{"id":3350,"date":"2026-11-17T18:42:41","date_gmt":"2026-11-17T10:42:41","guid":{"rendered":"https:\/\/resource.fatek.com\/index.php\/2026\/11\/17\/p5hmi-fvd-en-08\/"},"modified":"2026-11-17T18:42:41","modified_gmt":"2026-11-17T10:42:41","slug":"p5hmi-fvd-en-08","status":"publish","type":"post","link":"https:\/\/resource.fatek.com\/index.php\/2026\/11\/17\/p5hmi-fvd-en-08\/","title":{"rendered":"Chapter 8 Alarm"},"content":{"rendered":"<p>The alarm function is used to monitor value changes in specified registers. If the value exceeds the defined range, it will be recorded in the table. You can also configure it to issue an audible notification or send the report log via email through SMTP.<\/p>\n<h3>8.1 Alarm List<\/h3>\n<p>Click \u3010Alarm\u3011in the function list on the left side of FvDesigner to open the settings page.<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/p5hmi-fvd-en-08\/p5hmi-fvd-en-08-001.png\" \/><\/p>\n<p>Figure 131\u3010Alarm List\u3011Screen<\/p>\n<p>Table 57 \u3010Alarm List\u3011Property Setting Page<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p><strong>Property<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>Description<\/strong><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Basic\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>\u3010Enable Global Alarm Scrolling Text\u3011<br \/>When checked, a global alarm marquee will be displayed on all screens. You can configure the display direction and content.<\/p>\n<p>\u3010Enable Global Serial Number\u3011<br \/>This option must be enabled if you want the Alarm Display to show data from multiple groups.<\/p>\n<p>\u3010Show progress bar when saving\u3011<br \/>Check this option to display a progress bar on the screen when alarm data is being saved as a file.<\/p>\n<p>\u3010Group\u3011<br \/>Displays the alarm groups that have already been created. You can add, delete, or edit groups from the right side of the screen.<br \/>An HMI can create up to 64 groups, while a PC can create up to 256 groups.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Sync Data\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>This option is visible only when the project model is set to PC, and it is used to synchronize alarm data to a database.<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<h3>8.2 Alarm Setting<\/h3>\n<p>The properties of an\u3010Alarm\u3011is divided into\u3010Setting\u3011and\u3010Export Data\u3011, in which \u3010Setting\u3011is used to set the behavior and occurrence conditions of the\u3010Alarm\u3011 and\u3010Export Data\u3011is used to set data export behaviors for alarms that already occurred.<\/p>\n<h4>8.2.1 \u3010Setting\u3011<\/h4>\n<p>The \u201cSetting\u201d screen is as shown in the figure below, the meanings of each setting are also listed below:<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/p5hmi-fvd-en-08\/p5hmi-fvd-en-08-002.png\" \/><\/p>\n<p>Figure 132\u3010Setting\u3011Screen of\u3010Alarm\u3011<\/p>\n<p>Table 58\u3010Setting\u3011Properties of\u3010Alarm\u3011<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p><strong>Property<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>Description<\/strong><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Group ID\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>Set the Group ID of the\u3010Alarm\u3011.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Comment\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>Set the comment of the\u3010Alarm\u3011.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Import\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>A CSV or Excel file file can be selected after clicking this option. All of the\u3010Alarm\u3011contents of the file will be applied to the current\u3010Alarm\u3011settings.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Export\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>The settings of the current\u3010Alarm\u3011can be saved into a CSV or Excel file after clicking this option.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Group Setting\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>\u3010General\u3011<\/strong><\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td><\/td>\n<td>\n<p>Description<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>\u3010Records\u3011<\/p>\n<\/td>\n<td>\n<p>Set the maximum number of alarms to save for the current\u3010Alarm\u3011group.