{"id":3205,"date":"2026-11-17T18:38:17","date_gmt":"2026-11-17T10:38:17","guid":{"rendered":"https:\/\/resource.fatek.com\/index.php\/2026\/11\/17\/mplc-m02-en-20\/"},"modified":"2026-11-17T18:38:17","modified_gmt":"2026-11-17T10:38:17","slug":"mplc-m02-en-20","status":"publish","type":"post","link":"https:\/\/resource.fatek.com\/index.php\/2026\/11\/17\/mplc-m02-en-20\/","title":{"rendered":"Chapter 20 Repairs and Maintenance"},"content":{"rendered":"<h3>20-1 Precautions<\/h3>\n<p>When performing the required servicing and maintenance, please watch the following requirements because incorrect or careless operations may result in personal injury and equipment damage. <\/p>\n<ul>\n<li>\u26a0 Please confirm that the ambient environment is not exposed to corrosive substances (<em>e.g., <\/em>chlorides and sulfide gas) and combustible substances (<em>e.g.,<\/em> oil mist and cutting powder) or dusty area to prevent PLC System from failure or causing a fire. <\/li>\n<li>\u26a0 Do not contact the terminal to prevent the terminal from getting oxidized or personnel from electrocution.<\/li>\n<li>\u26a0 Shut down the external power and then dismantle the terminal or the screws to avoid personnel electrocution.<\/li>\n<li>\u26a0 Do not apply heavy force on the cables or drag or clip the cable too hard to prevent cable from damage or terminal from loosening while avoiding electrocution. <\/li>\n<li>\u26a0 Confirm that the input voltage is within the rating scope. <\/li>\n<li>\u26a0 Do not attempt to disassemble or modify the module or repair the module privately; otherwise, it may lead to product failure, fire or personnel injury. <\/li>\n<li>After replacing the CPU module, confirm that all programs and parameters are being created in the new CPU module and are duly set. Following that, you may start the PLC System to prevent the controlled component from executing a false action. <\/li>\n<li>Please read the manuals carefully in order to get familiar with the required operation mechanisms when the PLC is running such as procedure change, forced output and RUN\/STOP, etc. The purpose is to prevent incorrect output or equipment damage as may be caused by inaccurate operations. <\/li>\n<li>Before touching the module, please touch the grounding metal first or wear an anti-static bracelet in order to discharge the electrostatic from the human body to prevent it from damaging the module.<\/li>\n<li>When using a mobile phone or communication device, please keep appropriate distance to prevent from interfering with the system as to cause the false action. <\/li>\n<li>Do not install the PLC Control System in an environment exposed to direct sunlight or humidity. <\/li>\n<li>Please confirm that appropriate distance has been maintained between the PLC Control System and the heat source such as coil, heater and resistor, etc. to prevent the component from being exposed to higher temperature. <\/li>\n<li>Please install an emergency power shutdown system and an over-current protection device as required in order to protect the PLC Control System.<\/li>\n<li>During the operations and maintenance process, please check the installation stability in order to avoid unexpected vibrations as to damage the PLC Control System and the controlled component. <\/li>\n<\/ul>\n<h3>20-2 19-1 Pr\u00e9cautions<\/h3>\n<ul>\n<li>Lors de l&#8217;ex\u00e9cution de l&#8217;entretien et de l&#8217;entretien requis, veuillez respecter les exigences suivantes, car des op\u00e9rations incorrectes ou n\u00e9gligentes peuvent entra\u00eener des blessures corporelles et des dommages mat\u00e9riels.<\/li>\n<li>\u26a0 Veuillez confirmer que l&#8217;environnement ambiant n&#8217;est pas expos\u00e9 \u00e0 des substances corrosives (par exemple, des chlorures et des gaz sulfur\u00e9s) et \u00e0 des substances combustibles (par exemple, du brouillard d&#8217;huile et de la poudre de coupe) ou \u00e0 une zone poussi\u00e9reuse pour \u00e9viter que le syst\u00e8me PLC ne tombe en panne ou ne provoque un incendie.<\/li>\n<li>\u26a0 Ne pas toucher le terminal pour \u00e9viter que le terminal ne s&#8217;oxyde ou que le personnel ne s&#8217;\u00e9lectrocute.