{"id":3228,"date":"2026-11-17T18:38:45","date_gmt":"2026-11-17T10:38:45","guid":{"rendered":"https:\/\/resource.fatek.com\/index.php\/2026\/11\/17\/mplc-m04-en-03\/"},"modified":"2026-11-17T18:38:45","modified_gmt":"2026-11-17T10:38:45","slug":"mplc-m04-en-03","status":"publish","type":"post","link":"https:\/\/resource.fatek.com\/index.php\/2026\/11\/17\/mplc-m04-en-03\/","title":{"rendered":"Chapter 3 Introduction of UperLogic"},"content":{"rendered":"<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>\u26a0Danger<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<ol>\n<li>When installing or removing the M-series CPU modules and various expansion modules or the equipment connected to it, all power must be turned off, otherwise it may cause electric shock or wrong action, resulting in death or serious personal injury and damage to the machine equipment.<\/li>\n<li>Before the installation and wiring construction is completed, do not tear off the dust-proof paper on the PLC cooling hole, so as to prevent the drilling iron filings or wiring scraps from falling into the PLC during construction, causing fire, failure or malfunction.<\/li>\n<li>After confirming that the installation and wiring are all completed, remember to tear off the above-mentioned dustproof paper to avoid poor heat dissipation of the PLC, resulting in fire, failure or malfunction.<\/li>\n<\/ol>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>This section describes the functions that will be displayed in the UperLogic software interface. <\/p>\n<p>Displayed in the webpage below are the UperLogic working window and the status of the respective connection window. <\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m04-en-03\/mplc-m04-en-03-001.jpg\" \/><\/p>\n<p>Fig. 8: Webpage configuration<\/p>\n<h3>3-1 File<\/h3>\n<p>Such function allows the user to perform project operations such as opening a new project, saving a project, saving a new file, importing and exporting, and printing.<\/p>\n<p><img decoding=\"async\" alt=\"D:\\patrick\\\u66f4\u63db\u624b\u518a\u5716\u7247\\\u5716_en\\9.PNG\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m04-en-03\/mplc-m04-en-03-002.png\" \/><\/p>\n<p>Fig. 9: File<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p><strong>Function<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>Description<\/strong><\/p>\n<\/td>\n<td>\n<p>Detailed introduction<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Open new project<\/p>\n<\/td>\n<td>\n<p>Create a new project for executing the editing. <\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_4-1_Open_a\">Section 4.1.<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Open project<\/p>\n<\/td>\n<td>\n<p>Open previously written project for executing the editing.<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_4-7_Open_Old\">Section 4.7<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Save project<\/p>\n<\/td>\n<td>\n<p>Save currently edited project to disk. <\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_4-4_Save_the\">Section 4.4<\/a>.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Save project as<\/p>\n<\/td>\n<td>\n<p>Save currently edited project as another project name in the disk. <\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_4-5_Save_a\">Section 4.5<\/a>.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Close project<\/p>\n<\/td>\n<td>\n<p>Close currently edited project. <\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td>\n<p>Import<\/p>\n<\/td>\n<td>\n<p>Import previously saved information to project. <\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_4-6_Project_Content\">Section 4.6.<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Export<\/p>\n<\/td>\n<td>\n<p>Export the information from project to disk. <\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_4-6_Project_Content\">Section 4.6<\/a>.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Exit<\/p>\n<\/td>\n<td>\n<p>Close UperLogic.<\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>Table 1: Detailed file function introduction<\/p>\n<h3>3-2 Quick Toolbar<\/h3>\n<p>The Quick Toolbar allows users to select frequently used functions for quick selection.<\/p>\n<p><img decoding=\"async\" alt=\"D:\\patrick\\\u66f4\u63db\u624b\u518a\u5716\u7247\\\u5716_en\\10.PNG\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m04-en-03\/mplc-m04-en-03-003.png\" \/><\/p>\n<p>Fig. 10: Quick Toolbar<\/p>\n<p>Quick key will display the function that can be used under current status. <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p><strong>Status<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>Quick Toolbar display status<\/strong><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Offline editing, and project not opened.<\/p>\n<\/td>\n<td>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m04-en-03\/mplc-m04-en-03-004.png\" \/><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Offline editing, and project opened.