\/17\/mplc-m01-en-07\/"},"modified":"2026-11-17T18:37:50","modified_gmt":"2026-11-17T10:37:50","slug":"mplc-m01-en-07","status":"publish","type":"post","link":"https:\/\/resource.fatek.com\/index.php\/2026\/11\/17\/mplc-m01-en-07\/","title":{"rendered":"Power Supply Wiring &#038; Power Consumption Calculation and Power Sequenci"},"content":{"rendered":"<h2>7 Power Supply Wiring &amp; Power Consumption Calculation and Power Sequencing Requirements <\/h2>\n<p><strong>Power Supply Wiring &amp; Power Consumption Calculation and Power Sequencing Requirements<\/strong><\/p>\n<p>There are two kinds of power for M series PLC power module. The 1st one is CPU dedicated power supply (To CPU &amp; high speed or local I\/O Expansion modules). The 2nd one is external Sensor power supply. The CPU module and the expansion module are also divided in 2 parts of circuits. The 1st one is 24VDC (Internal Circuit), the 2nd one is 24VDC (Output Sensor Circuit). The 24VDC (Internal Circuit) is supplied by the CPU dedicated power supply of the M series PLC power module. The 24VDC (Output Sensor Circuit) can be supplied by an external power supply or by the external Sensor power supply of the M series PLC power module. Neither the CPU module nor the expansion module has internal power supply, and both must consume the power of the power module to supply power.\u00a0<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>\u26a0Caution<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>In industrial environments, main power may irregularly experience a surge current or high voltage pulse caused by the start or shut down of high power equipment. Users are advised to take necessary measures (for example, the use of isolation transformer or other MOV suppression devices) for the protection of PLC and its peripherals.\u00a0<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>\u26a0Caution<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>\t  Dans les environnements industriels, l\u2019alimentation principale peut subir de mani\u00e8re irr\u00e9guli\u00e8re des surtensions de courant ou des impulsions de haute tension, provoqu\u00e9es par la mise en marche ou l\u2019arr\u00eat d\u2019\u00e9quipements de forte puissance. Il est recommand\u00e9 aux utilisateurs de prendre les mesures n\u00e9cessaires (par exemple l\u2019utilisation d\u2019un transformateur d\u2019isolement ou d\u2019autres dispositifs de suppression tels que les varistances MOV) afin de prot\u00e9ger le PLC et ses p\u00e9riph\u00e9riques.<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<h3>7-1  Specifications and Wiring of Power Module<\/h3>\n<p>Power Module Specification Table<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td colspan=\"2\">\n<p>Specification               Model<\/p>\n<\/td>\n<td>\n<p>MPA024-24<\/p>\n<\/td>\n<td>\n<p>MPA048-24<\/p>\n<\/td>\n<td>\n<p>MRPWE-AC<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"10\">\n<p>input<\/p>\n<\/td>\n<td>\n<p>Input Voltage<\/p>\n<\/td>\n<td>\n<p>100~240VAC<\/p>\n<\/td>\n<td>\n<p>100~240VAC<\/p>\n<\/td>\n<td>\n<p>100~240VAC<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Input Frequency<\/p>\n<\/td>\n<td>\n<p>50\/60Hz<\/p>\n<\/td>\n<td>\n<p>50\/60Hz<\/p>\n<\/td>\n<td>\n<p>50\/60Hz<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Max. Input Current<\/p>\n<\/td>\n<td>\n<p>1A max.<\/p>\n<\/td>\n<td>\n<p>1A max.<\/p>\n<\/td>\n<td>\n<p>1A max.