<\/li>\n<li>\u26a0 Coupez l\u2019alimentation externe puis d\u00e9montez le terminal ou les vis pour \u00e9viter l\u2019\u00e9lectrocution du personnel.<\/li>\n<li>\u26a0 N&#8217;appliquez pas de force excessive sur les c\u00e2bles, ne tirez pas et ne coupez pas trop fort le c\u00e2ble pour \u00e9viter qu&#8217;il ne soit endommag\u00e9 ou que la borne ne se desserre tout en \u00e9vitant l&#8217;\u00e9lectrocution.<\/li>\n<li>\u26a0 V\u00e9rifiez que la tension d&#8217;entr\u00e9e est dans la plage nominale.<\/li>\n<li>\u26a0 N\u2019essayez pas de d\u00e9monter ou de modifier le module ou de r\u00e9parer le module en priv\u00e9\u00a0; sinon, cela peut entra\u00eener une d\u00e9faillance du produit, un incendie ou des blessures corporelles.<\/li>\n<li>Apr\u00e8s avoir remplac\u00e9 le module CPU, v\u00e9rifiez que tous les programmes et les param\u00e8tres sont cr\u00e9\u00e9s dans le nouveau module CPU et sont d\u00fbment d\u00e9finis. Ensuite, vous pouvez d\u00e9marrer le syst\u00e8me PLC pour emp\u00eacher le composant contr\u00f4l\u00e9 d&#8217;ex\u00e9cuter une fausse action.<\/li>\n<li>Veuillez lire attentivement les manuels afin de vous familiariser avec les m\u00e9canismes de fonctionnement requis lorsque l&#8217;API est en cours d&#8217;ex\u00e9cution, comme le changement de proc\u00e9dure, la sortie forc\u00e9e et RUN\/STOP, etc. Le but est d&#8217;\u00e9viter une sortie incorrecte ou des dommages \u00e0 l&#8217;\u00e9quipement qui peuvent \u00eatre caus\u00e9s par des op\u00e9rations inexactes.<\/li>\n<li>Avant de toucher le module, veuillez d&#8217;abord toucher le m\u00e9tal de mise \u00e0 la terre ou porter un bracelet antistatique afin de d\u00e9charger l&#8217;\u00e9lectricit\u00e9 statique du corps humain pour \u00e9viter qu&#8217;il n&#8217;endommage le module.<\/li>\n<li>Lorsque vous utilisez un t\u00e9l\u00e9phone cellulaire ou un appareil de communication, veuillez garder une distance appropri\u00e9e pour \u00e9viter d&#8217;interf\u00e9rer avec le syst\u00e8me et de provoquer une fausse action.<\/li>\n<li>N&#8217;installez pas le syst\u00e8me de contr\u00f4le PLC dans un environnement expos\u00e9 \u00e0 la lumi\u00e8re directe du soleil ou \u00e0 l&#8217;humidit\u00e9.<\/li>\n<li>Veuillez confirmer qu&#8217;une distance appropri\u00e9e a \u00e9t\u00e9 maintenue entre le syst\u00e8me de contr\u00f4le PLC et la source de chaleur telle que la bobine, le radiateur et la r\u00e9sistance, etc. pour \u00e9viter que le composant ne soit expos\u00e9 \u00e0 une temp\u00e9rature plus \u00e9lev\u00e9e.<\/li>\n<li>Veuillez installer un syst\u00e8me d&#8217;arr\u00eat d&#8217;urgence de l&#8217;alimentation et un dispositif de protection contre les surintensit\u00e9s au besoin afin de prot\u00e9ger le syst\u00e8me de contr\u00f4le PLC.<\/li>\n<li>Pendant le processus d&#8217;exploitation et de maintenance, veuillez v\u00e9rifier la stabilit\u00e9 de l&#8217;installation afin d&#8217;\u00e9viter des vibrations inattendues susceptibles d&#8217;endommager le syst\u00e8me de contr\u00f4le PLC et le composant contr\u00f4l\u00e9.<\/li>\n<\/ul>\n<h3>20-3 Daily Maintenance<\/h3>\n<p>The connection terminal may present loosening signs after running the PLC System for a longer time. To maintain the PLC System at normal operating status, the inspection should be executed according to daily maintenance items after confirming that the ambient environment meets the environmental specifications that are specified in Chapter 3. When discovering any abnormal signs, please make improvements immediately according to the specified troubleshooting method.<\/p>\n<h4>20-3-1 Maintenance Tools<\/h4>\n<ul>\n<li>Screwdriver<\/li>\n<li>Stain removing alcohol<\/li>\n<li>Cleaning cotton rag<\/li>\n<li>Swab<\/li>\n<\/ul>\n<h4>20-3-2 Daily Maintenance Items<\/h4>\n<p>Daily maintenance items<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>No.<\/p>\n<\/td>\n<td colspan=\"2\">\n<p>Inspection Item<\/p>\n<\/td>\n<td>\n<p>Job Content<\/p>\n<\/td>\n<td>\n<p>Judgment Standard<\/p>\n<\/td>\n<td>\n<p>Action<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>1<\/p>\n<\/td>\n<td colspan=\"2\">\n<p>Appearance cleanliness<\/p>\n<\/td>\n<td>\n<p>Visual inspection<\/p>\n<\/td>\n<td>\n<p>If there are any stains.