{"id":3349,"date":"2026-11-17T18:42:39","date_gmt":"2026-11-17T10:42:39","guid":{"rendered":"https:\/\/resource.fatek.com\/index.php\/2026\/11\/17\/p5hmi-fvd-en-07\/"},"modified":"2026-11-17T18:42:39","modified_gmt":"2026-11-17T10:42:39","slug":"p5hmi-fvd-en-07","status":"publish","type":"post","link":"https:\/\/resource.fatek.com\/index.php\/2026\/11\/17\/p5hmi-fvd-en-07\/","title":{"rendered":"Chapter 7 Data Log"},"content":{"rendered":"<p>Objects such as\u3010Lamp\u3011or\u3010Numeric Input\/Display\u3011can be used to read the real-time changes of certain register values when the HMI is operating. However, in order to track changes of the value over time, the\u3010Data Log\u3011function must be used. The\u3010Data Log\u3011 function is used to log the values of an address according to a set interval or when certain conditions are met to provide users with the long-term trends of values in addresses.<\/p>\n<p>This chapter will explain Data Log functions, the settings, and how to export the data for the user to view and analyze.<\/p>\n<h3>7.1 Data Log List<\/h3>\n<p>Click on\u3010Data Log\u3011in the\u3010Project Explorer\u3011of FvDesigner, and the\u3010Data Log List\u3011 will pop up; the current\u3010Data Log Groups\u3011that were already set will be displayed on the list according to the order of the\u3010Group ID\u3011.<\/p>\n<p><img decoding=\"async\" alt=\"C:\\Users\\chien yu\\Desktop\\\u9621\u55bb\\FvDesigner\u548cPLC\u4f7f\u7528\u624b\u518a\\Fv manual\\164.JPG\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/p5hmi-fvd-en-07\/p5hmi-fvd-en-07-001.jpg\" \/><\/p>\n<p>Figure 122\u3010Data Log List\u3011Screen<\/p>\n<p>To add a new Data Log Group, click on the\u3010Add\u3011button to the right and the\u3010Data Log Group\u3011setting dialog will appear for the user to operate.<\/p>\n<p>To edit an existing \u3010Data Log Group\u3011, double-click on the\u3010Data Log Group\u3011entry or first select the\u3010Data Log Group\u3011entry and then click on the\u3010Edit\u3011button to the right. The properties setting dialog of the\u3010Data Log Group\u3011entry will appear for the user to modify.<\/p>\n<p>To delete an existing \u3010Data Log Group\u3011, select the\u3010Data Log Group\u3011entry and then click on the\u3010Delete\u3011button to the right to delete this\u3010Data Log Group\u3011entry.<\/p>\n<h3>7.2 Data Log Group Settings<\/h3>\n<p>Settings for the\u3010Data Log Group\u3011are divided into four parts:\u3010Setting\u3011,\u3010Logging Address List\u3011,\u3010Export Data\u3011and\u3010Print Data\u3011.\u3010Setting\u3011is used to set the behavior for the\u3010Data Log Group\u3011to log the data, the\u3010Data Address List\u3011is used to edit the address list logged by the\u3010Data Log Group\u3011, and the\u3010Export Data\u3011is used to set the export behavior of the logged data,\u3010Print Data\u3011is used to set the format to print out the data log.<\/p>\n<h4>7.2.1 \u3010Setting\u3011<\/h4>\n<p>The\u3010Setting\u3011screen is as shown in the figure below. The meaning of each setting are also listed below:<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/p5hmi-fvd-en-07\/p5hmi-fvd-en-07-002.png\" \/><\/p>\n<p>Figure 123\u3010Setting\u3011of\u3010Data Log Group\u3011<\/p>\n<p>Table 51\u3010Setting\u3011Properties of\u3010Data Log Group\u3011<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p><strong>Property<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>Description<\/strong><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Group ID\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>Set the Group ID of the\u3010Data Log Group\u3011.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Comment\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>Set a comment for the\u3010Data Log Group\u3011.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Import\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>A CSV , xlsx or xls file can be selected after clicking on this button. All the logged addresses included in the file will be applied to the\u3010Data Log Group\u3011settings.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Export\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>The settings of the current\u3010Data Log Group\u3011can be saved into a CSV , xlsx or xls file after clicking on this button.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Data\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>Set the data content logged by the\u3010Data Log Group\u3011.<\/p>\n<p>\u3010Occurrence\u3011<\/p>\n<p>Set the number of times to collect data<\/p>\n<p>\u3010Backup Memory\u3011<\/p>\n<p>Set to enable Backup Memory.<\/p>\n<p>Select to save the Data Log of the HMI into the backup memory of the HMI when the power of the HMI is interrupted in order to avoid loss of data.<\/p>\n<p>\u3010Occurrence\u3011<\/p>\n<p>Set the number of times\u3010Data Log Group\u3011 logs data.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Control\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>Set the conditions for the\u3010Data Log Group\u3011to log data.