<\/p>\n<p>HMI can hold 10,000 and PC can hold 65,535 .<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>\u3010Backup Memory\u3011<\/p>\n<\/td>\n<td>\n<p>Set to enable Backup Memory.<\/p>\n<p>Select to save the Alarm data of the HMI into the backup memory of the HMI when the power to the HMI is interrupted in order to avoid data loss.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>\u3010Polling Frequency\u3011<\/p>\n<\/td>\n<td>\n<p>Sets the Polling Frequency of\u3010Alarm\u3011. When the Polling Frequency is set to 0, the system will read the monitoring address as quickly as possible. If the Polling Frequency is set to a value greater than 0, the system will read the monitoring address according to the set time. This lowers the computing load of the system.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>\u3010Alarm Control Bit\u3011<\/p>\n<\/td>\n<td>\n<p>Check whether to enable the control address, the scan will only be performed when this address is on.<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p><strong>\u3010Action\u3011<\/strong><\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td><\/td>\n<td>\n<p>Description<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>\u3010Independent alarm records for trigger, ack. and recovery status\u3011<\/p>\n<\/td>\n<td>\n<p>If checked, the trigger time, acknowledgement time, and recovery time will be recorded separately. If not checked, the trigger time, acknowledgement time, and recovery time will be recorded in the same row.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>\u3010Buffer Notification Bit\u3011<\/p>\n<\/td>\n<td>\n<p>Set whether to trigger a specific address when the data stored in the alarm is full.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>\u3010Enable Buffer Clear Bit\u3011<\/p>\n<\/td>\n<td>\n<p>Set whether to enable the function to clear the alarm buffer record.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>\u3010Turn on Backlight and turn off Screen Saver\u3011<\/p>\n<\/td>\n<td>\n<p>Set whether the alarm turns off the screen saver and turns on the backlight when an alarm in the given group occurs.<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Add\u3011<\/strong><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/p5hmi-fvd-en-08\/p5hmi-fvd-en-08-003.png\" \/><\/p>\n<\/td>\n<td>\n<p>Adds an alarm entry to the bottom of the alarm table when this button is pressed. The alarm address will automatically increase. For example, if the bottommost entry in the alarm table has an address of M10, when the\u3010Add\u3011button is pressed, the new alarm entry will have an address of M11. When the\u3010Data Type\u3011is set to bit, the address will increase bitwise. <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Delete\u3011<\/strong><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/p5hmi-fvd-en-08\/p5hmi-fvd-en-08-004.png\" \/><\/p>\n<\/td>\n<td>\n<p>The alarm data selected in the alarm table below will be deleted when this button is pressed.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Copy\u3011<\/strong><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/p5hmi-fvd-en-08\/p5hmi-fvd-en-08-005.png\" \/><\/p>\n<\/td>\n<td>\n<p>The alarm data selected in the alarm table below will be copied when this button is pressed.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Paste\u3011<\/strong><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/p5hmi-fvd-en-08\/p5hmi-fvd-en-08-006.png\" \/><\/p>\n<\/td>\n<td>\n<p>A new alarm data entry will be added and the alarm settings copied will be filled into this new alarm entry when this button is pressed.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Alarm Table\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>Set the occurrence condition of the\u3010Alarm\u3011.<\/p>\n<p>\u3010Data Type\u3011<\/p>\n<p>Set the data type for the monitoring address of the\u3010Alarm\u3011.<\/p>\n<p>\u3010Address\u3011<\/p>\n<p>Set the monitoring address of the\u3010Alarm\u3011.<\/p>\n<p>\u3010Condition\u3011<\/p>\n<p>Set the condition to determine that an\u3010Alarm\u3011has occurred.<\/p>\n<p>\u3010Value\u3011<\/p>\n<p>Set a value to determine if an\u3010Alarm\u3011has occurred.<\/p>\n<p>\u3010Dynamic Value\u3011<\/p>\n<p>After checking,\u3010Value\u3011will become address mode for users to input.<\/p>\n<p>\u3010Message\u3011<\/p>\n<p>Set the message to display when an\u3010Alarm\u3011has occurred.