{"id":3378,"date":"2026-11-17T21:05:05","date_gmt":"2026-11-17T13:05:05","guid":{"rendered":"https:\/\/resource.fatek.com\/index.php\/2026\/11\/17\/fbs-hw-en-101\/"},"modified":"2026-11-17T21:12:55","modified_gmt":"2026-11-17T13:12:55","slug":"fbs-hw-en-101","status":"publish","type":"post","link":"https:\/\/resource.fatek.com\/index.php\/2026\/11\/17\/fbs-hw-en-101\/","title":{"rendered":"Appendix 1 FATEK Communication Protocol"},"content":{"rendered":"<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-101\/fbs-hw-en-101-001.png\" \/><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-101\/fbs-hw-en-101-002.png\" \/><\/p>\n<p>This Protocol is each communication port of FATEK PLC to communicate with the peripherals under standard mode. Any peripherals that want to communicate with FATEK PLC model have to meet the rules, not only the hardware connection but also the software parameter setting. Besides, the message format also has to be the same with this protocol so that the PLC can respond normally. <\/p>\n<p>1.1  Master and Slave Definition and Communication<\/p>\n<p>FATEK PLC is defined as slaves in the communication with peripheral devices that are always defined as masters when communicate with FATEK PLC. All the peripheral devices send the message when communicate with FATEK PLC and its respond when receive the message from masters. <\/p>\n<p>Command message <\/p>\n<p>Master \tSlave (peripheral devices) (FATEK PLC) <\/p>\n<p>Response <\/p>\n<p>1.2  The Communication Message Format of FATEK PLC <\/p>\n<p>\tThere are 6 data columns in the FATEK PLC communication format including command (master) and response (slave) message. <\/p>\n<p>Sending direction <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td colspan=\"2\" rowspan=\"2\">\n<p>First send <\/p>\n<\/td>\n<td colspan=\"7\">\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-101\/fbs-hw-en-101-003.png\" \/><\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>Last send<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"2\" rowspan=\"3\">\n<p>d<\/p>\n<\/td>\n<td rowspan=\"3\">\n<p>e<\/p>\n<\/td>\n<td colspan=\"2\" rowspan=\"3\">\n<p>f<\/p>\n<\/td>\n<td colspan=\"2\" rowspan=\"3\">\n<p>g<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"2\">\n<p>\u2193<\/p>\n<\/td>\n<td>\n<p>\u2193<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"2\">\n<p>c<\/p>\n<\/td>\n<td>\n<p>h<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"3\">\n<p>Column name\u2192<\/p>\n<\/td>\n<td rowspan=\"3\">\n<p>Start code <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>Slave <\/p>\n<\/td>\n<td colspan=\"5\">\n<p>Command <\/p>\n<\/td>\n<td>\n<p>End <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"2\">\n<p>station <\/p>\n<\/td>\n<td>\n<p>No. <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>Data <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>Checksum <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>code <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"7\">\n<p>No. <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>ASCII code\u2192<\/p>\n<\/td>\n<td>\n<p>STX <\/p>\n<\/td>\n<td>\n<p>H <\/p>\n<\/td>\n<td>\n<p>L <\/p>\n<\/td>\n<td>\n<p>H <\/p>\n<\/td>\n<td>\n<p>L <\/p>\n<\/td>\n<td>\n<p>0\uff5e500 ASCII code <\/p>\n<\/td>\n<td>\n<p>H <\/p>\n<\/td>\n<td>\n<p>L <\/p>\n<\/td>\n<td>\n<p>ETX <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>Pick LRC <\/p>\n<p>cStart code\uff08STX\uff09\uff1a The hexadecimal code of the STX in ASCII code is 02H. The start characters are all STX in command and response message. The receiving site can determine the data start code with STX.<\/p>\n<p>dThe station No. of slave \uff1aThe station numbers are hexadecimal two-number value. There is only master station and are 255 slave stations in the PLC communication frame. Every slave station has the only number from 1\uff5eFEH.\uff08if the station No. is 0, it means the master can send command to all slaves\uff09When the master want to send command to one or all\uff08station No.=0\uff09it accords the station No. assignment. The slave will send its own station No. when it send response message to master.<\/p>\n<p>Remark\uff1a The default value of station No. for PLC is all 1. The station No. can not be amended in the net, it can \tbe changed or amended through FP-08 or WinProladder. <\/p>\n<p>eCommand code \uff1aThe command No. is two numbers of hexadecimal systems. It is the action which the master wants slave to execute. For example, to read or write the status of discrete, force setting, run, stop\u2026 The command No. which is received from master is also included in response message when slave send the response message.<\/p>\n<p>fData information \uff1aThe data information contains 0\uff08no data\uff09\uff5e500 ASCII character. The data in this column is to assign the address or value for reading or writing. The beginning of this data information contains the error code in the response message. In normal condition\uff08no error happened\uff09the error code must be 0\uff0830H\uff09in the beginning and then follow the responding status or value in the response message. When error happened, it will be the error code instead of 0\uff0830H\uff09and it will not follow the data information.<\/p>\n<p>gChecksum     \uff1aChecksum check the hexadecimal value of ASCII code in the previous c\uff5ef columns and produce one checksum value in one byte length (two hexadecimal value 00\uff5eFF\uff09with \u201cLRC (Longitudinal Redundancy Check)\u201d method. This message will be checked with the same way at the receiving side when the message is received. When the two check values are the same, it means the data transferred correctly. If the two check values are different, there are some error happened. The calculation of LRC method is to add all the hexadecimal value (8 bits length) of ASCII code and ignore to carry the number to keep the check value at 8 bits length.<\/p>\n<p>hEnd code \uff08ETX\uff09\uff1aThe hexadecimal code of EXT code of ASCII is 03H. The EXT code of either command or response is all ETX. When the receiving side receive the ETX code, it means the data transmission terminated and start to process command or data.