<\/p>\n<p>\u3010Execution Condition\u3011<\/p>\n<p>Sets the condition to execute data logging.<\/p>\n<p>\u3010Time-based\u3011<\/p>\n<p>The\u3010Data Log Group\u3011will log data according to a set interval.<\/p>\n<p>\u3010Triggered by Bit\u3011 <\/p>\n<p>The address logging will be executed when the status changes of the \u3010Logging Control Bit\u3011satisfy the conditions set in\u3010Trigger Condition\u3011. <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>Execution Condition:\u3010Time-based\u3011<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>\u3010Start when Project Runs\u3011<\/p>\n<p>Set to start logging data when the project runs.<\/p>\n<p>\u3010Start Time\u3011<\/p>\n<p>When the\u3010Start when Project Runs\u3011is not selected then the start time for the\u3010Data Log Group\u3011can be set.The three time units that can be entered are hour, minute, and second.<\/p>\n<p>\u3010Time Interval\u3011<\/p>\n<p>Set the time interval for the data log function.<\/p>\n<p>The time interval will be a fixed value if\u3010Constant\u3011is selected. The time interval will be determined by the value in the address set if\u3010Address\u3011is selected; the data type of the address data read is fixed as\u301032Bit-UINT\u3011.<\/p>\n<p>\u3010Time Interval Unit\u3011<\/p>\n<p>Set the unit of the\u3010Time Interval\u3011.<\/p>\n<p>The maximum value of the time interval is 1 day. The maximum value that can be entered for the\u3010Time Interval\u3011is 24 if the\u3010Time Interval Unit\u3011is set as\u3010Hour\u3011. The maximum value that can be entered is 1440 if it is set as\u3010Minute\u3011. The maximum value that can be entered is 86400 if the Time Interval Unit\u3011is set as\u3010Second\u3011. If the\u3010Time Interval Unit\u3011is set as\u3010100ms\u3011, the maximum value that can be entered for the\u3010Time Interval\u3011is fixed as 9.<\/p>\n<p>\u3010Logging Control Bit\u3011<\/p>\n<p>Set an address to control whether to execute\u3010Data Log Group\u3011, the function will be executed when the address is ON.<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>Execution Condition:\u3010Trigger by Bit\u3011<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>\u3010Logging Control Bit\u3011<\/p>\n<p>Set an address to control whether to execute\u3010Data Log Group\u3011.<\/p>\n<p>\u3010Trigger Condition\u3011<\/p>\n<p>There are three options:\u3010Bit OFF -&gt; ON\u3011,\u3010Bit ON -&gt; OFF\u3011, and\u3010Bit Change\u3011.<\/p>\n<p>\u3010Reset Logging Control Bit\u3011<\/p>\n<p>When the\u3010Trigger Condition\u3011is\u3010Bit OFF -&gt; ON\u3011or\u3010Bit ON -&gt; OFF\u3011, the bit will be automatically reset.<\/p>\n<p>Note: If the communication error of the data log group happened then the triggered bit cannot reset automatically.<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Action\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>\u3010When Buffer is Full\u3011<\/p>\n<p>Set the action to take when the\u3010Data Log Group\u3011has completed the number of data loggings set in\u3010Occurrence\u3011. If\u3010Stop Data Logging\u3011is selected, data logging will be stopped; if\u3010Overwrite\u3011is selected, then the\u3010Data Log Group\u3011will continue to log data and the data previously saved will be overwritten as new data is logged.<\/p>\n<p>\u3010Trigger a Bit\u3011<\/p>\n<p>Set to trigger a specific bit when the data is full; the triggering address and the time to trigger the address can be set on the right if this is enabled.<\/p>\n<p>\u3010Enable Buffer Clear Bit\u3011<\/p>\n<p>Set to enable a buffer clear bit; the\u3010Buffer Clear Bit\u3011can be set at the right if this is enabled. When the status of this address is 1, the data saved in the buffer will be cleared.<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<h4>7.2.2 \u3010Logging Address List\u3011<\/h4>\n<p>The\u3010Logging Address List\u3011screen is as shown in the figure below, the meaning of each setting are listed below:<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/p5hmi-fvd-en-07\/p5hmi-fvd-en-07-003.png\" \/><\/p>\n<p>Figure 124\u3010Logging Address List\u3011Setting Screen of\u3010Data Log Group\u3011<\/p>\n<p>Table 52\u3010Logging Address List\u3011Setting Properties of\u3010Data Log Group\u3011<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p><strong>Property<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>Description<\/strong><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Address\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>You can choose whether to automatically\u3010continuous\u3011address when creating the address, or\u3010random\u3011to be filled in by the user.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Number of Addresses\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>Set how many addresses to collect.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Total Bits\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>Display the total bits of the data logged.