{"id":3188,"date":"2026-11-17T18:38:02","date_gmt":"2026-11-17T10:38:02","guid":{"rendered":"https:\/\/resource.fatek.com\/index.php\/2026\/11\/17\/mplc-m02-en-03\/"},"modified":"2026-11-17T18:38:02","modified_gmt":"2026-11-17T10:38:02","slug":"mplc-m02-en-03","status":"publish","type":"post","link":"https:\/\/resource.fatek.com\/index.php\/2026\/11\/17\/mplc-m02-en-03\/","title":{"rendered":"Chapter 3 Installation And Wiring"},"content":{"rendered":"<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>\u26a0Danger<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<ol>\n<li>Turn off all power before installation of M Series PLC or related equipments to prevent electric shock or damage to equipment.<\/li>\n<li>During installation, never remove the dust cover sheet that were attached on the PLC before wiring is completed to avoid complications such as fire hazards, breakdown, or malfunction caused by drill dust or wire shreds falling inside PLC.<\/li>\n<li>Upon completion of installation and wiring, remember to remove the dust cover sheet to avoid fire, breakdown or malfunction, caused by overheating.<\/li>\n<\/ol>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>\u26a0Danger<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<ol>\n<li>Coupez toute alimentation avant l&#8217;installation de l&#8217;automate de la s\u00e9rie M ou des \u00e9quipements connexes pour \u00e9viter tout choc \u00e9lectrique ou tout dommage \u00e0 l&#8217;\u00e9quipement.<\/li>\n<li>Lors de l&#8217;installation, ne retirez jamais la feuille de protection anti-poussi\u00e8re fix\u00e9e sur l&#8217;API avant la fin du c\u00e2blage afin d&#8217;\u00e9viter des complications telles que des risques d&#8217;incendie, des pannes ou des dysfonctionnements caus\u00e9s par la poussi\u00e8re de per\u00e7age ou des fragments de fil tombant \u00e0 l&#8217;int\u00e9rieur de l&#8217;API.<\/li>\n<li>Une fois l&#8217;installation et le c\u00e2blage termin\u00e9s, n&#8217;oubliez pas de retirer la feuille de protection anti-poussi\u00e8re pour \u00e9viter tout incendie, panne ou dysfonctionnement caus\u00e9 par une surchauffe.<\/li>\n<\/ol>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<h3>3-1 Environmental Specifications<\/h3>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>\u26a0Caution<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<ol>\n<li>Environmental specifications of M Series PLC cannot exceed those listed in this manual. In addition, do not operate this equipment in environments with oil smoke, conductive dust, high temperatures, high humidity, corrosion gases, inflammable gases, rain or condensation, and high vibrations and shock.<\/li>\n<li>Whether this product is used in a system or alone, it must be installed in an appropriate cabinet. The selection and installation of the cabinet must comply with local or national standards.<\/li>\n<\/ol>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>\u26a0 Prudence<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<ol>\n<li>Les sp\u00e9cifications environnementales de l&#8217;API de la s\u00e9rie M ne peuvent pas d\u00e9passer celles \u00e9num\u00e9r\u00e9es dans ce manuel. De plus, n&#8217;utilisez pas cet \u00e9quipement dans des environnements contenant de la fum\u00e9e d&#8217;huile, de la poussi\u00e8re conductrice, des temp\u00e9ratures \u00e9lev\u00e9es, une humidit\u00e9 \u00e9lev\u00e9e, des gaz de corrosion, des gaz inflammables, de la pluie ou de la condensation, ainsi que des vibrations et des chocs \u00e9lev\u00e9s.<\/li>\n<li>Que ce produit soit utilis\u00e9 dans un syst\u00e8me ou seul, il doit \u00eatre install\u00e9 dans une armoire appropri\u00e9e. Le choix et l&#8217;installation de l&#8217;armoire doivent \u00eatre conformes aux normes locales ou nationales.<\/li>\n<\/ol>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>Environmental Specifications Table<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>Item<\/p>\n<\/td>\n<td>\n<p>Specification<\/p>\n<\/td>\n<td>\n<p>note<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Operating Ambient Temperature<\/p>\n<\/td>\n<td>\n<p>0~55\u2103<\/p>\n<\/td>\n<td>\n<p>Permanent Installation<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Storage Temperature<\/p>\n<\/td>\n<td>\n<p>-25 ~ +70\u2103<\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td>\n<p>Relative Humidity<\/p>\n<p>(non-condensing)<\/p>\n<\/td>\n<td>\n<p>20 ~ 90%<\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td>\n<p>Pollution