<\/p>\n<\/td>\n<td>\n<p>Wipe off the stains.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>2<\/p>\n<\/td>\n<td colspan=\"2\">\n<p>Appearance completeness<\/p>\n<\/td>\n<td>\n<p>Visual inspection<\/p>\n<\/td>\n<td>\n<p>If there is any damage.<\/p>\n<\/td>\n<td>\n<p>Wipe off the stains.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>3<\/p>\n<\/td>\n<td colspan=\"2\">\n<p>Back board and DIN Rail installation status<\/p>\n<\/td>\n<td>\n<p>If the back board and the DIN rail are securely installed.<\/p>\n<\/td>\n<td>\n<p>The back board and the DIN rail must be securely installed.<\/p>\n<\/td>\n<td>\n<p>Check if the back board and the rail are properly installed.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>4<\/p>\n<\/td>\n<td colspan=\"2\">\n<p>Locking status of module connection area<\/p>\n<\/td>\n<td>\n<p>If the locking of module connection area is detaching or loosening.<\/p>\n<\/td>\n<td>\n<p>The locking device of the module connection area must be located at the locking position.<\/p>\n<\/td>\n<td>\n<p>Move the locking device of the module connection area back to the locking position. <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>5<\/p>\n<\/td>\n<td colspan=\"2\">\n<p>Appearance of wiring cable<\/p>\n<\/td>\n<td>\n<p>If the wiring cable is damaged. <\/p>\n<\/td>\n<td>\n<p>The wiring cable shall be intact without any damage. <\/p>\n<\/td>\n<td>\n<p>Replace the wiring cable. <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>6<\/p>\n<\/td>\n<td colspan=\"2\">\n<p>Connection status of each terminal<\/p>\n<\/td>\n<td>\n<p>If the terminal is loosening. <\/p>\n<\/td>\n<td>\n<p>The terminal cannot present any loosening sign. <\/p>\n<\/td>\n<td>\n<p>Connect the terminal properly.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>7<\/p>\n<\/td>\n<td>\n<p>Power module<\/p>\n<\/td>\n<td>\n<p>PWR lamp<\/p>\n<\/td>\n<td>\n<p>If the PWR lamp is ON.<\/p>\n<\/td>\n<td>\n<p>The PWR lamp must be ON.<\/p>\n<\/td>\n<td rowspan=\"5\">\n<p>For detailed troubleshooting, please refer to \u201cExpansion Module Troubleshooting\u201d section. <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"4\">\n<p>8<\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>Expansion module<\/p>\n<\/td>\n<td>\n<p>PWR lamp<\/p>\n<\/td>\n<td>\n<p>If the PWR lamp is ON.<\/p>\n<\/td>\n<td>\n<p>The PWR lamp must be ON.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>RUN lamp<\/p>\n<\/td>\n<td>\n<p>If the RUN lamp is ON.<\/p>\n<\/td>\n<td>\n<p>The RUN lamp must be ON.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>ERR lamp<\/p>\n<\/td>\n<td>\n<p>If the ERR lamp is OFF.<\/p>\n<\/td>\n<td>\n<p>The ERR lamp must be OFF.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>ALM lamp<\/p>\n<\/td>\n<td>\n<p>If the ALM lamp is OFF.<\/p>\n<\/td>\n<td>\n<p>The ALM lamp must be OFF.<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>* Remove the expansion module and then use a swab to wipe off the dust and stains present in inaccessible corners.<\/p>\n<h3>20-4 Regular Maintenance<\/h3>\n<p>When the routine daily maintenance is required, the module should be serviced cyclically according to the actual operating environment. The inspection should be executed according to daily maintenance items after confirming that the ambient environment meets the environmental specifications that are specified in Chapter 3. When discovering any abnormal signs, please make improvement immediately according to the specified troubleshooting method.<\/p>\n<h4>20-4-1 Maintenance Tools<\/h4>\n<ul>\n<li>Screwdriver<\/li>\n<li>Stain removing alcohol<\/li>\n<li>Cleaning cotton rag<\/li>\n<li>Swab<\/li>\n<li>Multimeter<\/li>\n<li>Temperature gauge<\/li>\n<li>Hygrometer<\/li>\n<\/ul>\n<h4>20-4-2 Regular Maintenance Items<\/h4>\n<p>Regular maintenance items table.<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>No.<\/p>\n<\/td>\n<td>\n<p>Inspection Item<\/p>\n<\/td>\n<td>\n<p>Job Content<\/p>\n<\/td>\n<td>\n<p>Judgment Standard<\/p>\n<\/td>\n<td>\n<p>Action<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>1<\/p>\n<\/td>\n<td>\n<p>Environmental temperature and humidity<\/p>\n<\/td>\n<td>\n<p>Measure with temperature gauge and hygrometer. <\/p>\n<\/td>\n<td>\n<p>Must meet the environmental specifications established for the respective module.