{"id":3213,"date":"2026-11-17T18:38:22","date_gmt":"2026-11-17T10:38:22","guid":{"rendered":"https:\/\/resource.fatek.com\/index.php\/2026\/11\/17\/mplc-m03-en-06\/"},"modified":"2026-11-17T18:38:22","modified_gmt":"2026-11-17T10:38:22","slug":"mplc-m03-en-06","status":"publish","type":"post","link":"https:\/\/resource.fatek.com\/index.php\/2026\/11\/17\/mplc-m03-en-06\/","title":{"rendered":"Chapter 6 Program scanning time"},"content":{"rendered":"<h3>6-1  Setting the Scanning Time<\/h3>\n<p>The program scanning time means the duration required for the PLC to complete the scanning of program change per time, and the PLC will execute the scanning from left to right and from top to bottom cyclically according to the procedure. Such working type is executed by scanning the status of each input point sequentially according to the system procedure. During the entire process, the status will be computed according to the procedure set by the user and then the system will issue the corresponding control signal sequentially to each output point. During the scanning process, apart from the aforesaid items, the PLC needs to carry out the self-diagnosis in order to communicate with external devices for processing the events that have been detected. Normally, the PLC is executing the scanning from top to bottom item by item and the event that interrupts the cyclic scanning will be regarded as the suspension in order to suspend the corresponding suspension procedure. After that, the system will continue the scanning from the suspended point. The scanning time is closely related to the length of the user\u2019s procedure, the type of suspension and the speed of command executed by the PLC. If the user sets up a longer procedure, the command execution time will take a pretty large percentage of the scanning time. Therefore, the scanning time will be extended according to the length of the procedure, the type of the command, the suspension processing and the communication, etc. To know about the information relating to PLC scanning time, max. scanning time and min. scanning time, the user may refer to the corresponding relay setting table specified in \u201c6.2: Scanning Time Monitoring\u201d.<\/p>\n<p>In the meantime, the user may also set up a fixed scanning time for the PLC to run the user\u2019s procedure according to such scanning time in order to coordinate with the required special applications. Through the monitoring window, the user may input the fixed scanning time required for R35373 special relay. Following that, the PLC will run the user procedure according to the fixed scanning time and the unit required for the input time will be expressed as \u201cms\u201d. If the actual execution time was longer than configuration time, the operation will be based on the real time<\/p>\n<p> <img decoding=\"async\" alt=\"D:\\patrick\\\u8aaa\u660e\u66f8\u7ffb\u8b6f_\u529f\u80fd\u7bc7\\\u5716\\17.PNG\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m03-en-06\/mplc-m03-en-06-001.png\" \/><\/p>\n<p>Figure 17 Configuration of fixed scanning time<\/p>\n<p>Through FUN08 MOV function, the user may also input the desired R35373 value to the relay.<\/p>\n<p>Example:<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m03-en-06\/mplc-m03-en-06-002.png\" \/><\/p>\n<p>Figure 18 Example program of changing fixed scanning time<\/p>\n<p>After turning on Contact-A of M1, the system will export \u201c20\u201d to R35373 (time unit is expressed as \u201cms\u201d). Therefore, the scanning will become 20ms.<\/p>\n<h3>6-2  Monitoring the Scanning Time<\/h3>\n<p>To check the duration of scanning time, the max. or the min. scanning time (such time will change along with the size of user\u2019s program), you may input R35370, R35371, R35372 and R35373 in the monitoring window and then start the inquiry.<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>Corresponding relay<\/p>\n<\/td>\n<td>\n<p>Function description<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>R35370<\/p>\n<\/td>\n<td>\n<p>Current scanning time<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>R35371<\/p>\n<\/td>\n<td>\n<p>Max. scanning time<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>R35372<\/p>\n<\/td>\n<td>\n<p>Min. scanning time<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>R35373<\/p>\n<\/td>\n<td>\n<p>Fixed scanning time<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>Table 7 Monitoring the scanning time of corresponding relay<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m03-en-06\/mplc-m03-en-06-003.png\" \/><\/p>\n<p>F<\/p>\n<p>Figure 19 Inquiry of Current scanning time, Max. scanning time, Min. scanning time.<\/p>\n","protected":false},"excerpt":{"rendered":"<p>6-1 Setting the Scanning Time The program scanning time [&hellip;]<\/p>\n","protected":false},"author":1,"featured_media":0,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[47],"tags":[],"class_list":["post-3213","post","type-post","status-publish","format-standard","hentry","category-en-mplc-m03"],"_links":{"self":[{"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/posts\/3213","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/comments?post=3213"}],"version-history":[{"count":0,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/posts\/3213\/revisions"}],"wp:attachment":[{"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/media?parent=3213"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/categories?post=3213"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/tags?post=3213"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}