<\/p>\n<p>\u3010Level\u3011<\/p>\n<p>Set the level (1~8) of this\u3010Alarm\u3011entry. This can be used to distinguish between different levels of alarm.<\/p>\n<p>\u3010Advanced Setting\u3011<\/p>\n<p>When the\u3010Advanced Setting\u3011button is pressed, a pop up dialog will appear for users to set the advanced settings for\u3010Alarm\u3011.<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<h4>8.2.2 \u3010Advanced Setting\u3011<\/h4>\n<p>The\u3010Advanced Setting\u3011properties setting dialog is as shown in the figure below, the meaning of each setting are listed below:<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/p5hmi-fvd-en-08\/p5hmi-fvd-en-08-007.png\" \/><\/p>\n<p>Figure 133\u3010Advanced Setting\u3011Property Setting Dialog of\u3010Alarm\u3011<\/p>\n<p>Table 59\u3010Advanced Setting\u3011Properties of\u3010Alarm\u3011<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p><strong>Property<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>Description<\/strong><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Dead Band\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>Set the confirmed alarm recovery area after an\u3010Alarm\u3011occurred.<\/p>\n<p>For example, if the alarm occurrence condition is set as x&gt;100, and\u3010Dead Band\u3011is set as 5%, then when x&gt;100 the alarm occurs and when x&lt;96 the alarm will recover.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Time Delay (the Multiple of Polling Frequency\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>Set the delay time to do trigger delay. If the polling frequency set 1 second, time delay set 5, then the alarm will be triggered when all the conditions were met within 5 seconds.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Change Base Screen\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>Set whether to enable the\u3010Change Base Screen\u3011function. If the function is enabled, you can select the\u3010Base Screen\u3011you want to change to when the alarm is triggered. <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Show Window Screen\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>Set to enable the\u3010Show Window Screen\u3011function. The corresponding\u3010Window Screen\u3011for this alarm entry can be selected on the right once this option is enabled.<\/p>\n<p>If this function is enabled when the alarm occurs, a window screen will display or a\u3010Show Window\u3011sub switch can be pressed on the\u3010Alarm Display\u3011object to display the\u3010Window Screen\u3011set for this alarm.<\/p>\n<p>\u3010Close when Alarm is Recovered\u3011<\/p>\n<p>When the alarm is restored, the corresponding window screen will automatically close.<\/p>\n<p>\u3010Reopen while Alarm is not Recovered\u3011<\/p>\n<p>The window screen for the alarm will constantly reopen unless the alarm recovers.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Show Text View\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>When an alarm occurs, you can click the alarm and call a text window through the\u3010Sub Switch\u3011. After clicking the drop-down menu, you can select the existing text in the\u3010Text Library\u3011to display, or add an index and content by yourself.<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/p5hmi-fvd-en-08\/p5hmi-fvd-en-08-008.png\" \/><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010While Alarm is Triggered\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>Set to execute other behaviors when an alarm is triggered.<\/p>\n<p>\u3010Notification\u3011<\/p>\n<p>Set to notify specific addresses when an alarm is triggered. If this option is enabled, set the notification address and signal.<\/p>\n<p>Level: Set the bit as 0 or 1.<\/p>\n<p>Pulse: Set the bit to 1 and automatically restore to 0 after continuing the time set by\u3010Width\u3011.<\/p>\n<p>\u3010Send Email\u3011<\/p>\n<p>Checkable when \u3010SMTP\u3011 is enabled. If enable, you can set the address of the person to be notified when the alarm occurs, as well as additional messages and files. For details, refer to <strong>ch8.2.3-\u3010Send Email\/Message<\/strong> <strong>Setting\u3011<\/strong><\/p>\n<p>\u3010Send Message\u3011<\/p>\n<p>Checkable when \u30104G\u3011 is enabled. If enable, you can set the address of the person to be notified when the alarm occurs, as well as additional messages and files.