Level<\/p>\n<\/td>\n<td>\n<p>Dergree \u2161<\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td>\n<p>Altitude<\/p>\n<\/td>\n<td>\n<p>\u22662000m<\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td>\n<p>Vibration <\/p>\n<p>(Fixed by DIN RAIL)<\/p>\n<\/td>\n<td>\n<p>5~8.4Hz Amplitude: 3.5mm<\/p>\n<p>8.4~150Hz Constant acceleration:19.6m\/s^2(2G)<\/p>\n<p>10G, 10 times each along the 3 axes (IEC61131-2 Standard)<\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td>\n<p>Shock<\/p>\n<\/td>\n<td>\n<p>10G, 3 times each along the 3 axes<\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td>\n<p>Noise Suppression<\/p>\n<\/td>\n<td>\n<p>1500Vp-p\uff0cWidth 1us<\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td>\n<p>Withstand Voltage<\/p>\n<\/td>\n<td>\n<p>1500 VAC 1 minute (Between power terminals and input\/output terminals, and between all external terminals and the housing)<\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<\/table>\n<\/div>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>\u26a0Warning<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>The listed environmental specifications are for M Series PLC under normal operation. Any operation in environment not conform to above conditions should be consulted with FATEK.<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>\u26a0 Avertissement<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Les sp\u00e9cifications environnementales \u00e9num\u00e9r\u00e9es concernent les automates de la s\u00e9rie M en fonctionnement normal. Toute op\u00e9ration dans un environnement non conforme aux conditions ci-dessus doit \u00eatre consult\u00e9e aupr\u00e8s de FATEK.<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<h3>3-2 Installation Precautions<\/h3>\n<p>To avoid interference, the PLC should be installed to keep from noise sources such as high- voltage or high- current and high-power switches. Other precautions are:<\/p>\n<p>The installation that the safety of any system incorporating the equipment is the responsibility of the assembler of the system.<\/p>\n<p>L&#8217;installation ainsi que la s\u00e9curit\u00e9 de tout syst\u00e8me int\u00e9grant l&#8217;\u00e9quipement rel\u00e8vent de la responsabilit\u00e9 de l&#8217;assembleur du syst\u00e8me.<\/p>\n<p>If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.<\/p>\n<p>Si l&#8217;\u00e9quipement est utilis\u00e9 d&#8217;une mani\u00e8re non sp\u00e9cifi\u00e9e par le fabricant, la protection fournie par l&#8217;\u00e9quipement peut \u00eatre alt\u00e9r\u00e9e.<\/p>\n<h4>3-2-1 Placement of PLC<\/h4>\n<p>Fixation of M Series PLC, which can be fixed by DIN RAIL, should place vertically and start from the CPU module on the left to the expansion module on the right.<\/p>\n<p>The high-speed expansion module requires two communication ports, so the high-speed expansion modules must be connected to the CPU module (Main unit) before the local I\/O modules. A maximum of six high-speed modules can be connected, and without an I\/O bus extension module, each CPU module can support up to 16 expansion modules. It should be noted that the number and types of modules that can be connected may vary slightly depending on the CPU model.<\/p>\n<p>A typical figure of placement is shown below:<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m02-en-03\/mplc-m02-en-03-001.png\" \/><\/p>\n<p>Placement of M series PLC installation<\/p>\n<h4>3-2-2 Placement of I\/O Bus Extension Module(Repeater, MRPWE)<\/h4>\n<p>When the power module can&#8217;t provide enough power for all the expansion modules, a \u201cRepeater module&quot; can be appropriately added to share the load of the power module. The repeater module is equivalent to the 48W power module. A maximum of 16 Local I\/O expansion modules can be installed between a power module and a repeater module. A maximum of 16 Local I\/O expansion modules can be installed between the repeater module and the next repeater module. A total of 64 expansion modules (Local I\/O expansion plus High-speed expansion modules) can be installed.