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Total Words\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>Display the total words of the data logged.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Logging Address List\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>\u3010Data Type\u3011<\/p>\n<p>Set the data type of the data logged. Only the first row can be modified if the logged address type is set as\u3010Sequential\u3011.<\/p>\n<p>\u3010Address\u3011<\/p>\n<p>Set the address of the data logged. Only the first row can be modified if the logged address type is set as\u3010Sequential\u3011.<\/p>\n<p>\u3010Name\u3011<\/p>\n<p>Set the address name of the data logged; the default name is the address is itself if no name is entered.<\/p>\n<p>\u3010Bits\/Words\u3011<\/p>\n<p>Display the length of the data logged by\u3010Data Type\u3011.\u3010Words\u3011can be modified if\u3010Data Type\u3011is set as\u3010Ascii String\u3011.<\/p>\n<p>\u3010Gain\u3011<\/p>\n<p>The amount of\u3010Gain\u3011can be set.<\/p>\n<p>Formula is as follows: y=Ax+B, gain is A, offset for the B, y value is displayed for HMI, x is PLC value.<\/p>\n<p>\u3010Offset\u3011<\/p>\n<p>Set the\u3010Offset\u3011value. See\u3010Gain\u3011for more details.<\/p>\n<p>\u3010Precision\u3011<\/p>\n<p>Set the amount of decimal places shown.<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<h4>7.2.3 \u3010Export Data\u3011<\/h4>\n<p>The\u3010Export Data\u3011screen is as shown in the figure below, the meaning of each setting are listed below:<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/p5hmi-fvd-en-07\/p5hmi-fvd-en-07-004.png\" \/><\/p>\n<p>Figure 125\u3010Export Data\u3011Setting Screen of\u3010Data Log Group\u3011<\/p>\n<p>Table 53\u3010Export Data\u3011Setting Properties of\u3010Data Log Group\u3011<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p><strong>Property<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>Description<\/strong><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Export Data\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>Set to enable to export data function; export settings will appear below if this function is enabled.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Format\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>Set the format of the output file; TXT, CSV, FBF, and PDF can be selected, FBF file is FATEK\u2019s proprietary format, which requires the format of reading or converting files using\u3010FBF Reader\u3011in FvDesigner\u3010Tools\u3011.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Destination\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>Set the destination of the output file; available selections include internal, microSD card or USB storage device.<\/p>\n<p>If the output destination is internal storage, you can use FTP to connect to the HMI to read the stored file.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Export Mode\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>Set the timing of exporting files. There are four operation modes when the drop-down menu is clicked.<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p><strong>Mode<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>Description<\/strong><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>\u3010When Buffer is Full\u3011<\/p>\n<\/td>\n<td>\n<p>When the\u3010Occurrence\u3011reaches the set times, it will be automatically exported.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>\u3010When Bit is Triggered\u3011<\/p>\n<\/td>\n<td>\n<p>When the set bit is triggered, the data will be exported<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>\u3010Export Daily Time\u3011<\/p>\n<\/td>\n<td>\n<p>Automatically export when HMI time reaches the set time<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>\u3010Export Regularly\u3011<\/p>\n<\/td>\n<td>\n<p>Export data according to the set time interval<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Enable Continue File Mode\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>Support for PC model with FBF export data format, Historic Trend and Historic Data Table will load the old files automatically if this option is checked. But at the same time, \u3010Enable Address Mode\u3011and the Sub switch save in the \u3010Historic Data Table\u3011will be disabled to avoid time repeat.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Enable Address Mode\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>After enabling, the exported file name, destination, suffix, export mode, data mode, date and time filtering, etc., will be controlled by the specific address. To be allowed to enable this mode, you need to first enable\u3010Export Mode\u3011and\u3010When Bit is Triggered\u3011. When\u3010Export Mode\u3011is\u3010When Buffer is Full\u3011, the export method cannot be set.<\/p>\n<p>\u3010Setting\u3011<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/p5hmi-fvd-en-07\/p5hmi-fvd-en-07-005.png\" \/><\/p>\n<p>\u3010File Name\u3011<\/p>\n<p>Use a defined address to set the name of the exported file. 5 characters is the default setting, maximum setting is 100 characters.