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Inrush Current (Cold Start)<\/p>\n<\/td>\n<td>\n<p>22A\/115Vac (44A\/230Vac)<\/p>\n<\/td>\n<td>\n<p>22A\/115Vac (44A\/230Vac)<\/p>\n<\/td>\n<td>\n<p>22A\/115Vac (44A\/230Vac)<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Withstand voltage<\/p>\n<\/td>\n<td>\n<p>3,000 VAC (Primary-secondary), <\/p>\n<p>1,500 VAC (Primary-PE), <\/p>\n<p>500 VAC(Secondary-PE)<\/p>\n<\/td>\n<td>\n<p>3,000 VAC (Primary-secondary),<\/p>\n<p> 1,500 VAC (Primary-PE), <\/p>\n<p>500 VAC(Secondary-PE)<\/p>\n<\/td>\n<td>\n<p>3,000 VAC (Primary-secondary), <\/p>\n<p>1,500 VAC (Primary-PE), <\/p>\n<p>500 VAC(Secondary-PE)<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Insulation resistance<\/p>\n<\/td>\n<td>\n<p>&gt;100M\u03a9\/500VDC<\/p>\n<\/td>\n<td>\n<p>&gt;100M\u03a9\/500VDC<\/p>\n<\/td>\n<td>\n<p>&gt;100M\u03a9\/500VDC<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Fuse Spec.<\/p>\n<\/td>\n<td>\n<p>2A<\/p>\n<\/td>\n<td>\n<p>2A<\/p>\n<\/td>\n<td>\n<p>2A<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Hold-up time<\/p>\n<\/td>\n<td>\n<p>&gt;15ms\/ 115VAC\uff0c<\/p>\n<p>&gt;60ms\/ 220VAC<\/p>\n<\/td>\n<td>\n<p>&gt;15ms\/ 115VAC\uff0c<\/p>\n<p>&gt;60ms\/ 220VAC<\/p>\n<\/td>\n<td>\n<p>&gt;15ms\/ 115VAC\uff0c<\/p>\n<p>&gt;60ms\/ 220VAC<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Isolation Type<\/p>\n<\/td>\n<td>\n<p>Transformer\/ Photocoupler Isolation\uff0c1500VAC\/1 minute<\/p>\n<\/td>\n<td>\n<p>Transformer\/ Photocoupler Isolation\uff0c1500VAC\/1 minute<\/p>\n<\/td>\n<td>\n<p>Transformer\/ Photocoupler Isolation\uff0c1500VAC\/1 minute<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Operation indication<\/p>\n<\/td>\n<td>\n<p>LED (green)<\/p>\n<\/td>\n<td>\n<p>LED (green)<\/p>\n<\/td>\n<td>\n<p>LED (green)<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"4\">\n<p>output<\/p>\n<\/td>\n<td>\n<p>Rated output power<\/p>\n<\/td>\n<td>\n<p>24W (Shared CPU dedicated power supply and external Sensor power supply)<\/p>\n<\/td>\n<td>\n<p>48W (Shared CPU dedicated power supply and external Sensor power supply)<\/p>\n<\/td>\n<td>\n<p>48W (Shared CPU dedicated power supply and external Sensor power supply)<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Rated output current<\/p>\n<\/td>\n<td>\n<p>1A (Shared CPU dedicated power supply and external Sensor power supply)<\/p>\n<\/td>\n<td>\n<p>2A (Shared CPU dedicated power supply and external Sensor power supply)<\/p>\n<\/td>\n<td>\n<p>2A (Shared CPU dedicated power supply and external Sensor power supply)<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Output voltage range<\/p>\n<\/td>\n<td>\n<p>24VDC\u00b11%<\/p>\n<\/td>\n<td>\n<p>24VDC\u00b11%<\/p>\n<\/td>\n<td>\n<p>24VDC\u00b11%<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Conversion efficiency<\/p>\n<\/td>\n<td>\n<p>86%\/110VAC\uff0c87%\/220VAC<\/p>\n<\/td>\n<td>\n<p>86%\/110VAC\uff0c87%\/220VAC<\/p>\n<\/td>\n<td>\n<p>86%\/110VAC\uff0c87%\/220VAC<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>Protection<\/p>\n<\/td>\n<td>\n<p>Overvoltage protection<\/p>\n<\/td>\n<td>\n<p>Latching overvoltage protection, re-power on to recover 34V~36V<\/p>\n<\/td>\n<td>\n<p>Latching overvoltage protection, re-power on to recover 34V~36V<\/p>\n<\/td>\n<td>\n<p>Latching overvoltage protection, re-power on to recover 34V~36V<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Overcurrent protection<\/p>\n<\/td>\n<td>\n<p>Method: Foldback overload protection, automatically recover when overload is removed 101%~133% rated output power<\/p>\n<\/td>\n<td>\n<p>Method: Foldback