<\/p>\n<p>The following figure shows the placement of repeater modules:<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m02-en-03\/mplc-m02-en-03-002.png\" \/><\/p>\n<p>Placement of Repeater Module<\/p>\n<h4>3-2-3 Placement of I\/O Bus Extension Module (MRGH &amp; MRGT)<\/h4>\n<p>When the control cabinet is not wide enough to accommodate the right expansion module, an I\/O Bus extension module (Head and Tail module) can be installed to extend the Local I\/O modules to the next row. Only a maximum of 16 Local I\/O modules expansion modules can be installed in the right side of the Head module, with maximum of 5 Tail modules in a total of 6 rows. A total of 64 expansion modules (Local I\/O expansion plus High-speed expansion modules) can be installed<\/p>\n<p><strong>*The Head module itself does not have the power supply function and only has the function of I\/O Bus Extension, so the power module must be installed in the left side of Head module.<\/strong><\/p>\n<p>The following figure shows the placement of Head\/Tail modules:<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m02-en-03\/mplc-m02-en-03-003.png\" \/><\/p>\n<p>Placement of Head\/Tail Module installation<\/p>\n<h4>3-2-4 Ventilation Space for Installation<\/h4>\n<p>The heat in M Series PLC is ventilated via air circulation. There should reserve more than 50mm space, both below and above PLC, and with vertical installation, for ventilation. as shown in the figure below :<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m02-en-03\/mplc-m02-en-03-004.png\" \/><\/p>\n<p>M Series PLC installation direction<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m02-en-03\/mplc-m02-en-03-005.jpg\" \/><\/p>\n<p>M Series PLC ventilation space<\/p>\n<h4>3-2-5 Fixation by DIN RAIL<\/h4>\n<p>In an environment with slight vibration (less than 0.5G), this is the most convenient way of fixation and is easy for maintenance. Please use DIN EN50022 DIN RAIL, as shown in the figure below.<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m02-en-03\/mplc-m02-en-03-006.png\" \/><\/p>\n<p>DIN RAIL SIZE<\/p>\n<p>Mount<\/p>\n<p>Hold PLC facing its front, press it down with a 15 degrees tilt onto the DIN RAIL. Swing it down until the upper edge of DIN RAIL groove on PLC back touches the upper tab of DIN RAIL. Then use this locked-in point as a pivot to press the PLC forward on the bottom and lock it in position. The procedure is illustrated below.<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m02-en-03\/mplc-m02-en-03-007.png\" \/><\/p>\n<p>Mount DIN RAIL<\/p>\n<p>Dismount<\/p>\n<p>Use a long screwdriver to reach in the hole on the DIN RAIL tab. Pull out the tab to \u201cpulled out\u201d position to remove PLC, as shown in the figure below.<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m02-en-03\/mplc-m02-en-03-008.png\" \/><\/p>\n<p>Dismount DIN RAIL<\/p>\n<p>When used in the vibration source, it is recommended that a DIN RAIL damper should be installed on the leftmost and rightmost sides of the M-Series PLC, respectively. In this way, it can stabilize all the modules, including the CPU module and expansion module per the leftmost and rightmost DIN RAIL dampers indicated in the figure below. <\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m02-en-03\/mplc-m02-en-03-009.png\" \/><\/p>\n<p>DIN RAIL BAFFLE<\/p>\n<h4>3-2-6 Installation of Expansion Modules<\/h4>\n<p>Expansion module installation method: after aligning the expansion module with the CPU Module slot or with the slot of the previous expansion module, insert the module and then push the latch-hook straight down to the base, as indicated in the figure below.<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m02-en-03\/mplc-m02-en-03-010.png\" \/><\/p>\n<p>Install expansion module<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m02-en-03\/mplc-m02-en-03-011.png\" \/><\/p>\n<p>Install the expansion module buckle<\/p>\n<h4>3-2-7 Installation and Remove of Plug-in Expansion Boards<\/h4>\n<ol>\n<li>Press the top and bottom clips of the expansion case, then pull it upwards.<\/li>\n<\/ol>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m02-en-03\/mplc-m02-en-03-012.png\" \/><\/p>\n<p>Remove expansion panel method<\/p>\n<ol>\n<li>Cut off different support piece on the bracket(case) along the dotted line according to different plug-in expansion boards.<\/li>\n<\/ol>\n<p>  Plug-in expansion board: MB-CB5\uff0cMB-2HSC\uff0cMB-4X\uff0cMB-2PSO\u25c7\uff0cMB-4Y\u25c7<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m02-en-03\/mplc-m02-en-03-013.png\" \/><\/p>\n<p>Plug-in expansion board: MB-CB2<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m02-en-03\/mplc-m02-en-03-014.png\" \/><\/p>\n<ol>\n<li>Insert the plug-in expansion board into the groove inside the bracket (by the black arrow).