<\/p>\n<p>\u3010Destination\u3011<\/p>\n<p>Use a defined address to set the destination of the output file. The destination values are shown in the following table,<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>Register Value<\/p>\n<\/td>\n<td>\n<p>Function<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>1<\/p>\n<\/td>\n<td>\n<p>HMI<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>2<\/p>\n<\/td>\n<td>\n<p>microSD Card<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>3<\/p>\n<\/td>\n<td>\n<p>USB Storage Device<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Other Values<\/p>\n<\/td>\n<td>\n<p>HMI<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>\u3010Suffix\u3011<\/p>\n<p>Use a defined address to set the name of the exported file and the date\/time format. The suffix values are shown in the following table,<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>Register Value<\/p>\n<\/td>\n<td>\n<p>Function<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>1<\/p>\n<\/td>\n<td>\n<p>yymmdd<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>2<\/p>\n<\/td>\n<td>\n<p>yymmdd_hh<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>3<\/p>\n<\/td>\n<td>\n<p>yymmdd_hhmm<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>4<\/p>\n<\/td>\n<td>\n<p>yymmdd_hhmmss<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>5<\/p>\n<\/td>\n<td>\n<p>None<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>6<\/p>\n<\/td>\n<td>\n<p>yymm<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Other Values<\/p>\n<\/td>\n<td>\n<p>yymmdd_hhmmss<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>\u3010Export Mode\u3011<\/p>\n<p>Use a defined address to set the export mode. The export mode values are shown in the following table, <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>Register Value<\/p>\n<\/td>\n<td>\n<p>Function<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>1<\/p>\n<\/td>\n<td>\n<p>Overwrite Old Files<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>2<\/p>\n<\/td>\n<td>\n<p>Continue to write on old file<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Other Value<\/p>\n<\/td>\n<td>\n<p>Continue to write on old file<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>\u3010Data Mode\u3011<\/p>\n<p>Use a defined address to set the data mode of the exported data. The data mode values are shown in the following table,<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>Register Value<\/p>\n<\/td>\n<td>\n<p>Function<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>1<\/p>\n<\/td>\n<td>\n<p>Save all unsaved data and mark the exported data as saved.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>2<\/p>\n<\/td>\n<td>\n<p>Save all data and mark the exported data as saved<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>3<\/p>\n<\/td>\n<td>\n<p>Saved all data for a specific time without marking the exported data as saved.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Other Values<\/p>\n<\/td>\n<td>\n<p>Save all data and mark the exported data as saved<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>\u3010Data\/Time Filter\u3011<\/p>\n<p>\u3010Start Date (Year\/Month\/Day)\u3011<\/p>\n<p>Use a defined address to set the date at which filtering starts.<\/p>\n<p>\u3010Start Time (Hour\/Minute\/Second)\u3011<\/p>\n<p>Use a defined address to set the time to start filtering.<\/p>\n<p>\u3010End Date (Year\/Month\/Day)\u3011<\/p>\n<p>Use a defined address to set the date at which filtering ends.<\/p>\n<p>\u3010End Time (Hour\/Minute\/Second)\u3011<\/p>\n<p>Use a defined address to set the time at which filtering ends.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010File Name\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>Set the name of the exported file; the file name of the exported file includes the save date and time (such as: DataLog_140519_151735.txt).<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Suffix\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>Set the name of the exported file, such as yymmdd_hh,  the name of exported file only has a date and hours<\/p>\n<p>(Example: DataLog_140519_17.txt)<\/p>\n<p>This setting also provides regular export archive mode,<\/p>\n<p>If the suffix selected is &quot;yymm&quot;, it would produce one file per month,<\/p>\n<p>If the suffix selected is &quot;yymmdd&quot;, it would produce one file per day,<\/p>\n<p>If the suffix select &quot;yymmdd_hh&quot;, it would produce one file per hour,<\/p>\n<p>If the suffix selected is &quot; yymmdd_hhmm&quot;, it would produce one file per minute,<\/p>\n<p>If the suffix selected is &quot; yymmdd_hhmmss&quot;, it would produce one file per second,<\/p>\n<p>If the suffix to select &quot;no&quot;, one file includes all data.