<\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>Confirm the reasons causing the environmental change and then remove the problem. <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>2<\/p>\n<\/td>\n<td>\n<p>Air<\/p>\n<\/td>\n<td>\n<p>Measure the corrosive gas<\/p>\n<\/td>\n<td>\n<p>Corrosive gas should not be detected.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>3<\/p>\n<\/td>\n<td>\n<p>Power voltage<\/p>\n<\/td>\n<td>\n<p>Measured the supplied AC power.<\/p>\n<\/td>\n<td>\n<p>Must meet the power module specifications.<\/p>\n<\/td>\n<td>\n<p>Confirm the power supply system.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>4<\/p>\n<\/td>\n<td>\n<p>Dust\/stain attaching status<\/p>\n<\/td>\n<td>\n<p>Check the appearance<\/p>\n<\/td>\n<td>\n<p>If any dust and stain. <\/p>\n<\/td>\n<td>\n<p>Wipe off the dust and the stains.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>5<\/p>\n<\/td>\n<td>\n<p>Module installation status<\/p>\n<\/td>\n<td>\n<p>Check if the module is securely installed. <\/p>\n<\/td>\n<td>\n<p>The module must be securely installed.<\/p>\n<\/td>\n<td>\n<p> For correct installation method, please refer to \u201cInstallation and Wiring\u201d section. <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>6<\/p>\n<\/td>\n<td>\n<p>Locking status of connection area between modules<\/p>\n<\/td>\n<td>\n<p>If the locking of module connection area is detaching or loosening.<\/p>\n<\/td>\n<td>\n<p>The locking device of the module connection area must be located at the locking position.<\/p>\n<\/td>\n<td>\n<p>Move the locking device of the module connection area back to the locking position.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>7<\/p>\n<\/td>\n<td>\n<p>Terminal connection status<\/p>\n<\/td>\n<td>\n<p>Check by plugging and unplugging the connection port. <\/p>\n<\/td>\n<td>\n<p>The terminal cannot present any loosening signs. <\/p>\n<\/td>\n<td>\n<p>Connect the terminal properly. <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>8<\/p>\n<\/td>\n<td>\n<p>Appearance of wiring cable<\/p>\n<\/td>\n<td>\n<p>If the wiring cable is presenting any damage signs. <\/p>\n<\/td>\n<td>\n<p>The wiring cable should be intact without any damage.<\/p>\n<\/td>\n<td>\n<p>Replace the wiring cable.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>9<\/p>\n<\/td>\n<td>\n<p>PLC System diagnosis <\/p>\n<\/td>\n<td>\n<p>Check the error record.<\/p>\n<\/td>\n<td>\n<p>Caused by careless error. <\/p>\n<\/td>\n<td>\n<p>For detailed troubleshooting, please refer to \u201cExpansion Module Troubleshooting\u201d section.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>10<\/p>\n<\/td>\n<td>\n<p>Max. scanning time<\/p>\n<\/td>\n<td>\n<p>Check the status value of R35371 through the monitoring page.<\/p>\n<\/td>\n<td>\n<p>The maximum scanning time must be without the scope allowed by the system specifications. <\/p>\n<\/td>\n<td>\n<p>Check the reasons causing the extension of scanning time. <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>* Remove the expansion module and then use a swab to wipe off the dust and stains present in inaccessible corners.<\/p>\n","protected":false},"excerpt":{"rendered":"<p>20-1 Precautions When performing the required servicing [&hellip;]<\/p>\n","protected":false},"author":1,"featured_media":0,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[46],"tags":[],"class_list":["post-3205","post","type-post","status-publish","format-standard","hentry","category-en-mplc-m02"],"_links":{"self":[{"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/posts\/3205","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/comments?post=3205"}],"version-history":[{"count":0,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/posts\/3205\/revisions"}],"wp:attachment":[{"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/media?parent=3205"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/categories?post=3205"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/tags?post=3205"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}