<\/p>\n<p>\u3010IoT Message\u3011<\/p>\n<p>When this option is enabled, messages will be sent to third-party software via the IoT cloud server when an alarm is triggered.<\/p>\n<p>\t\u3010Attached Image\u3011When enabled, screenshots will be sent along with the message. However, please note that due to component update speeds, the image content may not correspond to the alarm content.<\/p>\n<p>\t\u3010Attached Information\u3011Enabling this option allows the configuration information of \u3010Record Address\u3011 in \u3010Setting\u3011 to be sent together.<\/p>\n<p>\t\u3010Context\u3011Enabling It is divided into \u3010Static\u3011 and \u3010Dynamic\u3011 and users can choose according to their needs. The receiving format can be previewed in \u3010Preview\u3011.<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/p5hmi-fvd-en-08\/p5hmi-fvd-en-08-009.png\" \/><\/p>\n<p><strong>(\u203b*For inquiries on how to bind third-party software, please refer to Chapter 7 of the &quot;FATEK IoT Cloud Service Manual&quot; available for download at\u5230<\/strong>h<a href=\"https:\/\/www.fatek.com\/en\/download.php?act=list&amp;cid=16\">Ittps:\/\/www.fatek.com\/en\/download.php?act=list&amp;cid=16<\/a><strong> )<\/strong><\/p>\n<p>\u3010Play Audio\u3011<\/p>\n<p>Set to play an audio file when an alarm is triggered. If this option is enabled, the audio set on the\u3010Audio Selector\u3011on the right which was selected from the\u3010sound library\u3011will be played when an alarm occurs. The\u3010Duration\u3011for the playback of the audio is controlled by the setting items below:\u3010Single Shot\u3011,\u3010Time-based\u3011,\u3010Until Acknowledged or Recovered\u3011and\u3010Until Screen is Touched\u3011are available for selection. <\/p>\n<p>When select enable and select the audio file is from microSD or USB storage, you can set the file name of the microSD or USB storage audio file, when alarm happens, will play the set of the audio, file name need to contain filename extention.<\/p>\n<p>If select\u3010Address\u3011, then the file name can be controlled by the set of the address.<\/p>\n<p>Build a audio file in the microSD or USB storage, and put the audio file in the audio folder, the audio file can be read by HMI when the alarm ring.<\/p>\n<p>\u3010Buzzer\u3011<\/p>\n<p>Sets whether or not to play the buzzer when the alarm is triggered. The buzzer sounds there are short, long, short-short, and long-short 4 ways. You can choose the buzz type, and adjust the\u3010Duration\u3011where you can choose\u3010Single Shot\u3011,\u3010Time-Based\u3011,\u3010Until Acknowledged or Recovered\u3011or\u3010Until Screen is Touched\u3011.<\/p>\n<p>\u3010Play Time\u3011<\/p>\n<p>When the\u3010Time-based\u3011option is selected, an option will appear and the play duration can be set.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Notify while Alarm is Acknowledged\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>Set to notify specific addresses when an alarm is acknowledged. If this option is enabled, the notification address set on the right will be set or reset when an alarm is acknowledged.<\/p>\n<p>Level: Set the bit as 0 or 1.<\/p>\n<p>Pulse: Set the bit to 1 and automatically restore to 0 after continuing the time set by\u3010Width\u3011.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Notify while Alarm is Recovered\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>Set to notify specific addresses when an alarm is recovered. If this option is enabled, the notification address set on the right will be set or reset when an alarm recovers.<\/p>\n<p>Level: Set the bit as 0 or 1.<\/p>\n<p>Pulse: Set the bit to 1 and automatically restore to 0 after continuing the time set by\u3010Width\u3011.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Number of Recorded Address\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>Set the number of address to read when an alarm is triggered; it can be set between 1~8. When the number set is changed, the number of rows in the address record table below will also change accordingly.<\/p>\n<p>\u3010Data Type\u3011<\/p>\n<p>Set the data type of the address to read when an alarm is triggered.<\/p>\n<p>\u3010Address\u3011<\/p>\n<p>Set the address to read when an alarm is triggered.<\/p>\n<p>\u3010Comment\u3011<\/p>\n<p>Set the comment of the address to read when an alarm is triggered. This comment can allow users to identify what the address represents.