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Create a folder with the name from comment\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>If this option is checked, the name of the folder will be name from\u3010Setting\u3011\u3010Comment\u3011, for example, comment temperature, the original Group_1 folder will be changed to the temperature folder, which is originally datalog \\ Group_1 will become datalog \\ temperature.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Save to the default folder\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>There is None, Folder created monthly and Folder created daily 3 opitons. If choose none then will not create another folder,for example, datalog\\Group_1\\DataLog_170403. csv. If choose folder created monthly then will create another monthly folder each month, for example, datalog\\Group_1\\201704\\DataLog_170403.csv.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Send Mail\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>It can be seen after\u3010SMTP\u3011is enabled. The purpose of this function is to send emails when exporting. The details are as follows:<\/p>\n<p>When this group has exported data, an email will be sent to the set group according to the settings here.<\/p>\n<p>At the same time, you can check to include &quot;Datalog File (the file exported this time)&quot; and send it together.<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/p5hmi-fvd-en-07\/p5hmi-fvd-en-07-006.png\" \/><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Export Data Without Headers\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>After checking, the title will not be exported when exporting data.<\/p>\n<p>(*Note: If you want to write a file with an existing title, the title of the file will still exist, please delete the old file before using this function)<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/p5hmi-fvd-en-07\/p5hmi-fvd-en-07-007.jpg\" \/><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010PDF Setting\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>When the export format is set to PDF, clicking settings allows you to adjust the PDF document style.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Date\/Time Format\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>\u3010Date\u3011<\/p>\n<p>Set the display format of the date when exporting files.<\/p>\n<p>\u3010Time\u3011<\/p>\n<p>Set the display format of the time when exporting files.<\/p>\n<p>\u3010Combine Date and Time\u3011<\/p>\n<p>If set, the date and time columns will be combined into a single column.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Automatically Delete\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>Check to set the number of days the exported file should be retained in memory. For example, if set to seven days, the HMI will use its internal calendar and files greater than seven days will be removed.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Manually Delete (all files)\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>It will delete all files when the bit turns to ON.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Upload to Remote\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>Enable ch4.5-\u3010FTP Client\u3011function then this option can be seen.<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/p5hmi-fvd-en-07\/p5hmi-fvd-en-07-008.png\" \/><\/p>\n<p>\u3010Trigger Address\u3011<\/p>\n<p>Set a bit to trigger uploading.<\/p>\n<p>\u3010Select Server\u3011<\/p>\n<p>Click the drop-down menu to select the server to upload<\/p>\n<p>\u3010Upload Folder\u3011<\/p>\n<p>Fill in the path where the remote server is stored, if not filled in, it will be stored in the root directory of the server<\/p>\n<p>\u3010Upload mode\u3011<\/p>\n<p>There are 7 upload modes for\u3010Static\u3011, which will be described together with\u3010Dynamic\u3011below<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>Setting Value(INT)<\/p>\n<\/td>\n<td>\n<p>Description<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>-10<\/p>\n<\/td>\n<td>\n<p>Upload the oldest 10 files in directory<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>-5<\/p>\n<\/td>\n<td>\n<p>Upload the oldest 5 files in directory<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>-1<\/p>\n<\/td>\n<td>\n<p>Upload the oldest file in directory<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>0<\/p>\n<\/td>\n<td>\n<p>Upload all files in directory<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>1<\/p>\n<\/td>\n<td>\n<p>Upload the lastest file in directory<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>5<\/p>\n<\/td>\n<td>\n<p>Upload the lastest 5 files in directory<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>10<\/p>\n<\/td>\n<td>\n<p>Upload the lastest 10 files in directory<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>\u3010Send Result\u3011<\/p>\n<p>Set the address of the execution result display, the data type is\u3010INT\u3011,<\/p>\n<p>Success: 1 \/ Failure: -1<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Status Address\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>Set the saving address of the error code.