<\/p>\n<\/td>\n<td>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m04-en-03\/mplc-m04-en-03-005.png\" \/><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Online monitoring, and PLC is running <\/p>\n<\/td>\n<td>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m04-en-03\/mplc-m04-en-03-006.png\" \/><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Online monitoring, and PLC stops running<\/p>\n<\/td>\n<td>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m04-en-03\/mplc-m04-en-03-007.png\" \/><\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>Table 2: Quick Toolbar display status<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p><strong>Function<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>Description<\/strong><\/p>\n<\/td>\n<td>\n<p>Detailed Introduction<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Open new project<\/p>\n<\/td>\n<td>\n<p>Create a new project for executing the editing.<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#ch4_1\">Section 4.1<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Open project<\/p>\n<\/td>\n<td>\n<p>Open previously written project for executing the editing.<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#ch4_7\">Section 4.7<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Save project<\/p>\n<\/td>\n<td>\n<p>Save currently edited project to disk.<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#ch4_4\">Section 4.4<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Run (F9)<\/p>\n<\/td>\n<td>\n<p>Run PLC<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_11-5_Run\/Stop_PLC\">Section 11.5<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Stop Run (Shift+F9)<\/p>\n<\/td>\n<td>\n<p>Stops running PLC<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#ch11_5\">Section 11.5<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Upload<\/p>\n<\/td>\n<td>\n<p>Upload project from PLC to software<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_11-3_Upload\">Section 11.3<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Download<\/p>\n<\/td>\n<td>\n<p>Download currently edited project to PLC<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_11-4_Download\">Section 11.4<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Clear data<\/p>\n<\/td>\n<td>\n<p>Clear PLC data<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_11-6_Clear_PLC\">Section 11.6<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>PLC status<\/p>\n<\/td>\n<td>\n<p>Display current PLC status<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_11-7_PLC_Status\">Section 11.7<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Self-defined quick toolbar<\/p>\n<\/td>\n<td>\n<p>The user may define its own quick toolbar<\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>Table 3: Quick toolbar function introduction<\/p>\n<h3>3-3 Interface Outlook Setting<\/h3>\n<p>This function provides a number of software outlook interfaces for users to execute the adjustment according to their own demand. <\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m04-en-03\/mplc-m04-en-03-008.png\" \/><\/p>\n<p>Fig. 11: Interface outlook setting options<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p><strong>Format<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>Preview<\/strong><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Office Color<\/p>\n<p>Mode<\/p>\n<\/td>\n<td>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m04-en-03\/mplc-m04-en-03-009.png\" \/><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Fatek Dark Mode<\/p>\n<\/td>\n<td>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m04-en-03\/mplc-m04-en-03-010.png\" \/><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Fatek Light Mode<\/p>\n<\/td>\n<td>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m04-en-03\/mplc-m04-en-03-011.png\" \/><\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>Table 4: Interface outlook format preview<\/p>\n<h3>3-4 Ribbon Tag Page<\/h3>\n<p>This function is designed to organize the created commands in a \u201ctag\u201d group, and each group comprises the required commands. Each application program corresponds to the related tag group in order to demonstrate the functions that will be provided by the program. Its purpose is allowing the user to search and use the functions of the application program more easily, as per the tag categorization indicated in the figure below. <\/p>\n<h4>3-4-1 Project<\/h4>\n<p>This tag page is mainly used to set the overall information of the project such as memory configuration and security.<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m04-en-03\/mplc-m04-en-03-012.png\" \/><\/p>\n<p>Fig. 12: Project tag page<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>Type<\/p>\n<\/td>\n<td>\n<p>Function<\/p>\n<\/td>\n<td>\n<p>Description<\/p>\n<\/td>\n<td>\n<p>Detailed Introduction<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"7\">\n<p>System configuration<\/p>\n<\/td>\n<td>\n<p>Device View<\/p>\n<\/td>\n<td>\n<p>The equipment required for planning and checking current status of PLC.