<\/p>\n<p>1.3  The Communication Error Code of FATEK PLC <\/p>\n<p>If the error happened in OS command, address, value area of software operation or hardware problem will cause the slave system can not process the command comes from master system. If there is error happened, slave system will respond the message to master system. No matter what command code or data the master system sends, the format of responding message is all the same. Including the required start code (STX), end code (ETX) and checksum value, the command code and station No. will be sent back to master system. The slave system will judge what kind of the error and respond the error code to master system. <\/p>\n<p>\u25cf Following table is the response format of communication error of FATEK PLC\uff1a<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>Error code <\/p>\n<\/td>\n<td>\n<p>Description <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>0 <\/p>\n<\/td>\n<td>\n<p>Error free <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>2 <\/p>\n<\/td>\n<td>\n<p>Illegal value. <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>4 <\/p>\n<\/td>\n<td>\n<p>Illegal format, or communication command can not execute. <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>5 <\/p>\n<\/td>\n<td>\n<p>Can not run\uff08Ladder Checksum error when run PLC\uff09<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>6 <\/p>\n<\/td>\n<td>\n<p>Can not run\uff08PLC ID\u2260Ladder ID when run PLC\uff09<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>7 <\/p>\n<\/td>\n<td>\n<p>Can not run\uff08Snytax check error when run PLC\uff09<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>9 <\/p>\n<\/td>\n<td>\n<p>Can not run\uff08Function not supported\uff09<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>A <\/p>\n<\/td>\n<td>\n<p>Illegal address <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>1.4  The Function Description of Communication Command <\/p>\n<p>\tIn this section only focus on communication command code and explain the command message of master and the response format of slave.\uff08only perform the examples in success\uff09<\/p>\n<p>1.4.1 The Classification and Assignment of Components<\/p>\n<p>The main function of PLC communication is to read and write the status or value inside PLC components. Concerning the discrete and register which are available for read and write and address assignment are as following table\uff1a<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td><\/td>\n<td><\/td>\n<td>\n<p>Name <\/p>\n<\/td>\n<td>\n<p>Discrete address \uff085 characters\uff09<\/p>\n<\/td>\n<td>\n<p>16 bits register address\uff086 characters\uff09<\/p>\n<\/td>\n<td>\n<p>32 bits register address \uff087 characters\uff09<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"6\"><\/td>\n<td>\n<p>X <\/p>\n<\/td>\n<td>\n<p>Input discrete <\/p>\n<\/td>\n<td>\n<p>X0000\uff5eX9999 <\/p>\n<\/td>\n<td>\n<p>WX0000\uff5eWX9984 <\/p>\n<\/td>\n<td>\n<p>DWX0000\uff5eDWX9968 <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Y <\/p>\n<\/td>\n<td>\n<p>Output relay <\/p>\n<\/td>\n<td>\n<p>Y0000\uff5eY9999 <\/p>\n<\/td>\n<td>\n<p>WY0000\uff5eWY9984 <\/p>\n<\/td>\n<td>\n<p>DWY0000\uff5eDWY9968 <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>M <\/p>\n<\/td>\n<td>\n<p>Internal relay <\/p>\n<\/td>\n<td>\n<p>M0000\uff5eM9999 <\/p>\n<\/td>\n<td>\n<p>WM0000\uff5eWM9984 <\/p>\n<\/td>\n<td>\n<p>DWM0000\uff5eDWM9968 <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>S <\/p>\n<\/td>\n<td>\n<p>Step relay <\/p>\n<\/td>\n<td>\n<p>S0000\uff5eS9999 <\/p>\n<\/td>\n<td>\n<p>WS0000\uff5eWS9984 <\/p>\n<\/td>\n<td>\n<p>DWS0000\uff5eDWS9968 <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>T <\/p>\n<\/td>\n<td>\n<p>Timer discrete <\/p>\n<\/td>\n<td>\n<p>T0000\uff5eT9999 <\/p>\n<\/td>\n<td>\n<p>WT0000\uff5eWT9984 <\/p>\n<\/td>\n<td>\n<p>DWT0000\uff5eDWT9968 <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>C <\/p>\n<\/td>\n<td>\n<p>Counter discrete <\/p>\n<\/td>\n<td>\n<p>C0000\uff5eC9999 <\/p>\n<\/td>\n<td>\n<p>WC0000\uff5eWC9984 <\/p>\n<\/td>\n<td>\n<p>DWC0000\uff5eDWC9968 <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"5\"><\/td>\n<td>\n<p>TMR <\/p>\n<\/td>\n<td>\n<p>Timer register <\/p>\n<\/td>\n<td>\n<p>\u2212 <\/p>\n<\/td>\n<td>\n<p>RT0000\uff5eRT9999 <\/p>\n<\/td>\n<td>\n<p>DRT0000\uff5eDRT9998 <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>CTR <\/p>\n<\/td>\n<td>\n<p>Counter register <\/p>\n<\/td>\n<td>\n<p>\u2212 <\/p>\n<\/td>\n<td>\n<p>RC0000\uff5eRC9999 <\/p>\n<\/td>\n<td>\n<p>DRC0000\uff5eDRC9998 <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>HR <\/p>\n<\/td>\n<td>\n<p>Data register <\/p>\n<\/td>\n<td>\n<p>\u2212 <\/p>\n<\/td>\n<td>\n<p>R00000\uff5eR65535 <\/p>\n<\/td>\n<td>\n<p>DR00000\uff5eDR65534 <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>DR <\/p>\n<\/td>\n<td>\n<p>Data register <\/p>\n<\/td>\n<td>\n<p>\u2212 <\/p>\n<\/td>\n<td>\n<p>D00000\uff5eD65535 <\/p>\n<\/td>\n<td>\n<p>DD00000\uff5eDD65534 <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>FR <\/p>\n<\/td>\n<td>\n<p>File register <\/p>\n<\/td>\n<td>\n<p>\u2212 <\/p>\n<\/td>\n<td>\n<p>F00000\uff5eF65535 <\/p>\n<\/td>\n<td>\n<p>DF00000\uff5eDF65534 <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>\u25cfThe discrete status\uff08X\uff0cY\uff0cM\uff0cS\uff09can combine 16 or 32 continuous status as the 16-bit or 32-bit register, such as the <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>above table WX\u25b3\u25b3\u25b3\u25b3 or DWX\u25b3\u25b3\u25b3\u25b3<\/p>\n<\/td>\n<td>\n<p>, but \u25b3\u25b3\u25b3\u25b3<\/p>\n<\/td>\n<td>\n<p> should be multiple of 8.<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>\u25cfIt needs 5 characters when assign the discrete address and 6 characters when assign the 16-bit register address and \t7 characters to assign the 32-bit register address. <\/p>\n<p>\u25cfThe address boundary of components in above table is the largest for FATEK PLC. Users should notice the valid address and attribution of each PLC components.\uff08ex. The boundary for X\u3001Y address is 0000\uff5e0255; for S is 0000\uff5e0999 of FBE-PLC\uff09 If exceed the boundary of valid address, PLC will reply error code \u201cA\u201d (illegal address), and will not execute that command. <\/p>\n<p>1.4.2 The Description of Communication Command<\/p>\n<p>\u25cfThe description of communication command\uff1a<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>Command code <\/p>\n<\/td>\n<td>\n<p>Function description <\/p>\n<\/td>\n<td>\n<p>Message length can be <br \/>processed during one scan <\/p>\n<\/td>\n<td>\n<p>Remark <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>40 <\/p>\n<\/td>\n<td>\n<p>The gist read the system status of PLC <\/p>\n<\/td>\n<td>\n<p>\u2212 <\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td>\n<p>41 <\/p>\n<\/td>\n<td>\n<p>Control RUN\/STOP of PLC <\/p>\n<\/td>\n<td>\n<p>\u2212 <\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td>\n<p>42 <\/p>\n<\/td>\n<td>\n<p>Single discrete control <\/p>\n<\/td>\n<td>\n<p>1 point <\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>43 <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>The status reading of ENABLE\/DISABLE of continuous discrete <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>1\uff5e256 points <\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td><\/td>\n<\/tr>\n<tr>\n<td>\n<p>44 <\/p>\n<\/td>\n<td>\n<p>The status reading of continuous discrete <\/p>\n<\/td>\n<td>\n<p>1\uff5e256 points <\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td>\n<p>45 <\/p>\n<\/td>\n<td>\n<p>Write the status to continuous discrete <\/p>\n<\/td>\n<td>\n<p>1\uff5e256 points <\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td>\n<p>46 <\/p>\n<\/td>\n<td>\n<p>Read the data from continuous registers <\/p>\n<\/td>\n<td>\n<p>1\uff5e64 Words <\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td>\n<p>47 <\/p>\n<\/td>\n<td>\n<p>Write to continuous registers <\/p>\n<\/td>\n<td>\n<p>1\uff5e64 Words <\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>48 <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>Mixed read the random discrete status of register