<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>Error Code<\/p>\n<\/td>\n<td>\n<p>Description<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>0<\/p>\n<\/td>\n<td>\n<p>No Error<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>1<\/p>\n<\/td>\n<td>\n<p>Read Error<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>2<\/p>\n<\/td>\n<td>\n<p>Write Error<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>5<\/p>\n<\/td>\n<td>\n<p>Open Error<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>100<\/p>\n<\/td>\n<td>\n<p>Not enough storage space<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>The following example exports specified time data:<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/p5hmi-fvd-en-07\/p5hmi-fvd-en-07-009.jpg\" \/><\/p>\n<p>Figure 126 export specified time data example<\/p>\n<p>Base on checking\u3010Enable Address Mode\u3011and\u3010Data Mode\u3011, set data 3 to\u3010Data Mode\u3011. Fill in fill in the required time range into the register that set in\u3010Date\/Time Filter\u3011, datas between the range can be obtained.<\/p>\n<h4>7.2.4 \u3010Print Data\u3011<\/h4>\n<p>\u3010Print Data\u3011page as shown below, the meaning of each setting is as follows :<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/p5hmi-fvd-en-07\/p5hmi-fvd-en-07-010.png\" \/><\/p>\n<p>Figure 127\u3010Print Data\u3011Setting Screen of\u3010Data Log Group\u3011<\/p>\n<p>Table 54\u3010Print Data\u3011Setting Properties of\u3010Data Log Group\u3011<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>Properties<\/p>\n<\/td>\n<td>\n<p>Description<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>\u3010Print Data\u3011<\/p>\n<\/td>\n<td>\n<p>Set whether to enable Print Data function, enable the function do the following settings.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>\u3010Control\u3011<\/p>\n<\/td>\n<td>\n<p>\u3010Trigger Bit\u3011<\/p>\n<p>Set the trigger bit of print control.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>\u3010Format\u3011<\/p>\n<\/td>\n<td>\n<p>\u3010Date\u3011<\/p>\n<p>Set the date print format.<\/p>\n<p>\u3010Time\u3011<\/p>\n<p>Set time print format.<\/p>\n<p>\u3010Header\u3011<\/p>\n<p>If checked, according to the setting, it will print header first then print the data log content. Press \u2018\u2019setting\u2019\u2019 button to set the header. <\/p>\n<p>\u3010Setting (Header)\u3011<\/p>\n<p>Header setting, please refer to <strong>7.2.4.1-\u3010Print Data\u3011Header and Footer\u3010Setting\u3011<\/strong>for more details. <\/p>\n<p>\u3010Footer\u3011<\/p>\n<p>If checked, according to the setting, it will print data log content first then print the footer. Press \u2018\u2019setting\u2019\u2019 button to set the footer. <\/p>\n<p>\u3010Setting (Footer)\u3011<\/p>\n<p>Footer setting, please refer to <strong>7.2.4.1-\u3010Print Data\u3011Header and Footer\u3010Setting\u3011<\/strong>for more details.\u3002<\/p>\n<p>\u3010Title\u3011<\/p>\n<p>Print the data log title.<\/p>\n<p>\u3010Horizontal Grid Line\u3011<\/p>\n<p>Print out with horizontal grid line.<\/p>\n<p>\u3010Vertical Grid Line\u3011<\/p>\n<p>Print out with vertical grid line.<\/p>\n<p>\u3010Transpose\u3011<\/p>\n<p>Data will be printed from left to right.<\/p>\n<p>\u3010Preview\u3011<\/p>\n<p>Press the preview to view the following table settings, whether it meets the printing requirements, press \u2018\u2019preview\u2019\u2019 following figure will appear<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/p5hmi-fvd-en-07\/p5hmi-fvd-en-07-011.png\" \/><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>\u3010Print Items\u3011<\/p>\n<\/td>\n<td>\n<p>Print items includes: Index, Date, Time and Data.<\/p>\n<p>\u3010Copy the Selected Item Settings to Others\u3011<\/p>\n<p>When a certain row is selected, this button will be enabled. The user can use this button to copy the setting value of the selected item to other items, which simplifies the user&#8217;s setting procedure and improves the set efficiency.<\/p>\n<p>\u3010Print\u3011<\/p>\n<p>If checked, the printed data will include this item.<\/p>\n<p>\u3010Min Text Width\u3011<\/p>\n<p>The minimum expected text width of the print items, when the text width of the content is smaller than the minimum word width, will be automatically filled with spaces to keep the minimum word width setting. The letter width of the letter or number is 1 and the Chinese is 2 . <\/p>\n<p>\u3010Left Gap\u3011<\/p>\n<p>Space on the left of the print item<\/p>\n<p>\u3010Right Gap\u3011<\/p>\n<p>Space on the right of the print item <\/p>\n<p>\u3010Lead Zero\u3011<\/p>\n<p>For Data Log\u2019s items that are not \u2018\u2019text\u2019\u2019 type, when the width of the printed content is less than the minimum width, it will automatically filled with \u2018\u20190\u2019\u2019.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>\u3010Calculation\u3011<\/p>\n<\/td>\n<td>\n<p>After the actual data that collected, will calculate for data log items that are not &quot;text&quot; types, and the calculation results will be printed in sequence.