<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#ch10\">Section 10<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>I\/O Configuration<\/p>\n<\/td>\n<td>\n<p>Set the I\/O status<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_5-1_I\/O_Configuration\">Section 5.1<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Memory Allocation<\/p>\n<\/td>\n<td>\n<p>Check current memory configuration<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_5-2_Setting_up\">Section 5.2<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>ROR Register<\/p>\n<\/td>\n<td>\n<p>Check and edit the read-only Register. <\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_5-3_Setting_up\">Section 5.3<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Server Configuration<\/p>\n<\/td>\n<td>\n<p>Set the connection between PLC and server<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_5-4_Server_Configuration\">Section 5.4<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Communication Configuration<\/p>\n<\/td>\n<td>\n<p>Check and edit the settings of  communication configuration.<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#ch5_4\">Section 5.5<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Descrete Register Allocation<\/p>\n<\/td>\n<td>\n<p>Check current descrete and  register Allocation<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#ch5_2\">Section 5.2<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"4\">\n<p>Program Unit<\/p>\n<\/td>\n<td>\n<p>Main Program<\/p>\n<\/td>\n<td>\n<p>Add or revise Master Program<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_6-1_Main_Program\">Section 6.1<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Sub Program<\/p>\n<\/td>\n<td>\n<p>Add or revise main sub-program<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_Toc52807278\">Section 6.1<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Special Program<\/p>\n<\/td>\n<td>\n<p>Add or modify interrupt program or special Ppogram<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_6-6_Interrupt_Program\">Section 6.6<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>FCM Program<\/p>\n<\/td>\n<td>\n<p>Add or modify function module programs.<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_6-7_Function_Module\">Section 6.7<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Data Table<\/p>\n<\/td>\n<td>\n<p>Table Edit<\/p>\n<\/td>\n<td>\n<p>Set required tables<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#ch7\">Section 7<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Status Page<\/p>\n<\/td>\n<td>\n<p>Status Page<\/p>\n<\/td>\n<td>\n<p>Check current status of PLC Register<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#ch12_3\">Section 12.2<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Comment <\/p>\n<\/td>\n<td>\n<p>Comments<\/p>\n<\/td>\n<td>\n<p>Set and edit the comment<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#ch8\">Section 8<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Tag<\/p>\n<\/td>\n<td>\n<p>Tag<\/p>\n<\/td>\n<td>\n<p>Tag setting<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_8-5_Tag\">Section 8.5<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Element Memory<\/p>\n<\/td>\n<td>\n<p>Element Memory<\/p>\n<\/td>\n<td>\n<p>Set and edit the element memory<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_Element_Memory\">Section 12.3<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>Project<\/p>\n<\/td>\n<td>\n<p>Security<\/p>\n<\/td>\n<td>\n<p>Edit PLC security related setting.<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#ch13\">Section 13<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Option<\/p>\n<\/td>\n<td>\n<p>Set project automatic backup<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#ch4_2\">Section 4.2<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"7\">\n<p>Motion control<\/p>\n<\/td>\n<td>\n<p>Motion Network<\/p>\n<\/td>\n<td>\n<p>Edit motion network related setting<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_9-1_Motion_Network\">Section 9.1<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Motion Axis<\/p>\n<\/td>\n<td>\n<p>Edit motion axis related setting<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_9-2_Motion_Axis\">Section 9.2<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Motion Point<\/p>\n<\/td>\n<td>\n<p>Edit the motion point related setting<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_9-3_Motion_Point\">Section 9.3<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Motion Flow<\/p>\n<\/td>\n<td>\n<p>Edit the motion process related setting<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_9-4_Motion_Flow\">Section 9.4<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Motion Sync Control<\/p>\n<\/td>\n<td>\n<p>Edit the motion synchronization related setting<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_9-5_Motion_Sync\">Section 9.5<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Motion Param Mapping<\/p>\n<\/td>\n<td>\n<p>Edit the motion network related setting<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_9-6_Motion_Param\">Section 9.6<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Motion Recipe<\/p>\n<\/td>\n<td>\n<p>Edit the motion recipe<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_9-7_Motion_Recipe\">Section 9.7<\/a><\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>Table 5: Setting project tag page <\/p>\n<h4>3-4-2 Design<\/h4>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m04-en-03\/mplc-m04-en-03-013.png\" \/> This tab page is mainly used to edit the related design of the ladder diagram and the motion flow block program.