data<\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>1\uff5e64 points or Words <\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td><\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>49 <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>Mixed write the random discrete status of register data<\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>1\uff5e32 points or Words <\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td><\/td>\n<\/tr>\n<tr>\n<td>\n<p>4E <\/p>\n<\/td>\n<td>\n<p>Loop back testing <\/p>\n<\/td>\n<td>\n<p>0\uff5e256 characters <\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td>\n<p>53 <\/p>\n<\/td>\n<td>\n<p>The detail read the system status of PLC <\/p>\n<\/td>\n<td>\n<p>\u2212 <\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<\/table>\n<\/div>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p> 1\uff1a   The message of discrete status is represented by one character (1 means ON, 0 means OFF) and the \tdata of 16-bit register uses 4 characters to represent the value of one WORD\uff080000H\uff5eFFFFH\uff09<\/p>\n<p> 2\uff1a   The data of 32-bit register is DW\uff08two continuous Words\uff09, it has to use 8 characters to represent its data. If the component is 32-bit register, the component has to be treated as 2W. For example, in command code 46 and 47, they can process 64 16-bit components and only process 32 32-bit components. <\/p>\n<p> 3\uff1a\tIn the command code 48 and 49, the message length is the total of discrete and word. They can not \texceed 64W(command 48) and 32W(command 49). As increase one point, its total words will decrease \tone word. It is the same in the other hand. Because the message length of 32-bit component uses 2 \twords, it will be less 2 words or point when increase one 32-bit component. For example, the message \tlength of command 48 is 1\uff5e64W. If it read 20 32-bit components, its message will occupy 40 words and \tremain 24W available for discrete or 16-bit register. In this example, command code can read 44 \tcomponents\uff0820 32-bit components and 24discrete or 16-bit components\uff09 in one communication. <\/p>\n<p> 4\uff1a\tThe operation (read and write) of continuous discrete or register is not only one component and the \tnumbers are continuous so that you don\u2019t need to assign their components number during your \tassignment. You just only need to appoint the start number and how many components (N). Its operating \tobject can only being one of discrete or register and can not be operated randomly. <\/p>\n<p> 5\uff1a  The random operating objects can read or write several discrete and register. As their number is not \tcontinuous, you have to appoint their number and allow operating discrete and register randomly. <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-101\/fbs-hw-en-101-004.png\" \/><\/p>\n<p>\u25cfCommand code 40\uff08Read the system status of PLC\uff09<\/p>\n<p>Format <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"2\">\n<p>MASTER <\/p>\n<\/td>\n<td>\n<p>S <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>0 <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>1 <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>4 <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>0 C 7 <\/p>\n<\/td>\n<td>\n<p>E <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>Command <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>X <\/p>\n<\/td>\n<td>\n<p>X <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>H L H L H L <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"2\">\n<p>PLC <\/p>\n<\/td>\n<td>\n<p>S <\/p>\n<\/td>\n<td rowspan=\"3\">\n<p>1 <\/p>\n<\/td>\n<td rowspan=\"3\">\n<p>4 <\/p>\n<\/td>\n<td rowspan=\"3\">\n<p>0 <\/p>\n<\/td>\n<td colspan=\"2\" rowspan=\"2\">\n<p>STATUS <\/p>\n<\/td>\n<td colspan=\"2\" rowspan=\"2\">\n<p>STATUS <\/p>\n<\/td>\n<td colspan=\"2\" rowspan=\"2\">\n<p>STATUS <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>H <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>L <\/p>\n<\/td>\n<td>\n<p>E <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>T <br \/>X 0 <\/p>\n<\/td>\n<td>\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>response <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>1 <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>2 <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>3 <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>X <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>H <\/p>\n<\/td>\n<td>\n<p>L <\/p>\n<\/td>\n<td>\n<p>H <\/p>\n<\/td>\n<td>\n<p>L <\/p>\n<\/td>\n<td>\n<p>H <\/p>\n<\/td>\n<td>\n<p>L <\/p>\n<\/td>\n<td>\n<p>H <\/p>\n<\/td>\n<td>\n<p>L <\/p>\n<\/td>\n<td>\n<p>H <\/p>\n<\/td>\n<td>\n<p>L <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>B0\uff1aRUN\/STOP <\/p>\n<p>B2\uff1aLadder checksum <\/p>\n<p>error\/NORMAL <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"3\">\n<p>STATUS 1\uff1a<\/p>\n<\/td>\n<td rowspan=\"3\">\n<p>B7 <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>H <\/p>\n<\/td>\n<td rowspan=\"3\">\n<p>B5 <\/p>\n<\/td>\n<td rowspan=\"3\">\n<p>B4 <\/p>\n<\/td>\n<td rowspan=\"3\">\n<p>B3 <\/p>\n<\/td>\n<td rowspan=\"3\">\n<p>B2 <\/p>\n<\/td>\n<td rowspan=\"3\">\n<p>L <\/p>\n<\/td>\n<td rowspan=\"3\">\n<p>B1 <\/p>\n<\/td>\n<td rowspan=\"3\">\n<p>B0 <\/p>\n<\/td>\n<td>\n<p>B3\uff1aUSE MEMORY PACK\/NOT <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>USE <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>B6 <\/p>\n<\/td>\n<td>\n<p>B4\uff1aWDT Timeout\/NORMAL <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>B5\uff1aSET ID\/NOT SET ID <\/p>\n<p>STATUS 2\uff1a    Reserved \tB6\uff1aEMERGENCY <\/p>\n<p>(LADDER \t\t STOP\/NORMAL program \tB7\uff1a0\uff08RESERVE FOR capacity) \t\t FUTURE\uff09<\/p>\n<p>STATUS 3\uff1a\t0\uff08RESERVE FOR FUTURE\uff09<\/p>\n<p>Ex. If the PLC is equipped with MEMORY PACK and ID is set in both PLC and MEMORY PACK and PLC status <\/p>\n<p>is \u201cRUN\u201d under normal condition, the system status of PLC which MASTER read will be as following: <\/p>\n<p>\uff08B5,B3, and B0 are 1 and the other are all 0 that the STATUS is 29H\uff09\u3002<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"2\">\n<p>MASTER <\/p>\n<\/td>\n<td>\n<p>S <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>0 1 4 0 C 7 <\/p>\n<\/td>\n<td>\n<p>E <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>Command <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>X <\/p>\n<\/td>\n<td>\n<p>X <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>02H 30H 31H 34H 30H 43H 37H 03H <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"3\">\n<p>PLC <br \/>response <\/p>\n<\/td>\n<td>\n<p>S <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>E <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>T <\/p>\n<\/td>\n<td>\n<p>0 1 4 0 0 2 9 0 0 0 0 2 2 <\/p>\n<\/td>\n<td>\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"3\">\n<p>X X <\/p>\n<p>02H 30H 31H 34H 30H 30H 32H 39H 30H 30H 30H 30H 32H 32H 03H <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-101\/fbs-hw-en-101-005.png\" \/><\/p>\n<p>\u25cfCommand code 41\uff08Control the PLC RUN\/STOP\uff09<br \/>Format <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"2\">\n<p>MASTER <\/p>\n<\/td>\n<td>\n<p>S <\/p>\n<\/td>\n<td rowspan=\"3\">\n<p>0 <\/p>\n<\/td>\n<td rowspan=\"3\">\n<p>1 <\/p>\n<\/td>\n<td rowspan=\"3\">\n<p>4 <\/p>\n<\/td>\n<td rowspan=\"3\">\n<p>1 <\/p>\n<\/td>\n<td colspan=\"5\">\n<p>E <\/p>\n<\/td>\n<td rowspan=\"8\">\n<p>1 <\/p>\n<\/td>\n<td rowspan=\"10\">\n<p>H <\/p>\n<\/td>\n<td rowspan=\"10\">\n<p>L <\/p>\n<\/td>\n<td rowspan=\"6\">\n<p>E <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>C 7 <\/p>\n<\/td>\n<td colspan=\"4\" rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"4\">\n<p>Command <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"7\">\n<p>X <\/p>\n<\/td>\n<td colspan=\"4\" rowspan=\"7\">\n<p>H L H L <\/p>\n<\/td>\n<td colspan=\"5\">\n<p>X <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"5\">\n<p>H L <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"5\">\n<p>S <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>PLC <\/p>\n<\/td>\n<td colspan=\"3\" rowspan=\"2\">\n<p>T <br \/>X 0 <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>1 <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>4 <\/p>\n<\/td>\n<td>\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"3\">\n<p>response <\/p>\n<\/td>\n<td rowspan=\"3\">\n<p>X <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"3\">\n<p>H <\/p>\n<\/td>\n<td>\n<p>L <\/p>\n<\/td>\n<td>\n<p>H <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>L <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"2\">\n<p>Control <\/p>\n<\/td>\n<td colspan=\"3\">\n<p>0\uff1aSTOP <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>Ex. <\/p>\n<\/td>\n<td>\n<p>Turn on PLC to \u201cRUN\u201d <\/p>\n<\/td>\n<td>\n<p>code <\/p>\n<\/td>\n<td>\n<p>1\uff1aRUN <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"2\">\n<p>MASTER <\/p>\n<\/td>\n<td>\n<p>S <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>0 1 4 1 1 F 9 <\/p>\n<\/td>\n<td>\n<p>E <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>Command <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>X <\/p>\n<\/td>\n<td>\n<p>X <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>02H 30H 31H 34H 31H 31H 46H 39H 03H <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"3\">\n<p>PLC <br \/>response <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>S <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>E <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>T <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>0 1 4 1 0 F 8 <\/p>\n<\/td>\n<td>\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"4\">\n<p>X \tX <\/p>\n<p>02H 30H 31H 34H 31H 30H 46H 38H 03H <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-101\/fbs-hw-en-101-006.png\" \/><\/p>\n<p>\u25cfCommand code 42\uff08Single discrete control\uff09<\/p>\n<p>Format \tThis command can control the appointed discrete to do ENABLE, DISABLE, SET, RESET four activities. <\/p>\n<p>S \tE <\/p>\n<p>MASTER <\/p>\n<p>T \t0 1 4 2 \tDiscrete No. \tT <\/p>\n<p>Command \tX \tX <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"2\">\n<p>PLC <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>H L H L <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>H L <\/p>\n<\/td>\n<td>\n<p>S <\/p>\n<\/td>\n<td rowspan=\"3\">\n<p>0 1 4 2 <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>H L <\/p>\n<\/td>\n<td>\n<p>E <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>response <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>X <\/p>\n<\/td>\n<td>\n<p>H L H L <\/p>\n<\/td>\n<td>\n<p>X <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>1\uff1aDisable <\/p>\n<p>Running 2\uff1aEnable <\/p>\n<p>code 3\uff1aSet <\/p>\n<p>4\uff1aReset <\/p>\n<p>Ex. The following communication format is the example to DISABLE the discrete X16. <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"2\">\n<p>MASTER <\/p>\n<\/td>\n<td>\n<p>S <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>0 1 4 2 1 X 0 0 1 6 1 9 <\/p>\n<\/td>\n<td>\n<p>E <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>Command <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>X <\/p>\n<\/td>\n<td>\n<p>X <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>02H 30H 31H34H32H 31H 58H 30H 30H 31H 36H 31H 39H 03H <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"2\">\n<p>PLC <\/p>\n<\/td>\n<td>\n<p>S <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>0 1 4 2 0 F 9 <\/p>\n<\/td>\n<td>\n<p>E <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>response <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>X <\/p>\n<\/td>\n<td>\n<p>X <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>02H 30H 31H 34H 32H 30H 46H 39H 03H <\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-101\/fbs-hw-en-101-007.png\" \/><\/p>\n<p>\u25cfCommand code 43\uff08The status reading of ENABLE\/DISABLE of continuous discrete\uff09<\/p>\n<p>Format \tUse this command to read the ENABLE\/DISABLE status of continuous adding discrete. <\/p>\n<p>S \tE <\/p>\n<p>MASTER <\/p>\n<p>T 0 1 4 3 Start No. \tT <\/p>\n<p>Command \tX \tX <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"3\">\n<p>PLC <\/p>\n<\/td>\n<td rowspan=\"8\">\n<p>H L H L <\/p>\n<\/td>\n<td rowspan=\"8\">\n<p>Number N\uff1a<\/p>\n<\/td>\n<td colspan=\"3\">\n<p>H L <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>E <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"3\">\n<p>S <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>0 1 4 3 <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>\u2027\u2027\u2027\u2027<\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"5\">\n<p>response <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"3\">\n<p>X <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>X <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"2\">\n<p>H L H L <\/p>\n<\/td>\n<td>\n<p>H L <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"3\">\n<p>The range of Hex value of two number can be <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"3\">\n<p>1\u2264N\u2264256\uff08When N=00H it equals to 256\uff09<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>Ex. If Y10\uff0cY12\uff0cY16 of the continuous 7 discrete, Y10\uff5eY16 are DISABLE and the others are all ENABLE, the <\/p>\n<p>PLC status of this command reading is as following. <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"2\">\n<p>MASTER <\/p>\n<\/td>\n<td>\n<p>S <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>0 1 4 3 0 7 Y 0 0 1 0 4 B <\/p>\n<\/td>\n<td>\n<p>E <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>Command <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>X <\/p>\n<\/td>\n<td>\n<p>X <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p> 02H 30H 31H 34H 33H 30H 37H 59H 30H 30H 31H 30H 34H 42H 03H <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"2\">\n<p>PLC <\/p>\n<\/td>\n<td>\n<p>S <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>0 1 4 3 0 1 0 1 0 0 0 1 4 D <\/p>\n<\/td>\n<td>\n<p>E <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>response <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>X <\/p>\n<\/td>\n<td>\n<p>X <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>02H 30H 31H 34H 33H 30H 31H 30H 31H 30H 30H 30H 31H 34H 44H 03H <\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-101\/fbs-hw-en-101-008.png\" \/><\/p>\n<p>\u25cfCommand code 44\uff08The status reading of continuous discrete\uff09<\/p>\n<p>Format <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"2\">\n<p>MASTER <\/p>\n<\/td>\n<td>\n<p>S <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>0 1 4 4 <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>Start No. <\/p>\n<\/td>\n<td>\n<p>E <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>Command <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>X <\/p>\n<\/td>\n<td>\n<p>X <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"3\">\n<p>PLC <\/p>\n<\/td>\n<td rowspan=\"8\">\n<p>H L H L <\/p>\n<\/td>\n<td rowspan=\"8\">\n<p>Number N\uff1a<\/p>\n<\/td>\n<td colspan=\"3\">\n<p>H L <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>E <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"3\">\n<p>S <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>0 1 4 4 <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>\u2027\u2027\u2027\u2027<\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"5\">\n<p>response <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"3\">\n<p>X <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>X <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"2\">\n<p>H L H L <\/p>\n<\/td>\n<td>\n<p>H L <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"3\">\n<p>The range of Hex value of two numbers can be <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"3\">\n<p>1\u2264N\u2264256\uff08When N=00H, is equals to 256\uff09<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>Ex. If the status of X50, X52, X55 are all 0 and X51, X53, X54 are all 1, following is the status of reading the <\/p>\n<p>continuous 6 inputs\uff08X50\uff5eX55\uff09<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"2\">\n<p>MASTER <\/p>\n<\/td>\n<td>\n<p>S <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>0 1 4 4 0 6 X 0 0 5 0 4 E <\/p>\n<\/td>\n<td>\n<p>E <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>Command <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>X <\/p>\n<\/td>\n<td>\n<p>X <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>02H 30H 31H 34H 34H 30H 36H 58H 30H 30H 35H 30H 34H 44H 03H <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"2\">\n<p>PLC <\/p>\n<\/td>\n<td>\n<p>S <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>0 1 4 4 0 0 1 0 1 1 0 1 E <\/p>\n<\/td>\n<td>\n<p>E <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>response <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>X <\/p>\n<\/td>\n<td>\n<p>X <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>02H 30H 31H 34H 34H 30H 30H 31H 30H 31H 31H 30H 31H 44H 03H <br \/>X55 Status <br \/>X54 Status<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"2\">\n<p>No error <\/p>\n<\/td>\n<td>\n<p>X53 Status<\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>N=6<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>X52 Status<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>X51 Status <br \/>X50 Status<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-101\/fbs-hw-en-101-009.png\" \/><\/p>\n<p>\u25cfCommand code 45\uff08Write the status to continuous discrete\uff09<\/p>\n<p>Format <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"2\">\n<p>MASTER <\/p>\n<\/td>\n<td>\n<p>S <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>0 1 4 5 <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>Start No. <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>\u2027\u2027\u2027\u2027<\/p>\n<\/td>\n<td>\n<p>E <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>Command <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>X <\/p>\n<\/td>\n<td>\n<p>X <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"3\">\n<p>PLC <\/p>\n<\/td>\n<td rowspan=\"8\">\n<p>H L H L <\/p>\n<\/td>\n<td rowspan=\"8\">\n<p>Number N\uff1a<\/p>\n<\/td>\n<td colspan=\"3\">\n<p>H L <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>E <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"3\">\n<p>S <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<td colspan=\"2\" rowspan=\"2\">\n<p>0 1 4 5 <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"5\">\n<p>response <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"3\">\n<p>X <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>X <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"2\">\n<p> H L H L <\/p>\n<\/td>\n<td>\n<p>H L <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"3\">\n<p>The range of Hex value of two numbers can be <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"3\">\n<p>1\u2264N\u2264256\uff08When N=00H it equals to256\uff09<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>Ex. <\/p>\n<\/td>\n<td>\n<p>Write the status to continuous 4 outputs\uff08Y0\uff5eY3\uff09, Y0 and Y3 are 1, Y1 and Y2 are 0. <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>Y0 Status <br \/>Y1 Status <br \/>Y2 Status <br \/>Y3 Status <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"2\">\n<p>MASTER <\/p>\n<\/td>\n<td>\n<p>S <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>0 1 4 5 0 4 Y 0 0 0 0 1 0 0 1 0 B <\/p>\n<\/td>\n<td>\n<p>E <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>Command <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>X <\/p>\n<\/td>\n<td>\n<p>X <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p> 02H 30H 31H 34H 35H 30H 34H 59H 30H 30H 30H 30H 31H 30H 30H 31H 30H 42H 03H <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"2\">\n<p>PLC <\/p>\n<\/td>\n<td>\n<p>S <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>0 1 4 5 0 F C <\/p>\n<\/td>\n<td>\n<p>E <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>response <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>X <\/p>\n<\/td>\n<td>\n<p>X <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>02H 30H 31H 34H 35H 30H 46H 43H 03H <\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-101\/fbs-hw-en-101-010.png\" \/><\/p>\n<p>\u25cfCommand code 46\uff08Read the data from continuous registers\uff09<\/p>\n<p>Format <\/p>\n<p>\u2027\u2027\u2027<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"2\">\n<p>MASTER <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>S <\/p>\n<\/td>\n<td colspan=\"2\" rowspan=\"2\">\n<p>Start register No. <\/p>\n<\/td>\n<td>\n<p>E <\/p>\n<\/td>\n<td colspan=\"2\" rowspan=\"6\">\n<p>S <\/p>\n<\/td>\n<td rowspan=\"5\">\n<p>\u2027\u2027\u2027<\/p>\n<\/td>\n<td rowspan=\"10\">\n<p>\u2027\u2027\u2027\u2027<\/p>\n<\/td>\n<td rowspan=\"5\">\n<p>\u2027\u2027\u2027<\/p>\n<\/td>\n<td rowspan=\"6\">\n<p>E <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>0 1 4 6 <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>Command <\/p>\n<\/td>\n<td colspan=\"2\" rowspan=\"2\">\n<p>(6 or 7 words) <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"2\">\n<p>X <\/p>\n<\/td>\n<td rowspan=\"7\">\n<p>X <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"3\">\n<p>PLC <\/p>\n<\/td>\n<td colspan=\"2\" rowspan=\"6\">\n<p> H L H L <\/p>\n<\/td>\n<td rowspan=\"6\">\n<p>\u2027\u2027\u2027<\/p>\n<\/td>\n<td rowspan=\"6\">\n<p> H L <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Data 