<\/li>\n<\/ol>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m02-en-03\/mplc-m02-en-03-015.png\" \/><\/p>\n<p>Insert the plug-in expansion board into the plug-in expansion board bracket method<\/p>\n<ol>\n<li>Paste the nameplate that comes with the module\u3002<\/li>\n<\/ol>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m02-en-03\/mplc-m02-en-03-016.png\" \/><\/p>\n<p>Paste the nameplate<\/p>\n<ol>\n<li>Install the plug-in expansion board including the expansion bracket(case) to the MQ CPU.\u3002<\/li>\n<\/ol>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m02-en-03\/mplc-m02-en-03-017.png\" \/><\/p>\n<p>Install the plug-in Expansion Board to the MQ CPU.<\/p>\n<ol>\n<li>Press the clips on the top and bottom of the expansion bracket. and use a flat-blade screwdriver to lift the expansion bracket at the point by the black arrow.<\/li>\n<\/ol>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m02-en-03\/mplc-m02-en-03-018.png\" \/><\/p>\n<p>Remove the Plug-in Expansion Board<\/p>\n<h4>3-2-8 Mount European Terminal Block<\/h4>\n<ul>\n<li>EU-standard terminal installation method: align the EU-standard terminal with the slot of the expansion module and then push it straight downward, as indicated in the figure below.<\/li>\n<\/ul>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m02-en-03\/mplc-m02-en-03-019.png\" \/><\/p>\n<p>Mount European terminal Block<\/p>\n<ul>\n<li>EU-standard terminal removing method: push the fastener on both ends of the EU-standard terminal downward and then lift both of them upward and you can take out the terminal, as indicated in the figure below. <\/li>\n<\/ul>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m02-en-03\/mplc-m02-en-03-020.png\" \/><\/p>\n<p>Dismount European terminal Block<\/p>\n<h4>3-2-9 DIO Converter Module and European terminal wiring<\/h4>\n<ol>\n<li>During the wiring of M Series PLC, please follow local national standards or regulations for installation.<\/li>\n<li>The product is Open type, intended to be installed in a final enclosure.<\/li>\n<li>Power Terminal Block plug wiring size 18-24 AWG. <\/li>\n<\/ol>\n<p>C\u00e2blage de la fiche du bornier d&#8217;alimentation, taille 18-24 AWG.<\/p>\n<ol>\n<li>The rating of the power wire used must be at least 105\u00b0C.<\/li>\n<\/ol>\n<p>La temp\u00e9rature nominale du fil d&#8217;alimentation utilis\u00e9 doit \u00eatre d&#8217;au moins 105\u00b0C<\/p>\n<ol>\n<li>Use Copper Conductors Only.<\/li>\n<\/ol>\n<p>Utilisez uniquement des conducteurs en cuivre.<\/p>\n<ol>\n<li>Shorter wires are preferred. It is advised that the length of I\/O wiring does not exceed 100m (10m for high-speed input).<\/li>\n<li>Input wiring should be separated from output or power wiring (at least 30~50mm apart). In case separation is not possible, adopt vertical crossing, no parallel wiring is allow.<\/li>\n<li>The specifications of the crimp sleeve for the DIO Converter Module and the European terminal are as follows:<\/li>\n<\/ol>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m02-en-03\/mplc-m02-en-03-021.png\" \/><\/p>\n<p>Crimp Sleeve Specifications<\/p>\n<h4>3-2-10 DIO Converter Module Installation<\/h4>\n<ul>\n<li>First fix the upper clip and then install the DIO Converter module into the DIN RAIL in the direction of the arrow.<\/li>\n<\/ul>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m02-en-03\/mplc-m02-en-03-022.png\" \/><\/p>\n<p>Install DIO Converter Module<\/p>\n<ul>\n<li>Please push up in the direction of the No. 1 arrow first and then pull out in the direction of the No. 2 arrow to disassemble.<\/li>\n<\/ul>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m02-en-03\/mplc-m02-en-03-023.png\" \/><\/p>\n<p>Disassemble DIO Converter Module<\/p>\n","protected":false},"excerpt":{"rendered":"<p>\u26a0Danger Turn off all power before installation of M Ser [&hellip;]<\/p>\n","protected":false},"author":1,"featured_media":0,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[46],"tags":[],"class_list":["post-3188","post","type-post","status-publish","format-standard","hentry","category-en-mplc-m02"],"_links":{"self":[{"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/posts\/3188","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/comments?post=3188"}],"version-history":[{"count":0,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/posts\/3188\/revisions"}],"wp:attachment":[{"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/media?parent=3188"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/categories?post=3188"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/tags?post=3188"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}