<\/p>\n<p>Fig. 13: Designing tag page<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>Type<\/p>\n<\/td>\n<td>\n<p>Function<\/p>\n<\/td>\n<td>\n<p>Description<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"3\">\n<p>Clip book<\/p>\n<\/td>\n<td>\n<p>Paste<\/p>\n<\/td>\n<td>\n<p>Paste the copied or clipped object<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Cut<\/p>\n<\/td>\n<td>\n<p>Cut the selected object<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Copy<\/p>\n<\/td>\n<td>\n<p>Copy the selected object<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"4\">\n<p>Edit<\/p>\n<\/td>\n<td>\n<p>Delete<\/p>\n<\/td>\n<td>\n<p>Delete the selected object<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Undo<\/p>\n<\/td>\n<td>\n<p>Restore to previous status<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Redo<\/p>\n<\/td>\n<td>\n<p>Cancel the restore<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Select All<\/p>\n<\/td>\n<td>\n<p>Select all objects<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"3\">\n<p>Find\/Replace<\/p>\n<\/td>\n<td>\n<p>Find<\/p>\n<\/td>\n<td>\n<p>Search object in Ladder Diagram<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Replace<\/p>\n<\/td>\n<td>\n<p>Search and replace corresponding object<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Goto<\/p>\n<\/td>\n<td>\n<p>To specific ladder program network bar<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>Ladder Block<\/p>\n<\/td>\n<td>\n<p>Block Close<\/p>\n<\/td>\n<td>\n<p>Close ladder block<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Block Open<\/p>\n<\/td>\n<td>\n<p>Open ladder block<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>Network<\/p>\n<\/td>\n<td>\n<p>Insert<\/p>\n<\/td>\n<td>\n<p>Insert network in upper or lower side<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Expand <\/p>\n<\/td>\n<td>\n<p>Compress or expand the network<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"24\">\n<p>Ladder Diagram<\/p>\n<\/td>\n<td>\n<p>Cursor Arrow<\/p>\n<\/td>\n<td>\n<p>Return to the mouse status where object is not being selected<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>A contact<\/p>\n<\/td>\n<td>\n<p>Constant open contact<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>B contact<\/p>\n<\/td>\n<td>\n<p>Constant close contact<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>TU contact<\/p>\n<\/td>\n<td>\n<p>Create a pulse wave when contact is energized (0\u21921).<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>TD contact<\/p>\n<\/td>\n<td>\n<p>Create a pulse wave when contact is closed (1\u21920).<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Coil<\/p>\n<\/td>\n<td>\n<p>Send computation result to the coil. <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Inverse Coil<\/p>\n<\/td>\n<td>\n<p>Send computation result back to coil<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Set Coil<\/p>\n<\/td>\n<td>\n<p>Set the coil.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Reset Coil<\/p>\n<\/td>\n<td>\n<p>Clear the coil.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Inverse<\/p>\n<\/td>\n<td>\n<p>Execute reverse phase for node status.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>TU Power Flow<\/p>\n<\/td>\n<td>\n<p>Retrieve upper differential for node status<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>TD Power Flow<\/p>\n<\/td>\n<td>\n<p>Retrieve lower differential for node status<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Horizontal Short<\/p>\n<\/td>\n<td>\n<p>Add horizontal line in Ladder Diagram<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Vertical Short<\/p>\n<\/td>\n<td>\n<p>Add vertical line in Ladder Diagram<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Horizontal Long<\/p>\n<\/td>\n<td>\n<p>Add long horizontal line in Ladder Diagram<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Set<\/p>\n<\/td>\n<td>\n<p>Set all bits for each point or Register (set as 1).<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Reset<\/p>\n<\/td>\n<td>\n<p>Clear all bits from each point or Register (set as 0).<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Timer<\/p>\n<\/td>\n<td>\n<p>General Timer command<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Counter<\/p>\n<\/td>\n<td>\n<p>General Counter command<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Function<\/p>\n<\/td>\n<td>\n<p>Set corresponding Function command<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Cursor Delete<\/p>\n<\/td>\n<td>\n<p>Delete object from Ladder Diagram<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Delete Vertical Short<\/p>\n<\/td>\n<td>\n<p>Delete vertical line from Ladder Diagram<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Delete Horizontal Long<\/p>\n<\/td>\n<td>\n<p>Delete horizontal line from Ladder Diagram<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Zooming<\/p>\n<\/td>\n<td>\n<p>Open the table setting corresponding to application command<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"13\">\n<p>Motion Process<\/p>\n<\/td>\n<td>\n<p>Finish<\/p>\n<\/td>\n<td>\n<p>Finish motion control<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Branch Selection<\/p>\n<\/td>\n<td>\n<p>Select the corresponding branch<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Horizontal Branch<\/p>\n<\/td>\n<td>\n<p>Simultaneous branching<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Coverage<\/p>\n<\/td>\n<td>\n<p>Make motion process branches