<\/p>\n<p>\u3010Number\u3011<\/p>\n<p>Set the number of calculations.<\/p>\n<p>The following is the setting description of the calculation item:<\/p>\n<p>\u3010Type\u3011<\/p>\n<p>Set the type of calculation, includes Total, Average, Maximum and Minimum.<\/p>\n<p>\u3010Name\u3011<\/p>\n<p>Calculate the customized name of the project, which will be printed with the calculation results.<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<h5>7.2.4.1 \u3010Print Data\u3011Header and Footer\u3010Setting\u3011<\/h5>\n<p>For the header\/footer, when click the\u3010Setting\u3011button, the following dialog box appears. There are two modes:\u3010Static\u3011and\u3010Dynamic\u3011.<\/p>\n<p>\u3010Static\u3011<\/p>\n<p>Users can edit any text content as static header\/footer content.<\/p>\n<p>\u3010Dynamic\u3011<\/p>\n<p>The user sets the variables and edits the pattern, and matches the keyword &quot;%[number]&quot; (eg: %1, %2, %3, etc.) to achieve the dynamic header\/footer requirements, where the keyword will be replaced by the actual content of the variable. <\/p>\n<p>\u3010Dtat Log\u3011\u3010Print Data\u3011\u3010Header\/Footer\u3011as shown in the figure below, the meaning of each setting option is as follows:<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/p5hmi-fvd-en-07\/p5hmi-fvd-en-07-012.png\" \/><\/p>\n<p>Figure 128\u3010Print Data\u3011\u3010Header\/Footer\u3011Setting Screen of\u3010Data Log Group\u3011(Static mode)<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/p5hmi-fvd-en-07\/p5hmi-fvd-en-07-013.png\" \/><\/p>\n<p>Figure 129\u3010Print Data\u3011\u3010Header\/Footer\u3011Setting Screen of\u3010Data Log Group\u3011(Dynamic mode)<\/p>\n<p>Table 55\u3010Export Data\u3011Setting Properties of\u3010Data Log Group\u3011<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>Options<\/p>\n<\/td>\n<td>\n<p>Description<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>\u3010Variable Address\u3011<\/p>\n<\/td>\n<td>\n<p>\u3010Refresh Mode\u3011<\/p>\n<p>The refresh mode for setting variable content can be divided into:<\/p>\n<ul>\n<li>\u3010Refresh Periodically\u3011: refresh variable content periodically, when select this mode please set the\u3010Time Interval\u3011.<\/li>\n<li>\u3010Refreshed By Trigger Bit(0-&gt;1)\u3011\uff1awhen the bit turn 0 to 1, refresh variable content.<\/li>\n<li>\u3010Refreshed By Trigger Bit (1-&gt;0)\u3011\uff1awhen the bit turn 1 to 0, refresh variable content.<\/li>\n<li>\u3010Refreshed By Trigger Bit Changed\u3011: when the bit turn 1 to 0, refresh variable content.<\/li>\n<\/ul>\n<p>\u3010Trigger Bit\u3011<\/p>\n<p>Set the refresh variable content trigger address.       <\/p>\n<p>This setting only needs to set when\u3010Refresh Mode\u3011<\/p>\n<p>is\u3010Refreshed By Trigger Bit(0-&gt;1)\u3011\u3001\u3010Refreshed By Trigger Bit (1-&gt;0)\u3011or\u3010Refreshed By Trigger Bit Changed\u3011.<\/p>\n<p>\u3010Reset Trigger Bit\u3011<\/p>\n<p>Whether to reset trigger bit after refreshing variables.   <\/p>\n<p>This setting only needs to set when\u3010Refresh Mode\u3011<\/p>\n<p>is\u3010Refreshed By Trigger Bit(0-&gt;1)\u3011or\u3010Refreshed By Trigger Bit (1-&gt;0)\u3011.<\/p>\n<p>\u3010Number\u3011<\/p>\n<p>Set the number of variables.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>\u3010Variable\u3011<\/p>\n<\/td>\n<td>\n<p>\u3010Data Type\u3011<\/p>\n<p>Set the data type of variable.<\/p>\n<p>\u3010Address\u3011<\/p>\n<p>Set the address of variable.<\/p>\n<p>\u3010Words\u3011<\/p>\n<p>The number of words required of data types to display variables. If\u3010Data Type\u3011is\u3010Ascii String\u3011, then can set the number of words to collect at the beginning of the address.<\/p>\n<p>\u3010Min Text Width\u3011<\/p>\n<p>Set the minimum text width of the variable content. When the word width of the content is smaller than the minimum word width, it will be automatically filled with spaces to keep the minimum word width setting. <\/p>\n<p>\u3010Precision\u3011<\/p>\n<p>Set the precision of the variable.<\/p>\n<p>\u3010Gain\u3011<\/p>\n<p>Set the gain of the variable.<\/p>\n<p>\u3010Offset\u3011<\/p>\n<p>Set the offset of the variable.<\/p>\n<p>\u3010Lead Zero\u3011<\/p>\n<p>For Data Log\u2019s items that are not \u2018\u2019text\u2019\u2019 type, when the width of the printed content is less than the minimum width, it will automatically filled with \u2018\u20190\u2019\u2019.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>\u3010Template\u3011<\/p>\n<\/td>\n<td>\n<p>The user sets the variables and edits the pattern, and matches the keyword &quot;%[number]&quot; (eg: %1, %2, %3, etc.) to achieve the dynamic header\/footer requirements, where the keyword will be replaced by the actual content of the variable. <\/p>\n<p>\u3010Preview\u3011<\/p>\n<p>For setting preview header\/footer content, as shown below:<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/p5hmi-fvd-en-07\/p5hmi-fvd-en-07-014.png\" \/><\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<h4>7.2.5 \u3010Sync Data\u3011<\/h4>\n<p>Synchronize the data from the database. When enabled, the data will be automatically read from the database when the connection is successful. If you want to view it in the\u3010Historic Data Table\u3011, select\u3010Historic Data Table\u3011in the\u3010Source\u3011of the\u3010Historic Data Table\u3011.