overload protection, automatically recover when overload is removed 101%~133% rated output power<\/p>\n<\/td>\n<td>\n<p>Method: Foldback overload protection, automatically recover when overload is removed 101%~133% rated output power<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"3\">\n<p>Environmental Specifications<\/p>\n<\/td>\n<td>\n<p>Operating Ambient Temperature<\/p>\n<\/td>\n<td>\n<p>0\u2103~55\u2103<\/p>\n<\/td>\n<td>\n<p>0\u2103~55\u2103<\/p>\n<\/td>\n<td>\n<p>0\u2103~55\u2103<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Relative Humidity<\/p>\n<\/td>\n<td>\n<p>20 ~ 90% (non-condensing)<\/p>\n<\/td>\n<td>\n<p>20 ~ 90% (non-condensing)<\/p>\n<\/td>\n<td>\n<p>20 ~ 90% (non-condensing)<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Storage Temperature<\/p>\n<\/td>\n<td>\n<p>-25 ~ +70\u2103<\/p>\n<\/td>\n<td>\n<p>-25 ~ +70\u2103<\/p>\n<\/td>\n<td>\n<p>-25 ~ +70\u2103<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"2\">\n<p>Certifications<\/p>\n<\/td>\n<td>\n<p>CE<\/p>\n<\/td>\n<td>\n<p>CE<\/p>\n<\/td>\n<td>\n<p>CE<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"2\">\n<p>External dimensions<\/p>\n<\/td>\n<td>\n<p>90mmX33.7mmX90mm<\/p>\n<\/td>\n<td>\n<p>90mmX33.7mmX90mm<\/p>\n<\/td>\n<td>\n<p>90mmX46.2mmX90mm<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>\u26a0Caution<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>The schematic diagram of power module is shown below. Also be cautious about the following:<\/p>\n<ol>\n<li>Please follow the wiring schemes regulated by local national standards to use single-pole switch\uff08break hot wire\u301dL\u301e\uff09, or double-pole switch\uff08break both\u301dL\u301eand\u301dN\u301e\uff09, to turn on or off the AC input power.<\/li>\n<li>In wiring, hot wire\u301dL\u301emust be connected to the L terminal on unit, while the ground line\u301dN\u301econnected to the N terminal. Please use wires with diameters \uff5e.<\/li>\n<li>All     terminals on CPU module or Power module have to be connected to the EG (Earth Ground) terminal of main power system as shown in the figure below, with wire diameters larger than .<\/li>\n<\/ol>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>\u26a0Caution<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Le sch\u00e9ma de principe du module de puissance est illustr\u00e9 ci-dessous. Il convient \u00e9galement de faire attention aux points suivants :<\/p>\n<ol>\n<li>\tVeuillez suivre les sch\u00e9mas de c\u00e2blage r\u00e9glement\u00e9s par les normes nationales locales pour utiliser l&#8217;interrupteur unipolaire\uff08break hot wire\u301dL\u301e\uff09, ou l&#8217;interrupteur bipolaire\uff08break both\u301dL\u301eand \u301dN\u301e\uff09, pour allumer ou \u00e9teindre l&#8217;alimentation en courant alternatif.<\/li>\n<li>\tLors du c\u00e2blage, le fil chaud\u301dL\u301e doit \u00eatre connect\u00e9 \u00e0 la borne L de l&#8217;appareil, tandis que le fil de terre\u301dN\u301edoit \u00eatre connect\u00e9 \u00e0 la borne N. Utilisez des fils de diam\u00e8tre \uff5e.<\/li>\n<li>Toutes les bornes   du module CPU ou du module d&#8217;alimentation doivent \u00eatre connect\u00e9es \u00e0 la borne EG (Earth Ground) du syst\u00e8me d&#8217;alimentation principal, comme indiqu\u00e9 dans la figure ci-dessous, avec des fils d&#8217;un diam\u00e8tre sup\u00e9rieur \u00e0  .