converge<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Point Reset<\/p>\n<\/td>\n<td>\n<p>Set the reset process<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Position Control<\/p>\n<\/td>\n<td>\n<p>Set the positioning control process<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Speed Control<\/p>\n<\/td>\n<td>\n<p>Set speed control process<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Torque Control<\/p>\n<\/td>\n<td>\n<p>Set torque control process<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Standby<\/p>\n<\/td>\n<td>\n<p>Set standby process<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Sub-process<\/p>\n<\/td>\n<td>\n<p>Set up Sub-process<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Page Skipping<\/p>\n<\/td>\n<td>\n<p>Skip to other process<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Synchronizing Control<\/p>\n<\/td>\n<td>\n<p>Set synchronizing control process<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Computation<\/p>\n<\/td>\n<td>\n<p>Execute computing<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>Table 6: Setting tag design page<\/p>\n<h4>3-4-3 PLC<\/h4>\n<p>This tag page is mainly used for editing the Ladder Diagram related design. <\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m04-en-03\/mplc-m04-en-03-014.png\" \/><\/p>\n<p>Fig. 14: PLC tag page<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>Type<\/p>\n<\/td>\n<td>\n<p>Function<\/p>\n<\/td>\n<td>\n<p>Description<\/p>\n<\/td>\n<td>\n<p>Detailed introduction<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"4\">\n<p>PLC<\/p>\n<\/td>\n<td>\n<p>Run PLC<\/p>\n<\/td>\n<td>\n<p>Run PLC<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#ch11_5\">Section 11.5<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Stop PLC<\/p>\n<\/td>\n<td>\n<p>Stop running PLC<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#ch11_5\">Section 11.5<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Trail Run<\/p>\n<\/td>\n<td>\n<p>Test project while editing online<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_11-10_Online_Edit\">Section 11.10<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Discard Change<\/p>\n<\/td>\n<td>\n<p>Abandon the action of online editing<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_11-10_Online_Edit\">Section 11.10<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>Operation<\/p>\n<\/td>\n<td>\n<p>Upload<\/p>\n<\/td>\n<td>\n<p>Upload project from PLC to software<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#ch11_3\">Section 11.3<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Download<\/p>\n<\/td>\n<td>\n<p>Download currently edited project to PLC.<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_\u4e0b\u8f09\">Section 11.4<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Syntax Check<\/p>\n<\/td>\n<td>\n<p>Syntax Check<\/p>\n<\/td>\n<td>\n<p>Check if syntax error exists in Ladder Diagram<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_6-5_Syntax_Check\">Section 6.5<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"3\">\n<p>Mode<\/p>\n<\/td>\n<td>\n<p>Offline Edit<\/p>\n<\/td>\n<td>\n<p>Edit when not connected with PLC. <\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_11-2_Offline_Edit\">Section 11.2<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Online Monitor<\/p>\n<\/td>\n<td>\n<p>Moniter when connected with PLC.<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_11-1_Connection\">Section 11.1<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Online Editing<\/p>\n<\/td>\n<td>\n<p>Edit when connected with PLC.<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_11-10_Online_Edit\">Section 11.10<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"3\">\n<p>Monitor<\/p>\n<\/td>\n<td>\n<p>Status Page<\/p>\n<\/td>\n<td>\n<p>Check current status of PLC Register<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#ch12_3\">Section 12.2<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Data Chart<\/p>\n<\/td>\n<td>\n<p>The Trend Curve used for checking the change of each Register. <\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_12-2-3_Data_Chart\">Section 12.2.3<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Motion Chart<\/p>\n<\/td>\n<td>\n<p>Check current status of motion control<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_9-1-4_Monitor_Chart\">Section 9.1.4<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Connect<\/p>\n<\/td>\n<td>\n<p>Connection Parameter<\/p>\n<\/td>\n<td>\n<p>Set up PLC connection method and relevant parameters<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_\u9023\u7dda\">Section 11.1<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"4\">\n<p>Others<\/p>\n<\/td>\n<td>\n<p>Quick Control<\/p>\n<\/td>\n<td>\n<p>Set up PLC-related operation in quicker way<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_11-9_Quick_Control\">Section 11.9<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>PLC Setting<\/p>\n<\/td>\n<td>\n<p>Set up PLC-related setting<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_11-8_PLC_Setting\">Section 11.8<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Clear PLC<\/p>\n<\/td>\n<td>\n<p>Clear PLC data<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#ch11_6\">Section 11.6<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>PLC Status<\/p>\n<\/td>\n<td>\n<p>Display current PLC status<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#ch11_7\">Section 11.7<\/a><\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>Table 7: Setting PLC tag page<\/p>\n<h4>3-4-4 View<\/h4>\n<p>This tag page is mainly used for editing the Ladder Diagram related design.