1 <\/p>\n<\/td>\n<td>\n<p>Data N <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>0 1 4 6 <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>(4 or 8 <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>(4 or 8 <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"3\">\n<p>response <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"2\">\n<p>X <\/p>\n<\/td>\n<td>\n<p>number) <\/p>\n<\/td>\n<td>\n<p>number) <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>X <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"2\">\n<p> H L H L <\/p>\n<\/td>\n<td>\n<p>\u2027\u2027\u2027<\/p>\n<\/td>\n<td>\n<p>\u2027\u2027\u2027 H L <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>\u25cf Number N consists of Hex value of two numbers, its range can be 01H\uff5e40H or 20H\uff0832-bit component\uff09\u25cf The number of 16-bit register contains 6 characters and the Hex value of its data contains 4 characters. \uff08It can \t\tbe shown as 0000H\uff5eFFFFH\uff09<br \/>\u25cf The number of 32-bit register contains 7 characters and the Hex value of its data contains 8 characters.\uff08It can be shown as 00000000H\uff5eFFFFFFFFH\uff09<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"4\">\n<p>Ex. <\/p>\n<p>MASTER <\/p>\n<p>Command <\/p>\n<\/td>\n<td colspan=\"3\">\n<p>Read the data of continuous 3 16-bit registers and start with R12.\uff08R12\uff0cR13\uff0cR14\uff09<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>S <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>E <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>T <\/p>\n<\/td>\n<td>\n<p>0 1 4 6 0 3 R 0 0 0 1 2 7 5 <\/p>\n<\/td>\n<td>\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>X <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>X <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>02H 30H 31H 34H 36H 30H 33H 52H 30H 30H 30H 31H 32H 37H 35H 03H <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"2\">\n<p>PLC <\/p>\n<\/td>\n<td>\n<p>S <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>0 1 4 6 0 1 0 A 5 7 F C 4 0 0 0 1 8 9 <\/p>\n<\/td>\n<td>\n<p>E <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>response <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>X <\/p>\n<\/td>\n<td>\n<p>X <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>02H 30H 31H34H 36H 30H 31H 30H 41H 35H 37H 46H 43H 34H 30H 30H 30H 31H 38H 39H 03H <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>The data <\/p>\n<\/td>\n<td>\n<p>The data <\/p>\n<\/td>\n<td>\n<p>The data <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>of R12 <\/p>\n<\/td>\n<td>\n<p>of R13 <\/p>\n<\/td>\n<td>\n<p>of R14 <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>\u25cf Refer to the above example, the PLC responds as R12=10A5H, R13=7FC4H, R14=0001H <\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-101\/fbs-hw-en-101-011.png\" \/><\/p>\n<p>\u25cfCommand code 47\uff08Write to continuous registers\uff09<\/p>\n<p>Format <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"3\">\n<p>MASTER <\/p>\n<\/td>\n<td colspan=\"2\" rowspan=\"2\">\n<p>S <\/p>\n<\/td>\n<td>\n<p>\u2027\u2027\u2027<\/p>\n<\/td>\n<td>\n<p>\u2027\u2027\u2027<\/p>\n<\/td>\n<td rowspan=\"10\">\n<p>\u2027\u2027\u2027<\/p>\n<\/td>\n<td>\n<p>\u2027\u2027\u2027<\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>E <\/p>\n<\/td>\n<td colspan=\"2\" rowspan=\"6\">\n<p>S <\/p>\n<\/td>\n<td rowspan=\"10\">\n<p>H L <\/p>\n<\/td>\n<td rowspan=\"6\">\n<p>E <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>Start register No. <\/p>\n<\/td>\n<td>\n<p>Data 1 <\/p>\n<\/td>\n<td>\n<p>Data N <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>0 1 4 7 <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>(4 or 8 <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>(4 or 8 <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>Command <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>(6 or 7 words) <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"2\">\n<p>X <\/p>\n<\/td>\n<td>\n<p>numbers) <\/p>\n<\/td>\n<td>\n<p>numbers) <\/p>\n<\/td>\n<td rowspan=\"6\">\n<p>X <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>PLC <\/p>\n<\/td>\n<td colspan=\"2\" rowspan=\"5\">\n<p> H L H L <\/p>\n<\/td>\n<td rowspan=\"5\">\n<p>\u2027\u2027\u2027<\/p>\n<\/td>\n<td rowspan=\"5\">\n<p>\u2027\u2027\u2027<\/p>\n<\/td>\n<td rowspan=\"5\">\n<p>\u2027\u2027\u2027 H L <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>0 1 4 7 <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"3\">\n<p>response <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"2\">\n<p>X <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>X <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"2\">\n<p> H L H L <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>\u25cf Number N consists of Hex value of two numbers, its range can be 01H\uff5e40H or 20H\uff0832-bit component\uff09\u25cf The number of 16-bit register contains 6 characters and the Hex value of its data contains 4 characters.\uff08It can be \tshown as 0000H\uff5eFFFFH\uff09<br \/>\u25cf The number of 32-bit register contains 7 characters and the Hex value of its data contains 8 characters.\uff08It can be \tshown as 00000000H\uff5eFFFFFFFFH\uff09<\/p>\n<p>Ex. Input AAAAH to the 16-bit register WY8 and input 5555H to WY24.  This is the format of input data to continuous register because WY8 and WY24 are continuous. <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>Start component <\/p>\n<\/td>\n<td>\n<p>WY8 Data <\/p>\n<\/td>\n<td>\n<p>WY24 Data <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>numbers <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"2\">\n<p>MASTER <\/p>\n<\/td>\n<td>\n<p>S <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>0 1 4 7 0 2 WY 0 0 0 8 A A A A 5 5 5 5 8 0 <\/p>\n<\/td>\n<td>\n<p>E <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>Command <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>X <\/p>\n<\/td>\n<td>\n<p>X <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>02H 30H 31H 34H 37H 30H 32H 57H 59H 30H 30H 30H 38H 41H 41H 41H 41H 35H 35H 35H 35H 38H 30H 03H <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"2\">\n<p>PLC <\/p>\n<\/td>\n<td>\n<p>S <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>0 1 4 7 0 F F <\/p>\n<\/td>\n<td>\n<p>E <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>response <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>X <\/p>\n<\/td>\n<td>\n<p>X <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>02H 30H 31H 34H 37H 30H 46H 45H 03H <\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-101\/fbs-hw-en-101-012.png\" \/><\/p>\n<p>\u25cfCommand code 48\uff08Mixed read the random discrete status or register data\uff09Format <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"3\">\n<p>MASTER <\/p>\n<\/td>\n<td colspan=\"2\" rowspan=\"2\">\n<p>S <\/p>\n<\/td>\n<td>\n<p>\u2027\u2027\u2027<\/p>\n<\/td>\n<td colspan=\"2\">\n<p>\u2027\u2027\u2027<\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>E <\/p>\n<\/td>\n<td rowspan=\"6\">\n<p>S <\/p>\n<\/td>\n<td rowspan=\"9\">\n<p>0 1 4 8 <\/p>\n<\/td>\n<td rowspan=\"9\">\n<p>c<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"3\" rowspan=\"4\">\n<p>(5 , 6 or 7 words) \u2027\u2027\u2027\u2027\u2027\u2027Component No.N <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>0 1 4 8 <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>Command <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"2\">\n<p>X <\/p>\n<\/td>\n<td rowspan=\"5\">\n<p>X <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>PLC <\/p>\n<\/td>\n<td colspan=\"2\" rowspan=\"4\">\n<p> H L H L <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>\u2027\u2027\u2027<\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>\u2027\u2027\u2027<\/p>\n<\/td>\n<td rowspan=\"4\">\n<p> H L <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>response <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>X <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p> H L H L <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"5\">\n<p>c<\/p>\n<\/td>\n<td>\n<p>\u2027\u2027\u2027<\/p>\n<\/td>\n<td rowspan=\"5\">\n<p>\u2027\u2027\u2027\u2027\u2027\u2027<\/p>\n<\/td>\n<td colspan=\"2\">\n<p>\u2027\u2027\u2027<\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>E <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Component No.1 <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>Component No.N <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>data <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>data <\/p>\n<\/td>\n<td>\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>(1, 4 or 8 numbers) <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>(1, 4 or 8 numbers)<\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>X <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>\u2027\u2027\u2027<\/p>\n<\/td>\n<td>\n<p>\u2027\u2027\u2027<\/p>\n<\/td>\n<td>\n<p> H L <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>\u25cfNumber N consists of Hex value of two numbers, it means the total numbers of components. Its range can be 01H\t\uff5e40H.\uff08Refer to the item 3\uff09<br \/>\u25cfIf the component is discrete, its number can only be 5 characters and status response can only be one number \uff081 \tor 0\uff09<br \/>\u25cfIf the component is 16-bit register, its number can be 6 characters and data response is Hex value of 4 characters. \u25cfIf the component is 32-bit register, its number can be 7 characters and data response is Hex value of 8 characters. <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>Ex. <\/p>\n<\/td>\n<td colspan=\"6\">\n<p>Read the status and data of R1\uff0cY9 and DWM0\uff08i.e. M31\uff5eM0\uff09<\/p>\n<\/td>\n<td rowspan=\"8\">\n<p>S <\/p>\n<\/td>\n<td rowspan=\"10\">\n<p>0 1 4 8 <\/p>\n<\/td>\n<td rowspan=\"10\">\n<p>c<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"4\">\n<p>Component 1 <\/p>\n<\/td>\n<td>\n<p>Component 2 <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>Component 3 <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"2\" rowspan=\"2\">\n<p>MASTER <\/p>\n<\/td>\n<td>\n<p>S <\/p>\n<\/td>\n<td colspan=\"3\" rowspan=\"4\">\n<p>0 1 4 8 0 3 R 0 0 0 0 1 Y 0 0 0 9 D W M 0 0 0 0 3 F <\/p>\n<\/td>\n<td>\n<p>E <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"2\" rowspan=\"2\">\n<p>Command <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>X <\/p>\n<\/td>\n<td>\n<p>X <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"7\">\n<p>02H 30H 31H 34H 38H 30H 33H 52H 30H 30H 30H 30H 31H 59H 30H 30H 30H 39H 44H 57H 4DH 30H 30H 30H 30H 33H 46H 03H <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"2\" rowspan=\"3\">\n<p>PLC <br \/>response <\/p>\n<\/td>\n<td colspan=\"5\" rowspan=\"3\">\n<p>The status of <br \/>component 2 <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>X <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>\t\t\t\t\t\t\t\t02H 30H 31H 34H 38H \tData of component 1 \tData of component 3 <br \/>\t\tc <br \/>\t\t\t\t\t\tE <br \/>\t\t\t\t0 5 C 3 4 1 0 0 3 5 4 7 B A C 5 T <br \/>\t\t\t\t\t\tX <br \/>\t\t\t30H 35H 43H 33H 34H 31H 30H 30H 33H 35H 34H 37H 42H 41H 43H 35H 03H <br \/>\u25cfIn the above example, R1=5C34H and Y9 status is 1\uff08\u301dON\u301e\uff09\uff0cDWM0=3547BAH <\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-101\/fbs-hw-en-101-013.png\" \/><\/p>\n<p>\u25cfCommand code 49\uff08Mixed write the random discrete status or register data\uff09<\/p>\n<p>Format <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"3\">\n<p>MASTER <\/p>\n<\/td>\n<td colspan=\"2\" rowspan=\"2\">\n<p>S <\/p>\n<\/td>\n<td>\n<p>\u2027\u2027\u2027<\/p>\n<\/td>\n<td>\n<p>\u2027\u2027\u2027<\/p>\n<\/td>\n<td rowspan=\"6\">\n<p>\u2027\u2027\u2027\u2027\u2027\u2027\u2027\u2027\u2027\u2027\u2027<\/p>\n<\/td>\n<td>\n<p>\u2027\u2027\u2027<\/p>\n<\/td>\n<td rowspan=\"6\">\n<p>c<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>Component No.1 <\/p>\n<\/td>\n<td>\n<p>Component No.1 <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>Component No.N <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>0 1 4 9 <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>data <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"3\">\n<p>Command <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>(5, 6 or 7 words) <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>(5, 6 or 7 words) <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"2\">\n<p>X <\/p>\n<\/td>\n<td>\n<p>(1, 4 or 8 words) <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"2\">\n<p> H L H L <\/p>\n<\/td>\n<td>\n<p>\u2027\u2027\u2027<\/p>\n<\/td>\n<td>\n<p>\u2027\u2027\u2027<\/p>\n<\/td>\n<td>\n<p>\u2027\u2027\u2027<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>\u2027\u2027\u2027<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"5\">\n<p>PLC <\/p>\n<\/td>\n<td rowspan=\"8\">\n<p>c<\/p>\n<\/td>\n<td>\n<p>Component No.N <\/p>\n<\/td>\n<td rowspan=\"8\">\n<p>H L <\/p>\n<\/td>\n<td>\n<p>E <\/p>\n<\/td>\n<td colspan=\"2\" rowspan=\"4\">\n<p>S <\/p>\n<\/td>\n<td rowspan=\"8\">\n<p>H L <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>E <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>data <\/p>\n<\/td>\n<td>\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>(1, 4 or 8 words) <\/p>\n<\/td>\n<td rowspan=\"6\">\n<p>X <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"5\">\n<p>\u2027\u2027\u2027<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>0 1 4 9 <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"3\">\n<p>response <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"2\">\n<p>X <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>X <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"2\">\n<p> H L H L <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>\u25cf Number N consists of Hex value of two numbers, it means the total numbers of write to components. Its range \tcan be 01H\uff5e40H.