<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/p5hmi-fvd-en-07\/p5hmi-fvd-en-07-015.png\" \/><\/p>\n<p>Figure 130\u3010Data Log Group\u3011\u3010Sync Data\u3011Setting Page<\/p>\n<p>Table 56\u3010Data Log Group\u3011\u3010Sync Data\u3011Property Setting Page<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p><strong>Property<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>Description<\/strong><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Sync Data\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>Set whether to enable the data sync function. After enabling, the setting items will appear below.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010General\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>\u3010Destination\u3011<\/p>\n<p>Set the synchronize destination<\/p>\n<p>\u3010Database\u3011<\/p>\n<p>Set the synchronize database<\/p>\n<p>\u3010Table Name Prefix\u3011<\/p>\n<p>Set the generated table name of the after synchronization. If FvDatalog is set in this field then will generate FvDatalog_data and FvDatalog_data_format 2 tables.<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>Table Name<\/p>\n<\/td>\n<td>\n<p>Description<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>&lt;Customized Name&gt;_data<\/p>\n<\/td>\n<td>\n<p>Store the data of the Data Log<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>&lt; Customized Name &gt;_data_format<\/p>\n<\/td>\n<td>\n<p>Store the setting of the Data Log(Use for internal system)<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>Note: When the Data Log setting has changed (but the table name is not changed), after downloading to the HMI, the synchronized data table in the database needs to be deleted first then the new Data Log will take effect.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Control\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>\u3010Sync Mode\u3011<\/p>\n<p>Set the timing of synchronizing data to the database, including When Buffer is Full, When Bit is Triggered, Daily Synchronization, and Sync Regularly.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Status\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>\u3010Sync Status\u3011<\/p>\n<p>Set the storage address of the status<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>Value<\/p>\n<\/td>\n<td>\n<p>Status Description<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>0<\/p>\n<\/td>\n<td>\n<p>Unconnect<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>1<\/p>\n<\/td>\n<td>\n<p>Connecting<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>2<\/p>\n<\/td>\n<td>\n<p>Connected<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>3<\/p>\n<\/td>\n<td>\n<p>Synchronizing<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>\u3010Sync Error\u3011<\/p>\n<p>Set error code storage address<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>Value<\/p>\n<\/td>\n<td>\n<p>Status Description<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>0<\/p>\n<\/td>\n<td>\n<p>No error<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>1<\/p>\n<\/td>\n<td>\n<p>Unkown error<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>2<\/p>\n<\/td>\n<td>\n<p>Database connection failed<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>3<\/p>\n<\/td>\n<td>\n<p>Insufficient access authority<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>4<\/p>\n<\/td>\n<td>\n<p>Database name error<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>5<\/p>\n<\/td>\n<td>\n<p>Format error<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>6<\/p>\n<\/td>\n<td>\n<p>Table connection failed<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>7<\/p>\n<\/td>\n<td>\n<p>Build table failed<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>8<\/p>\n<\/td>\n<td>\n<p>Write table failed<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n","protected":false},"excerpt":{"rendered":"<p>Objects such as\u3010Lamp\u3011or\u3010Numeric Input\/Display\u3011can be us [&hellip;]<\/p>\n","protected":false},"author":1,"featured_media":0,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[57],"tags":[],"class_list":["post-3349","post","type-post","status-publish","format-standard","hentry","category-en-p5hmi-fvd"],"_links":{"self":[{"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/posts\/3349","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/comments?post=3349"}],"version-history":[{"count":0,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/posts\/3349\/revisions"}],"wp:attachment":[{"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/media?parent=3349"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/categories?post=3349"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/tags?post=3349"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}