<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m04-en-03\/mplc-m04-en-03-015.png\" \/><\/p>\n<p>Fig. 15: Inspection tag page<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>Type<\/p>\n<\/td>\n<td>\n<p>Function<\/p>\n<\/td>\n<td>\n<p>Description<\/p>\n<\/td>\n<td>\n<p>Detailed introduction<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"5\">\n<p>Project Window<\/p>\n<\/td>\n<td>\n<p>Project Management<\/p>\n<\/td>\n<td>\n<p>Display or hide project management window.<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_3-5_Project_Window\">Section 3.5<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Tool Box<\/p>\n<\/td>\n<td>\n<p>Display or hide toolkit<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_3-5-2_Tool_Box\">Section 3.5.2<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Module List<\/p>\n<\/td>\n<td>\n<p>Display or hide module list<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_10-2_Module_List\">Section 10.2<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Memory Address<\/p>\n<\/td>\n<td>\n<p>Display or hide the memory address<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_3-5-4_Position_of\">Section 3.5.4<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Cross Reference<\/p>\n<\/td>\n<td>\n<p>Display or hide cross reference<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_3-5-5_Cross_Reference\">Section 3.5.5<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"6\">\n<p>View Setting<\/p>\n<\/td>\n<td>\n<p>Program Unit Comment<\/p>\n<\/td>\n<td>\n<p>Display or hide program comment<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_6-1-5_Inputting_program\">Section 6.1.5<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Network Comment<\/p>\n<\/td>\n<td>\n<p>Display or hide network comment<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_6-2-5_Editing_comment\">Section 6.2.5<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Element Comment<\/p>\n<\/td>\n<td>\n<p>Display or hide element comment<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_8-3_Element_Comment\">Section 8.3<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Register Value<\/p>\n<\/td>\n<td>\n<p>Display or hide Register data<\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td>\n<p>Longer Text<\/p>\n<\/td>\n<td>\n<p>Display longer text to avoid excessive truncation<\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td>\n<p>Elided Long Text Middle<\/p>\n<\/td>\n<td>\n<p>Truncating or abbreviating excessively long text.<\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td>\n<p>Font<\/p>\n<\/td>\n<td>\n<p>Font size<\/p>\n<\/td>\n<td>\n<p>Set font size for Ladder Diagram<\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td rowspan=\"4\">\n<p>Window<\/p>\n<\/td>\n<td>\n<p>Cascade<\/p>\n<\/td>\n<td>\n<p>Display window overlapping<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_6-2-1_Display_elements\">Section 6.2.1<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Tile Horizontal<\/p>\n<\/td>\n<td>\n<p>Display entire window array<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_6-2-1_Display_elements\">Section 6.2.1<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Switch Window<\/p>\n<\/td>\n<td>\n<p>Quick switch to corresponding window<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_6-2-1_Display_elements\">Section 6.2.1<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Close All<\/p>\n<\/td>\n<td>\n<p>Close all windows<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_6-2-1_Display_elements\">Section 6.2.1<\/a><\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>Table 8: Setting inspection tag page <\/p>\n<h4>3-4-5 Tools<\/h4>\n<p>This tag page is mainly used for editing the Ladder Diagram related design.<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m04-en-03\/mplc-m04-en-03-016.png\" \/><\/p>\n<p>Fig. 16: Tool tag page<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>Type<\/p>\n<\/td>\n<td>\n<p>Function<\/p>\n<\/td>\n<td>\n<p>Description<\/p>\n<\/td>\n<td>\n<p>Detailed introduction<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"4\">\n<p>Tools<\/p>\n<\/td>\n<td>\n<p>System Backup<\/p>\n<\/td>\n<td>\n<p>Set up and save system project related backup <\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_14-1-1_System_Backup\">Section 14.1.1<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>System Restore<\/p>\n<\/td>\n<td>\n<p>Read originally saved system backup data<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_14-1-2_System_Backup\">Section 14.1.2<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Memory Card Operations<\/p>\n<\/td>\n<td>\n<p>Execute memory cartridge related operation<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_14-2_Memory_Card\">Section 14.2<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>CRC16 Generator<\/p>\n<\/td>\n<td>\n<p>System will calculate and produce the checking value automatically<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_14-3_CRC16_Calculator\">Section 14.3<\/a><\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>Table 9: Setting tool tag page <\/p>\n<h3>3-5 Project Window<\/h3>\n<h4>3-5-1 Project Management<\/h4>\n<p>Such function allows the user to organize regularly used functions into a tree diagram and then display it in the left-hand side Project Management window. By clicking the respective function setting tag under the Project Management, it also allows the user to open the required window in quicker way. For example, click the \u201cIO Configuration\u201d and the relevant setting window will pop up.  <\/p>\n<p><img decoding=\"async\" alt=\"D:\\patrick\\\u66f4\u63db\u624b\u518a\u5716\u7247\\\u5716_en\\17.PNG\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m04-en-03\/mplc-m04-en-03-017.png\" \/><\/p>\n<p>Fig. 17: Project management window<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p><strong>Type<\/strong><\/p>\n<\/td>\n<td>\n<p>Description<\/p>\n<\/td>\n<td>\n<p>Detailed introduction<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>System Configuration<\/p>\n<\/td>\n<td>\n<p>Check Register related setting <\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#ch5\">Section 5<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Program Unit<\/p>\n<\/td>\n<td>\n<p>Check Main Program and sub-program<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_6-2_Ladder_Diagram\">Section 6.2<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Comment <\/p>\n<\/td>\n<td>\n<p>Manage the comment deployed in the Ladder Diagram<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_Comment_information\">Section 8<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Status Page<\/p>\n<\/td>\n<td>\n<p>Monitor current status of Register<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#ch12_3\">Section 12.2<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Data Chart<\/p>\n<\/td>\n<td>\n<p>Monitor the trend graph of individual register changes<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_12-2-3_Data_Chart\">Section 12.2.3<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Motion Control<\/p>\n<\/td>\n<td>\n<p>Set the motion control related parameters. <\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_Motion_control\">Section 9<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Data Table<\/p>\n<\/td>\n<td>\n<p>Set up various tables<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_Creating_Tables\">Section 7<\/a><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Element Memory<\/p>\n<\/td>\n<td>\n<p>Set and edit the element memory<\/p>\n<\/td>\n<td>\n<p>Please refer to <a href=\"#_Element_Memory\">Section 12.3<\/a><\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>Table 10: Setting project management window<\/p>\n<h4>3-5-2 Tool Box<\/h4>\n<p>For easier operation by users, normal commands are categorized for organizing in the toolkit. By clicking [View]\u2192 [Tool Box] in the function toolbar, the user will be allowed to open the Tool Box command window.<\/p>\n<p><img decoding=\"async\" alt=\"D:\\patrick\\\u66f4\u63db\u624b\u518a\u5716\u7247\\\u5716_en\\18.PNG\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m04-en-03\/mplc-m04-en-03-018.png\" \/><\/p>\n<p>Fig. 18: Tool Box window<\/p>\n<p>For the introduction of the functions in the tool box, please refer to the Instruction User Manual.<\/p>\n<h4>3-5-3 Module List<\/h4>\n<p>Click [View]\u2192 [Module List] in the function toolbar, the following module management webpage appears, as shown in the figure below:<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m04-en-03\/mplc-m04-en-03-019.jpg\" \/><\/p>\n<p>Fig. 19: Module List<\/p>\n<p>Please refer to <a href=\"#ch10_2\">Section 10-2<\/a> for detailed description.<\/p>\n<h4>3-5-4 Memory Address<\/h4>\n<p>When there are too many components used in the project, it is impossible for the user to fully remember which components or functions use which resources, but through this function, the user can clearly see which registers are used and the corresponding registers; therefore, users can plan the resources in the project more efficiently.<\/p>\n<p>As shown in the figure below, red represents the used registers, and green represents the unused registers. Double-click the list item with the left mouse button to open the corresponding function window.<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m04-en-03\/mplc-m04-en-03-020.png\" \/><\/p>\n<p>Fig. 20: Memory Address<\/p>\n<h4>3-5-5 Cross Reference<\/h4>\n<p>Through this function, users can quickly query the location, characteristics, functions and other information of registers or tags, and use the filtering function to further search for registers or tags with specific conditions. Double-click the list item with the left mouse button to open the corresponding function window.