<\/li>\n<\/ol>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>\u26a0Warning<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>24VDC Output power for Sensor circuit cannot be connected in parallel with other powers, in which the conflict between two sets of power will decrease their lifetime or cause immediate damage. This will induce unexpected malfunction of PLC and cause serious or even deadly damage to people or equipment.<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>\u26a0 Avertissement<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>L&#8217;alimentation de sortie 24VDC pour le circuit du capteur ne peut pas \u00eatre connect\u00e9e en parall\u00e8le avec d&#8217;autres alimentations, dans lesquelles le conflit entre deux ensembles d&#8217;alimentation r\u00e9duira leur dur\u00e9e de vie ou causera des dommages imm\u00e9diats. Cela entra\u00eenerait un dysfonctionnement inattendu de l&#8217;automate et causerait des dommages graves, voire mortels, aux personnes ou \u00e0 l&#8217;\u00e9quipement.<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m01-en-07\/mplc-m01-en-07-001.png\" \/><\/p>\n<p>PLC System Wiring<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m01-en-07\/mplc-m01-en-07-002.png\" \/><\/p>\n<p> Power Supply Wiring Diagram<\/p>\n<h3>7-2  Maximum Current Consumption of Expansion Module<\/h3>\n<p>The CPU module and expansion modules themselves have no power supply and must be supplied by the M series PLC power module. The following table shows the maximum current consumption of each expansion module.<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>\u26a0Warning<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Any output of M series PLC power module, the total amount of current cannot exceed the value listed in the below table. Any violation will cause a voltage drop by overloading the power supply, or intermittent powered with the supply in protection mode, either of which will result in unexpected action of PLC and cause harm to people or damage to equipment.<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>\u26a0 Avertissement<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>\t Pour toute sortie d&#8217;un module d&#8217;alimentation PLC de la s\u00e9rie M, la quantit\u00e9 totale de courant ne peut pas d\u00e9passer la valeur indiqu\u00e9e dans le tableau ci-dessous. Toute violation entra\u00eenera une chute de tension en surchargeant l&#8217;alimentation, ou une alimentation intermittente avec l&#8217;alimentation en mode de protection, ce qui entra\u00eenera une action inattendue de l&#8217;automate et causera des dommages aux personnes ou \u00e0 l&#8217;\u00e9quipement.<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>Maximum Current Consumption of Expansion Module Table<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td colspan=\"3\">\n<p>Model                            Current Consumption <\/p>\n<\/td>\n<td>\n<p>24VDC (Internal Circuit)<\/p>\n<\/td>\n<td>\n<p>24VDC (Output Sensor Circuit)<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>Advanced and power Expansion Modules<\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>Power Modules<\/p>\n<\/td>\n<td>\n<p>MPA024-24<\/p>\n<\/td>\n<td>\n<p>&#8211;<\/p>\n<\/td>\n<td>\n<p>&#8211;<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>MPA048-24<\/p>\n<\/td>\n<td>\n<p>&#8211;<\/p>\n<\/td>\n<td>\n<p>&#8211;<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"9\">\n<p>Plug-in Expansion Boards<\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>Communication<\/p>\n<p>Plug-in Expansion Boards<\/p>\n<\/td>\n<td>\n<p>MB-CB2<\/p>\n<\/td>\n<td>\n<p>Approaches 0 