<\/p>\n<p>\u3010Precision\u3011<\/p>\n<p>Set the decimal point of the recorded value displayed in the\u3010Alarm Display\u3011.<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<h4>8.2.3 \u3010Send Email\/Message Setting\u3011<\/h4>\n<p>The\u3010Setting\u3011dialog box for sending emails is shown in the figure below. <\/p>\n<p>The meaning of each setting option is as follows:<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/p5hmi-fvd-en-08\/p5hmi-fvd-en-08-010.png\" \/><\/p>\n<p>Figure 134\u3010Advanced Setting\u3011\u3010Send Email\/Message\u3011Property Setting Dialog of\u3010Alarm\u3011<\/p>\n<p>Table 60\u3010Advanced Setting\/Message\u3011\u3010Send Email\u3011Properties of\u3010Alarm\u3011<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>Options<\/p>\n<\/td>\n<td>\n<p>Description<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>\u3010Recipent\u3011<\/p>\n<\/td>\n<td>\n<p>When the alarm occurs, the recipient of the email must first set the\u3010Contacts\u3011and\u3010Groups\u3011in the\u3010Contact Lists\u3011tab of the\u3010SMTP\u3011tab in\u3010Severs\u3011, or the\u3010Contacts\u3011button on the right set\u3010Contacts\u3011and\u3010Groups\u3011to be selected here. <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>\u3010Contacts\u3011<\/p>\n<\/td>\n<td>\n<p>Provide the e-mail address of the person who receive the e-mail, and\u3010Contacts\u3011and\u3010Groups\u3011, etc. Press \u3010Contact Lists\u3011, the following figure will appear, you can add, delete, edit, import, export, etc. For more details, refer to <strong>chapter4.3.1-\u3010SMTP\u3011setting<\/strong>.<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/p5hmi-fvd-en-08\/p5hmi-fvd-en-08-011.png\" \/><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>\u3010Title\u3011<\/p>\n<\/td>\n<td>\n<p>Title of email, the title will be group\u2019s name if do not checked the\u3010Use Customized Title\u3011box on the right side, such as Alarm.Group 1.2, which indicates the second alarm in the first group of the alarm. Check the box\u3010Use Customized Title\u3011to edit the title of the mail here.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>\u3010Attached Information\u3011<\/p>\n<\/td>\n<td>\n<p>Set whether to send an email when an alarm occurs attach other messages or files at the same time.<\/p>\n<p>\u3010Attach Screenshot\u3011<\/p>\n<p>Check whether to attach HMI screenshot while sending email.<\/p>\n<p>\u3010Attach Image from Video Input\u3011<\/p>\n<p>Check whether to attach image from video input while sending email.<\/p>\n<p>\u3010Time\u3011<\/p>\n<p>Check whether to attach occurring time while sending email.<\/p>\n<p>\u3010Message\u3011<\/p>\n<p>Check whether to attach alarm message while sending email.<\/p>\n<p>\u3010Record Address\u3011<\/p>\n<p>Check whether to attach record address while sending email.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>\u3010Context\u3011<\/p>\n<\/td>\n<td>\n<p>\u3010Static\u3011<\/p>\n<p>Set the mail content and sent it when the alarm occurs.<\/p>\n<p>\u3010Dynamic\u3011<\/p>\n<p>A maximum of 99 bytes can be set, and the register of the sending message needs to be set<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<h4>8.2.4 \u3010Export Data\u3011<\/h4>\n<p>The\u3010Export Data\u3011screen is as shown in the figure below, the meaning of each setting are listed below:<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/p5hmi-fvd-en-08\/p5hmi-fvd-en-08-012.png\" \/><\/p>\n<p>Figure 135\u3010Export Data\u3011Setting Screen of\u3010Alarm\u3011<\/p>\n<p>Table 61\u3010Export Data\u3011Setting Properties of\u3010Alarm\u3011<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p><strong>Property<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>Description<\/strong><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Export Data\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>Set to enable the export function of the alarm data. Export setting items will appear below once this option is selected.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010General\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>\u3010Format\u3011<\/p>\n<p>Set the format of the export file; TXT file , CSV file or PDF file can be selected.<\/p>\n<p>\u3010Destination\u3011<\/p>\n<p>Set the destination of the exported file: internal, microSD card or USB storage device can be selected.