<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m04-en-03\/mplc-m04-en-03-021.png\" \/><\/p>\n<p>Fig. 21: Cross Reference<\/p>\n<h3>3-6 Webpage Configuration Management<\/h3>\n<p>In addition to displaying the window list currently opened, the user may also open the designated window or execute the arraying. When opening several windows, the user may arrange the display windows according to personal operating habitude. <\/p>\n<p><img decoding=\"async\" alt=\"D:\\patrick\\\u66f4\u63db\u624b\u518a\u5716\u7247\\\u5716_en\\19.PNG\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m04-en-03\/mplc-m04-en-03-022.png\" \/><\/p>\n<p>Fig. 22: Webpage management<\/p>\n<p>For example, the user may drag the window of the opened monitoring page to the desired position, release the mouse and then the user will be allowed to change the window arraying pattern. <\/p>\n<p><img decoding=\"async\" alt=\"D:\\patrick\\\u66f4\u63db\u624b\u518a\u5716\u7247\\\u5716_en\\20.PNG\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m04-en-03\/mplc-m04-en-03-023.png\" \/><\/p>\n<p>Fig. 23: Changing window arraying pattern<\/p>\n<h3>3-7\tQuick key<\/h3>\n<p>Click [Project] \u2192[Project] \u2192 [Quick Key] to view the shortcut keys provided, and also allow users to define familiar quick keys.<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/mplc-m04-en-03\/mplc-m04-en-03-024.png\" \/><\/p>\n<p>Fig. 24: Quick Key<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p><strong>Type<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>Function<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>Quick key<\/strong><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>Project<\/p>\n<\/td>\n<td>\n<p>Function Manual<\/p>\n<\/td>\n<td>\n<p>\u201cF1\u201d<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Special Manual<\/p>\n<\/td>\n<td>\n<p>\u201cF2\u201d<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"4\">\n<p>File<\/p>\n<\/td>\n<td>\n<p>New<\/p>\n<\/td>\n<td>\n<p>Ctrl+N<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Open<\/p>\n<\/td>\n<td>\n<p>Ctrl+O<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Save<\/p>\n<\/td>\n<td>\n<p>Ctrl+S<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Print<\/p>\n<\/td>\n<td>\n<p>Ctrl+P<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"3\">\n<p>Design<\/p>\n<\/td>\n<td>\n<p>Find<\/p>\n<\/td>\n<td>\n<p>Ctrl+F<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Replace<\/p>\n<\/td>\n<td>\n<p>Ctrl+R<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Goto<\/p>\n<\/td>\n<td>\n<p>Ctrl+G<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>Ladder<\/strong><\/p>\n<\/td>\n<td><\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td><\/td>\n<td><\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td><\/td>\n<td><\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td><\/td>\n<td><\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td><\/td>\n<td><\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td><\/td>\n<td><\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td><\/td>\n<td><\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td><\/td>\n<td><\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td><\/td>\n<td><\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td><\/td>\n<td><\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td><\/td>\n<td><\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td><\/td>\n<td><\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td rowspan=\"9\">\n<p>PLC<\/p>\n<\/td>\n<td>\n<p>Run<\/p>\n<\/td>\n<td>\n<p>F9<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Stop<\/p>\n<\/td>\n<td>\n<p>Ctrl+F9<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Trial Run<\/p>\n<\/td>\n<td>\n<p>F10<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Discard Change<\/p>\n<\/td>\n<td>\n<p>Shift+F10<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Upload<\/p>\n<\/td>\n<td>\n<p>F11<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Download<\/p>\n<\/td>\n<td>\n<p>Ctrl+F11<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Offline Editing<\/p>\n<\/td>\n<td>\n<p>Ctrl+F12<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Online Monitoring<\/p>\n<\/td>\n<td>\n<p>F12<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Online Editing<\/p>\n<\/td>\n<td>\n<p>Shift+F12<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"4\">\n<p>Other<\/p>\n<\/td>\n<td>\n<p>Syntax Check<\/p>\n<\/td>\n<td>\n<p>F8<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Register Content<\/p>\n<\/td>\n<td>\n<p>F7<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Options<\/p>\n<\/td>\n<td>\n<p>Ctrl+F8<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Ribbon Collapse<\/p>\n<\/td>\n<td>\n<p>Ctrl+F1<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>\tTable 11: Quick key list<\/p>\n","protected":false},"excerpt":{"rendered":"<p>\u26a0Danger When installing or removing the M-series CPU mo [&hellip;]<\/p>\n","protected":false},"author":1,"featured_media":0,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[48],"tags":[],"class_list":["post-3228","post","type-post","status-publish","format-standard","hentry","category-en-mplc-m04"],"_links":{"self":[{"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/posts\/3228","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/comments?post=3228"}],"version-history":[{"count":0,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/posts\/3228\/revisions"}],"wp:attachment":[{"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/media?parent=3228"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/categories?post=3228"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/tags?post=3228"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}