mA<\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td>\n<p>MB-CB5<\/p>\n<\/td>\n<td>\n<p>Approaches 0 mA<\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>DI Plug-in Expansion Boards<\/p>\n<\/td>\n<td>\n<p>MB-2HSC<\/p>\n<\/td>\n<td>\n<p>Approaches 0 mA<\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td>\n<p>MB-4X<\/p>\n<\/td>\n<td>\n<p>Approaches 0 mA<\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>DO Plug-in Expansion Boards<\/p>\n<\/td>\n<td>\n<p>MB-2PSO\u25c7<\/p>\n<\/td>\n<td>\n<p>Approaches 0 mA<\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td>\n<p>MB-4Y\u25c7<\/p>\n<\/td>\n<td>\n<p>Approaches 0 mA<\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td>\n<p>AI Plug-in Expansion Boards<\/p>\n<\/td>\n<td>\n<p>MB-2ADL<\/p>\n<\/td>\n<td>\n<p>20 mA<\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td>\n<p>AO Plug-in Expansion Boards<\/p>\n<\/td>\n<td>\n<p>MB-2DAL<\/p>\n<\/td>\n<td>\n<p>80 mA<\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td>\n<p>RTC Plug-in Expansion Boards<\/p>\n<\/td>\n<td>\n<p>MB-RTC<\/p>\n<\/td>\n<td>\n<p>Approaches 0 mA<\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td rowspan=\"3\">\n<p>High Speed Expansion Modules<\/p>\n<\/td>\n<td rowspan=\"3\">\n<p>High Speed Communication Modules<\/p>\n<\/td>\n<td>\n<p>MHCM22<\/p>\n<\/td>\n<td>\n<p>40mA<\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td>\n<p>MHCM55<\/p>\n<\/td>\n<td>\n<p>40mA<\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td>\n<p>MHCM25<\/p>\n<\/td>\n<td>\n<p>40mA<\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td rowspan=\"18\">\n<p>Local I\/O Expansion Modules<\/p>\n<\/td>\n<td>\n<p>DI Modules<\/p>\n<\/td>\n<td>\n<p>M16X<\/p>\n<\/td>\n<td>\n<p>70mA<\/p>\n<\/td>\n<td>\n<p>7.5mA\/ Point<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"3\">\n<p>DO Modules<\/p>\n<\/td>\n<td>\n<p>M16YT<\/p>\n<\/td>\n<td>\n<p>150mA<\/p>\n<\/td>\n<td>\n<p>Max.0.5A\/ Point<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>M16YJ<\/p>\n<\/td>\n<td>\n<p>163mA<\/p>\n<\/td>\n<td>\n<p>Max.0.5A\/ Point<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>M16YR<\/p>\n<\/td>\n<td>\n<p>90mA<\/p>\n<\/td>\n<td>\n<p>Max.2A\/ Point<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"3\">\n<p>DIO Combo Modules<\/p>\n<\/td>\n<td>\n<p>M1616XYT<\/p>\n<\/td>\n<td>\n<p>202mA<\/p>\n<\/td>\n<td>\n<p>X :7.5mA<br \/>Y:0.5A\/ Point<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>M1616XYJ<\/p>\n<\/td>\n<td>\n<p>202mA<\/p>\n<\/td>\n<td>\n<p>X :7.5mA<br \/>Y:0.5A\/Point<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>M1616XYR<\/p>\n<\/td>\n<td>\n<p>202mA<\/p>\n<\/td>\n<td>\n<p>X :7.5mA <\/p>\n<p>Y:@2A\/Point<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>AI Modules<\/p>\n<\/td>\n<td>\n<p>M04AD<\/p>\n<\/td>\n<td>\n<p>78.2mA<\/p>\n<\/td>\n<td>\n<p>&#8211;<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>M04ADR<\/p>\n<\/td>\n<td>\n<p>78.2mA<\/p>\n<\/td>\n<td>\n<p>&#8211;<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>AO Modules<\/p>\n<\/td>\n<td>\n<p>M04DA<\/p>\n<\/td>\n<td>\n<p>14.2mA<\/p>\n<\/td>\n<td>\n<p>107mA<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>M04DAR<\/p>\n<\/td>\n<td>\n<p>14.2mA<\/p>\n<\/td>\n<td>\n<p>107mA<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>AIO Combo Modules<\/p>\n<\/td>\n<td>\n<p>M0202AH<\/p>\n<\/td>\n<td>\n<p>22.58mA<\/p>\n<\/td>\n<td>\n<p>39.85mA<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>Temperature measurement