<\/p>\n<p>If the output destination is internal storage, you can use FTP to connect to the HMI to read the stored file.<\/p>\n<p>\u3010Export Mode\u3011<\/p>\n<p>Set the time to export the file. If\u3010Export Regularly\u3011is selected, the alarm occurrence data saved by\u3010Alarm\u3011will be exported according to a set interval. If\u3010Triggered by Bit\u3011is selected, the alarm occurrence data saved by\u3010Alarm\u3011will be exported when the set bit is triggered.<\/p>\n<p>\u3010Time Interval\/Trigger Bit\u3011<\/p>\n<p>Depending on the export method, you can select export conditions here.<\/p>\n<p>\u3010File Name\u3011<\/p>\n<p>Set the name of the exported file; the file name of the exported file name includes the date and time the file was saved (for example: Alarm_140519_151735.txt).<\/p>\n<p>\u3010Suffix\u3011<\/p>\n<p>Set the name of the exported file, such as yymmdd_hh,<\/p>\n<p>the name of exported file only dates and hours<\/p>\n<p>(Example: DataLog_140519_17.txt)<\/p>\n<p>This setting also provides export archive mode,<\/p>\n<p>If the suffix selected is &quot;yymm&quot;, it would produce one file per month,<\/p>\n<p>If the suffix selected is &quot;yymmdd&quot;, it would produce one file per day,<\/p>\n<p>If the suffix select &quot;yymmdd_hh&quot;, it would produce one file per hour,<\/p>\n<p>If the suffix selected is &quot; yymmdd_hhmm&quot;, it would produce one file per minute,<\/p>\n<p>If the suffix selected is &quot; yymmdd_hhmmss&quot;, it would produce one file per second,<\/p>\n<p>If the suffix to select &quot;no&quot;, one file includes all data.<\/p>\n<p>\u3010Create a folder with the name from comment\u3011<\/p>\n<p>If this option is checked, the name of the folder will be name from\u3010Setting\u3011\u3010Comment\u3011, for example, comment temperature, the original Group_1 folder will be changed to the temperature folder, which is originally alarm \\ Group_1 will become alarm \\ temperature.<\/p>\n<p>\u3010Save to the default folder\u3011<\/p>\n<p>There is none and folder created monthly two opitons, if choose none then will not create another folder, for example, alarm \\Group_1\\ Alarm _170403. csv. if choose folder created monthly then will create another monthly folder each month, for example, alarm \\Group_1\\201704\\ Alarm _170403.csv.<\/p>\n<p>\u3010PDF Setting\u3011<\/p>\n<p>When the export format is set to PDF, clicking Settings allows you to adjust the PDF document style.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Date\/Time Format\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>\u3010Date\u3011<\/p>\n<p>Set the display format of the date when exporting file.<\/p>\n<p>\u3010Time\u3011<\/p>\n<p>Set the display format of the time when exporting file.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Output Data\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>\u3010Output Data\u3011allows you to choose which items to export. You can select whether the export file will contain the alarm index, serial number, trigger date, alarm annotation, trigger time, confirmation time, recovery time, message, level, number of occurences, and record address. <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Automatically Delete\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>Check if you want to automatically delete the exported file.<\/p>\n<p>\u3010Preserve files for\u3011<\/p>\n<p>For example, if you set 7 days, the HMI will check whether there are files over 7 days according to the calendar in the early morning of each day, and those files will be deleted.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Manually Delete (all files)\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>Set the control bit to delete the files manually.<\/p>\n<p>\u3010Control Bit\u3011<\/p>\n<p>Set a bit as trigger control, delete when on, and automatically turn back to off after finish deleting.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Upload to Remote\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>Enable ch4.5-\u3010FTP Client\u3011function then this option can be seen.<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/p5hmi-fvd-en-08\/p5hmi-fvd-en-08-013.png\" \/><\/p>\n<p>\u3010Trigger Address\u3011<\/p>\n<p>Set a bit to trigger uploading.<\/p>\n<p>\u3010Select Server\u3011<\/p>\n<p>Click the drop-down menu to select the server to upload<\/p>\n<p>\u3010Upload Folder\u3011<\/p>\n<p>Fill in the path where the remote server is stored, if not filled in, it will be stored in the root directory of the server<\/p>\n<p>\u3010Upload mode\u3011<\/p>\n<p>There are 7 upload modes for\u3010Static\u3011, which will be described together with\u3010Dynamic\u3011below<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>Setting Value(INT)<\/p>\n<\/td>\n<td>\n<p>Description<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>-10<\/p>\n<\/td>\n<td>\n<p>Upload the oldest 10 files in directory<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>-5<\/p>\n<\/td>\n<td>\n<p>Upload the oldest 5 files in directory<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>-1<\/p>\n<\/td>\n<td>\n<p>Upload the oldest file in directory<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>0<\/p>\n<\/td>\n<td>\n<p>Upload all files in directory<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>1<\/p>\n<\/td>\n<td>\n<p>Upload the lastest file in directory<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>5<\/p>\n<\/td>\n<td>\n<p>Upload the lastest 5 files in directory<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>10<\/p>\n<\/td>\n<td>\n<p>Upload the lastest 10 files in directory<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>\u3010Send Result\u3011<\/p>\n<p>Set the address of the execution result display, the data type is\u3010INT\u3011,<\/p>\n<p>Success: 1 \/ Failure: -1<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Status Address\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>Set the save address for error codes.<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>Error Code<\/p>\n<\/td>\n<td>\n<p>Description<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>0<\/p>\n<\/td>\n<td>\n<p>No Error<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>1<\/p>\n<\/td>\n<td>\n<p>Read Error<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>2<\/p>\n<\/td>\n<td>\n<p>Write Error<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>5<\/p>\n<\/td>\n<td>\n<p>Open Error<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>100<\/p>\n<\/td>\n<td>\n<p>Not enough storage space<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<h3>8.3 Alarm Application Example<\/h3>\n<p>This section explains the application examples of the\u3010Alarm\u3011function and its setting procedure.<\/p>\n<h4>8.3.1 Enabling SMTP<\/h4>\n<p>To send emails, first enable the SMTP feature. Go to the <strong>System<\/strong> menu on the left side of FvDesigner and select <strong>Server<\/strong>.<\/p>\n<p>For detailed settings, refer to section 4.3\u3010SMTP\u3011<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/p5hmi-fvd-en-08\/p5hmi-fvd-en-08-014.png\" \/><\/p>\n<p>Figure 136\u3010SMTP\u3011Setting window<\/p>\n<h4>8.3.2 Configuring Email Sending<\/h4>\n<p>In <strong>Advanced Settings<\/strong>, check <strong>Enable Email Sending<\/strong>.<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/p5hmi-fvd-en-08\/p5hmi-fvd-en-08-015.png\" \/><\/p>\n<p>Figure 137 Enable Email Sending<\/p>\n<h4>8.3.3 Setting Up Email Content<\/h4>\n<p>Set the recipient group (click <strong>Contacts<\/strong> to configure), check the information to be attached, add a description, and save it.<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/p5hmi-fvd-en-08\/p5hmi-fvd-en-08-016.png\" \/><\/p>\n<p>Figure 138 Set Email Content<\/p>\n<h4>8.3.4 Receiving Emails<\/h4>\n<p>After downloading the project, emails will be received when an alarm is triggered.<br \/>To adjust fixed content (such as time and message text), go to <strong>System Messages<\/strong> to set the language used.<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/p5hmi-fvd-en-08\/p5hmi-fvd-en-08-017.png\" \/><\/p>\n<p>Figure 139 Received Email<\/p>\n<h3>8.4 \u3010Sync Data\u3011<\/h3>\n<p>Synchronize the alarm data from the database. When enabled, the data will be automatically read from the database when the connection is successful. If you want to view it in the\u3010Alarm Display\u3011, select\u3010Database\u3011in the\u3010Display Type\u3011of the \u3010Alarm Display\u3011.<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/p5hmi-fvd-en-08\/p5hmi-fvd-en-08-018.png\" \/><\/p>\n<p>Figure 140\u3010Alarm\u3011\u3010Sync Data\u3011Setting Page<\/p>\n<p>Table 62\u3010Alarm\u3011\u3010Sync Data\u3011Property Setting Page<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p><strong>Property<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>Description<\/strong><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Sync Data\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>Set whether to enable the data sync function. After enabling, the setting items will appear below.