Modules<\/p>\n<\/td>\n<td>\n<p>M04TC<\/p>\n<\/td>\n<td>\n<p>30.7mA<\/p>\n<\/td>\n<td>\n<p>&#8211;<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>M04TCR<\/p>\n<\/td>\n<td>\n<p>30.7mA<\/p>\n<\/td>\n<td>\n<p>&#8211;<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Temperature Measurement <\/p>\n<p>Combo Modules<\/p>\n<\/td>\n<td>\n<p>M0202TH<\/p>\n<\/td>\n<td>\n<p>30mA<\/p>\n<\/td>\n<td>\n<p>&#8211;<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>Load Cell Modules<\/p>\n<\/td>\n<td>\n<p>M02LC<\/p>\n<\/td>\n<td>\n<p>40.64mA<\/p>\n<\/td>\n<td>\n<p>&#8211;<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>M02LCR<\/p>\n<\/td>\n<td>\n<p>56.1mA<\/p>\n<\/td>\n<td>\n<p>&#8211;<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>End module<\/p>\n<\/td>\n<td>\n<p>MRE<\/p>\n<\/td>\n<td>\n<p>&#8211;<\/p>\n<\/td>\n<td>\n<p>&#8211;<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"3\">\n<p>I\/O Bus Extension modules<\/p>\n<\/td>\n<td>\n<p>Repeater Modules<\/p>\n<\/td>\n<td>\n<p>MRPWE-AC<\/p>\n<\/td>\n<td>\n<p>&#8211;<\/p>\n<\/td>\n<td>\n<p>&#8211;<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>I\/O Bus Extension module(Head)<\/p>\n<\/td>\n<td>\n<p>MRGH<\/p>\n<\/td>\n<td>\n<p>&#8211;<\/p>\n<\/td>\n<td>\n<p>&#8211;<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>I\/O Bus Extension module(Tail)<\/p>\n<\/td>\n<td>\n<p>MRGT<\/p>\n<\/td>\n<td>\n<p>&#8211;<\/p>\n<\/td>\n<td>\n<p>&#8211;<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Remote  Expansion Modules<\/p>\n<\/td>\n<td>\n<p>Remote I\/O Coupler<\/p>\n<\/td>\n<td>\n<p>MC0EN<\/p>\n<\/td>\n<td>\n<p>80mA<\/p>\n<\/td>\n<td>\n<p>&#8211;<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>Maximum Current Consumption of CPU Module Table<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td colspan=\"3\">\n<p>Model\t\tCurrent<\/p>\n<\/td>\n<td>\n<p>24VDC (Internal Circuit)<\/p>\n<\/td>\n<td>\n<p>24VDC (Output Sensor Circuit)<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"21\">\n<p>CPU Modules<\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>Compact CPU Modules<\/p>\n<\/td>\n<td>\n<p>MQ2M0-1616\u25c7<\/p>\n<\/td>\n<td>\n<p>150mA<\/p>\n<\/td>\n<td>\n<p>DI : 7.5mA\/Point <\/p>\n<p>DO : Max.0.1A\/Point<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>MQ2M1-1616\u25c7<\/p>\n<\/td>\n<td>\n<p>150mA<\/p>\n<\/td>\n<td>\n<p>DI : 7.5mA\/Point <\/p>\n<p>DO : Max.0.1A\/Point<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>MQ2M3-1616\u25c7<\/p>\n<\/td>\n<td>\n<p>150mA<\/p>\n<\/td>\n<td>\n<p>DI : 7.5mA\/Point <\/p>\n<p>DO : Max.0.1A\/Point<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>MQ2M6-1616\u25c7<\/p>\n<\/td>\n<td>\n<p>150mA<\/p>\n<\/td>\n<td>\n<p>DI : 7.5mA\/Point <\/p>\n<p>DO : Max.0.1A\/Point<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"3\">\n<p>Advanced CPU Modules<\/p>\n<\/td>\n<td>\n<p>MA1N0-1616\u25c7<\/p>\n<\/td>\n<td>\n<p>150mA<\/p>\n<\/td>\n<td>\n<p>DI : 7.5mA\/Point <\/p>\n<p>DO : Max.0.1A\/Point<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>MA1N3-1616\u25c7<\/p>\n<\/td>\n<td>\n<p>150mA<\/p>\n<\/td>\n<td>\n<p>DI : 7.5mA\/Point <\/p>\n<p>DO : Max.0.1A\/Point<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>MA1I4-1616\u25c7<\/p>\n<\/td>\n<td>\n<p>150mA<\/p>\n<\/td>\n<td>\n<p>DI : 7.5mA\/Point <\/p>\n<p>DO : Max.0.1A\/Point<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"10\">\n<p>General Motion Control CPU Module<\/p>\n<\/td>\n<td>\n<p>MS2C4-1616\u25c7<\/p>\n<\/td>\n<td>\n<p>200mA<\/p>\n<\/td>\n<td>\n<p>DI : 7.5mA\/Point <\/p>\n<p>DO : Max.0.1A\/Point<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>MS2C5-1616\u25c7<\/p>\n<\/td>\n<td>\n<p>200mA<\/p>\n<\/td>\n<td>\n<p>DI : 7.5mA\/Point <\/p>\n<p>DO : Max.0.1A\/Point<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>MS3C6-1616\u25c7<\/p>\n<\/td>\n<td>\n<p>200mA<\/p>\n<\/td>\n<td>\n<p>DI : 7.5mA\/Point <\/p>\n<p>DO : Max.0.1A\/Point<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>MU2C4-1616\u25c7<\/p>\n<\/td>\n<td>\n<p>200mA<\/p>\n<\/td>\n<td>\n<p>DI : 7.5mA\/Point <\/p>\n<p>DO : Max.0.1A\/Point<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>MU2C6-1616\u25c7<\/p>\n<\/td>\n<td>\n<p>200mA<\/p>\n<\/td>\n<td>\n<p>DI : 7.5mA\/Point <\/p>\n<p>DO : Max.0.1A\/Point<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>MU3C2-1616\u25c7<\/p>\n<\/td>\n<td>\n<p>200mA<\/p>\n<\/td>\n<td>\n<p>DI : 7.5mA\/Point <\/p>\n<p>DO : Max.0.1A\/Point<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>MU3C3-1616\u25c7<\/p>\n<\/td>\n<td>\n<p>200mA<\/p>\n<\/td>\n<td>\n<p>DI : 7.5mA\/Point <\/p>\n<p>DO : Max.0.1A\/Point<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>MU3C4-1616\u25c7<\/p>\n<\/td>\n<td>\n<p>200mA<\/p>\n<\/td>\n<td>\n<p>DI : 7.5mA\/Point <\/p>\n<p>DO : Max.0.1A\/Point<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>MU3C5-1616\u25c7<\/p>\n<\/td>\n<td>\n<p>200mA<\/p>\n<\/td>\n<td>\n<p>DI : 7.5mA\/Point <\/p>\n<p>DO : Max.0.1A\/Point<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>MU3C6-1616\u25c7<\/p>\n<\/td>\n<td>\n<p>200mA<\/p>\n<\/td>\n<td>\n<p>DI : 7.5mA\/Point <\/p>\n<p>DO : Max.0.1A\/Point<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"4\">\n<p>Advanced Motion Control CPU Module<\/p>\n<\/td>\n<td>\n<p>ME2C3-1616\u25c7<\/p>\n<\/td>\n<td>\n<p>200mA<\/p>\n<\/td>\n<td>\n<p>DI : 7.5mA\/Point <\/p>\n<p>DO : Max.0.1A\/Point<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>ME2C4-1616\u25c7<\/p>\n<\/td>\n<td>\n<p>200mA<\/p>\n<\/td>\n<td>\n<p>DI : 7.5mA\/Point <\/p>\n<p>DO : Max.0.1A\/Point<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>ME2C5-1616\u25c7<\/p>\n<\/td>\n<td>\n<p>200mA<\/p>\n<\/td>\n<td>\n<p>DI : 7.5mA\/Point <\/p>\n<p>DO : Max.0.1A\/Point<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>ME3C6-1616\u25c7<\/p>\n<\/td>\n<td>\n<p>200mA<\/p>\n<\/td>\n<td>\n<p>DI : 7.5mA\/Point <\/p>\n<p>DO : Max.0.1A\/Point<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<h3>7-3  Calculation Example of Power Capacity<\/h3>\n<p>Power module selection is depending on the sum of current consumption of all modules. Therefore, user must know the current consumption of each module. Please refer to the maximum current consumption of expansion module table, which has the maximum current consumption of each expansion module.<\/p>\n<p>User must consider the match between power and expansion modules cannot cause output power of any one group of overload use.<\/p>\n<p>The below diagram is a System Modules, try to calculate the power supply used of the system.<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>Type<\/p>\n<\/td>\n<td>\n<p>Power Module<\/p>\n<\/td>\n<td>\n<p>CPU Module<\/p>\n<\/td>\n<td>\n<p>Expansion Module<\/p>\n<\/td>\n<td>\n<p>Expansion Module<\/p>\n<\/td>\n<td>\n<p>Expansion Module<\/p>\n<\/td>\n<td>\n<p>Expansion Module<\/p>\n<\/td>\n<td>\n<p>END Module<\/p>\n<\/td>\n<td>\n<p>Extra Capacity<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Module Name<\/p>\n<\/td>\n<td>\n<p>MPA024-<\/p>\n<p>24<\/p>\n<\/td>\n<td>\n<p>ME3C6-<\/p>\n<p>1616T<\/p>\n<\/td>\n<td>\n<p>M16XX<\/p>\n<\/td>\n<td>\n<p>M16YT<\/p>\n<\/td>\n<td>\n<p>M04AD<\/p>\n<\/td>\n<td>\n<p>M04TC<\/p>\n<\/td>\n<td>\n<p>MRE<\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td>\n<p>24VDC <\/p>\n<p>(Input Circuit)<\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>+1000mA<\/p>\n<\/td>\n<td>\n<p>-200mA<\/p>\n<\/td>\n<td>\n<p>-70mA<\/p>\n<\/td>\n<td>\n<p>-150mA<\/p>\n<\/td>\n<td>\n<p>-78.2mA<\/p>\n<\/td>\n<td>\n<p>-30.7mA<\/p>\n<\/td>\n<td>\n<p>&#8211;<\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>231.1mA<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>24VDC (Output Circuit)<\/p>\n<\/td>\n<td>\n<p>-7.5mA*16 Point<\/p>\n<\/td>\n<td>\n<p>-7.5mA*16 Point<\/p>\n<\/td>\n<td>\n<p>&#8211;<\/p>\n<\/td>\n<td>\n<p>&#8211;<\/p>\n<\/td>\n<td>\n<p>&#8211;<\/p>\n<\/td>\n<td>\n<p>&#8211;<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<ul>\n<li><strong>Power Module &#8211; 24VDC (Input Circuit) &#8211; 24VDC (Output Circuit)<\/strong><br \/>\u30101000mA\u3011\u2013\u3010200mA+70mA+150mA+78.2mA+30.7mA\u3011-\u3010(7.5mA*16)+(7.5mA*16)\u3011=231.1mA<\/li>\n<\/ul>\n<h3>7-4 Requirement of Power Sequence in CPU Modlue &amp; Expansion Module<\/h3>\n<p>When the power is on, the M Series PLC first detects the type and number of expansion module attached to its expansion interface and get the actual I\/O configuration. Therefore, while the CPU module performs detection, the power in expansion module should be already UP, otherwise, the detected I\/O configuration will not correct. Namely, the power of expansion module should be ON simultaneously or even earlier. There will be no time sequence error when CPU module\/expansion module are connected together to one power. If the expansion module and CPU module powered by different powers (or the same power but different switches), or external power supply is used for expansion modules, time sequence of both powers should be considered. To solve the problem of the expansion module power not get ready before CPU module power does, M Series PLC provides a special R35367 register which can delay the detection time of I\/O configuration. The time base of R35367 is 0.01sec with a default value of 0, which can be set from 0~1000 (1~10c), as shown in the figure below. If the expansion module power cannot be UP within 1sec after main unit power is ON, the R35367 time needs to be set longer to delay the detection by CPU. It cannot exceed 10sec, however, otherwise the configuration of expansion interface cannot be detected.<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m01-en-07\/mplc-m01-en-07-003.png\" \/><\/p>\n<p>Power Timing Diagram<\/p>\n","protected":false},"excerpt":{"rendered":"<p>7 Power Supply Wiring &amp; Power Consumption Calculati [&hellip;]<\/p>\n","protected":false},"author":1,"featured_media":0,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[45],"tags":[],"class_list":["post-3179","post","type-post","status-publish","format-standard","hentry","category-en-mplc-m01"],"_links":{"self":[{"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/posts\/3179","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/comments?post=3179"}],"version-history":[{"count":0,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/posts\/3179\/revisions"}],"wp:attachment":[{"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/media?parent=3179"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/categories?post=3179"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/tags?post=3179"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}