<\/p>\n<p>Note: If enable this function, needs to enable serial number as well.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010General\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>\u3010Destination\u3011<\/p>\n<p>Set the synchronize destination<\/p>\n<p>\u3010Database\u3011<\/p>\n<p>Set the synchronize database<\/p>\n<p>\u3010Table Name Prefix\u3011<\/p>\n<p>Set the generated table name of the after synchronization. If set name \u201calarm\u201d as the figure above, then will generate two tables: alarm_data and alarm_data_format.<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>Table Name<\/p>\n<\/td>\n<td>\n<p>Description<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>&lt;Customized Name&gt;_data<\/p>\n<\/td>\n<td>\n<p>Store the data of the Alarm<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>&lt; Customized Name &gt;_data_format<\/p>\n<\/td>\n<td>\n<p>Store the setting of the Alarm(Use for internal system)<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>Note: When the Alarm setting has changed (but the table name is not changed), after downloading to the HMI, the synchronized data table in the database needs to be deleted first then the new alarm will take effect.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Control\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>\u3010Sync Mode\u3011<\/p>\n<p>Set the timing of synchronizing data to the database, including When Buffer is Full, When Bit is Triggered, Daily Synchronization, and Sync Regularly.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>\u3010Status\u3011<\/strong><\/p>\n<\/td>\n<td>\n<p>\u3010Sync Status\u3011<\/p>\n<p>Set the storage address of the status<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>Value<\/p>\n<\/td>\n<td>\n<p>Status Description<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>0<\/p>\n<\/td>\n<td>\n<p>Unconnect<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>1<\/p>\n<\/td>\n<td>\n<p>Connecting<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>2<\/p>\n<\/td>\n<td>\n<p>Connected<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>3<\/p>\n<\/td>\n<td>\n<p>Synchronizing<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>\u3010Sync Error\u3011<\/p>\n<p>Set error code storage address<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>Value<\/p>\n<\/td>\n<td>\n<p>Status Description<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>0<\/p>\n<\/td>\n<td>\n<p>No error<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>1<\/p>\n<\/td>\n<td>\n<p>Unkown error<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>2<\/p>\n<\/td>\n<td>\n<p>Database connection failed<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>3<\/p>\n<\/td>\n<td>\n<p>Insufficient access authority<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>4<\/p>\n<\/td>\n<td>\n<p>Database name error<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>5<\/p>\n<\/td>\n<td>\n<p>Format error<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>6<\/p>\n<\/td>\n<td>\n<p>Table connection failed<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>7<\/p>\n<\/td>\n<td>\n<p>Build table failed<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>8<\/p>\n<\/td>\n<td>\n<p>Write table failed<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n","protected":false},"excerpt":{"rendered":"<p>The alarm function is used to monitor value changes in  [&hellip;]<\/p>\n","protected":false},"author":1,"featured_media":0,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[57],"tags":[],"class_list":["post-3350","post","type-post","status-publish","format-standard","hentry","category-en-p5hmi-fvd"],"_links":{"self":[{"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/posts\/3350","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/comments?post=3350"}],"version-history":[{"count":0,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/posts\/3350\/revisions"}],"wp:attachment":[{"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/media?parent=3350"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/categories?post=3350"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/tags?post=3350"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}