\uff08Refer to the item 3\uff09<\/p>\n<p>\u25cfIf the component is discrete, its number can only be 5 characters and status response can only be one number \t\uff080 or 1\uff09<\/p>\n<p>\u25cf If the component is 16-bit register, its number can be 6 characters and data response is Hex value of 4 \tcharacters. <\/p>\n<p>\u25cf If the component is 32-bit register, its number can be 7 characters and data response is Hex value of 8 \tcharacters. <\/p>\n<p>Ex. Set the status of Y0 at 1, Y1 at 0, 16-bit register WM8 at 5555H, 32-bit register DR2 at FFH. <\/p>\n<p>The status of component 1  The status of component 2 <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"6\">\n<p>MASTER <br \/>Command <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>Component 1 <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>Component 2 Component 3  Data of component 3 <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"4\">\n<p>S <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>T <\/p>\n<\/td>\n<td colspan=\"3\">\n<p>0 1 4 9 0 4 Y 0 0 0 0 1 Y 0 0 0 1 0 W M 0 0 0 8 5 5 5 5 <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"4\">\n<p>X <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"3\">\n<p>02H 30H 31H 34H 39H 30H 34H 59H 30H 30H 30H 30H 31H 59H 30H 30H 30H 31H 30H 57H 4DH 30H 30H 30H 38H 35H 35H 35H 35H <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>c<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"2\">\n<p>Component 4 <\/p>\n<\/td>\n<td>\n<p>Data of component 4 <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>E <\/p>\n<p>D R 0 0 0 0 2 0 0 0 0 0 0 F F 3 C T <\/p>\n<p>X <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"2\">\n<p>PLC <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>c<\/p>\n<\/td>\n<td rowspan=\"4\">\n<p> 44H 52H 30H 30H 30H 30H 32H 30H 30H 30H 30H 30H 30H 46H 46H 33H 43H 03H <\/p>\n<\/td>\n<td>\n<p>S <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>0 1 4 9 0 0 0 <\/p>\n<\/td>\n<td>\n<p>E <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>response <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>X <\/p>\n<\/td>\n<td>\n<p>X <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>02H 30H 31H 34H 39H 30H 30H 30H 03H <\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-101\/fbs-hw-en-101-014.png\" \/><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-101\/fbs-hw-en-101-015.png\" \/><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-101\/fbs-hw-en-101-016.png\" \/><\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td colspan=\"2\">\n<p>\u25cfCommand code 4E\uff08Loop back testing\uff09<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"2\" rowspan=\"2\">\n<p>Format <\/p>\n<p>This command makes PLC respond all test data back to Master. It is only for testing the communication condition between Master and PLC and it will not influence the PLC function. <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"2\">\n<p>ER <\/p>\n<\/td>\n<td>\n<p>S <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>0 1 4 E <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>Testing data X <\/p>\n<\/td>\n<td>\n<p>E <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>and <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>X <\/p>\n<\/td>\n<td>\n<p>X <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"4\">\n<p>se <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p> H L H L <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>H L <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>S <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>Testing data X <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>H L <\/p>\n<\/td>\n<td>\n<p>E <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>T <\/p>\n<\/td>\n<td>\n<p>0 1 4 6 <\/p>\n<\/td>\n<td>\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"2\">\n<p>X <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>X <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"2\">\n<p> H L H L <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>These two messages are all the same <\/p>\n<\/td>\n<\/tr>\n<tr><\/tr>\n<tr>\n<td colspan=\"2\" rowspan=\"2\">\n<p>Ex. <\/p>\n<p>Use this command to send the data\u301dABCDEFG\u301efrom Master to PLC to rest weather the PLC respond <\/p>\n<p>normally. <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"2\">\n<p>ER <\/p>\n<\/td>\n<td>\n<p>S <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>0 1 4 E A B C D E F G B 8 <\/p>\n<\/td>\n<td>\n<p>E <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>and <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>X <\/p>\n<\/td>\n<td>\n<p>X <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>02H 30H 31H 34H 45H 41H 42H 43H 44H 45H 46H 47H 42H 38H 03H <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"3\">\n<p>se <\/p>\n<\/td>\n<td>\n<p>S <\/p>\n<\/td>\n<td rowspan=\"3\">\n<p>0 1 4 E A B C D E F G B 8 <\/p>\n<\/td>\n<td>\n<p>E <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>T <\/p>\n<\/td>\n<td>\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>X <\/p>\n<\/td>\n<td>\n<p>X <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>02H 30H 31H 34H 45H 41H 42H 43H 44H 45H 46H 47H 42H 38H 03H <\/p>\n<\/td>\n<\/tr>\n<tr><\/tr>\n<\/table>\n<\/div>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-101\/fbs-hw-en-101-017.png\" \/><\/p>\n<p>\u25cfCommand code 53\uff08Read the detailed system status of PLC\uff09<\/p>\n<p>Format <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"2\">\n<p>MASTER <\/p>\n<\/td>\n<td>\n<p>S <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>0 1 5 3 C B <\/p>\n<\/td>\n<td>\n<p>E <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>Command <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>X <\/p>\n<\/td>\n<td>\n<p>X <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p> H L H L H L <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"2\">\n<p>PLC <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>S <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>STATUS <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>STATUS <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>STATUS <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>STATUS <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>STATUS <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>STATUS <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>\u2027\u2027\u2027\u2027\u2027\u2027\u2027\u2027<\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>STATUS <br \/>64 <\/p>\n<\/td>\n<td>\n<p>E <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>0 1 5 3 <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"3\">\n<p>response <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>1 <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>2 <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>3 <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>4 <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>5 <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>6 <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"2\">\n<p>X <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>X <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"2\">\n<p> H L H L <\/p>\n<\/td>\n<td colspan=\"6\">\n<p>H L H L H L H L H L H L <\/p>\n<\/td>\n<td colspan=\"2\">\n<p> H L H L <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>B0\uff1aRUN\/STOP <br \/>B1\uff1aBattery Low\/Normal <br \/>B2\uff1aLadder checksum error\/Normal <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"3\">\n<p>STATUS 1 <\/p>\n<\/td>\n<td>\n<p>B3\uff1aUse MEMORY PACK\/Not use <\/p>\n<\/td>\n<td rowspan=\"3\">\n<p>STATUS 15 <\/p>\n<\/td>\n<td colspan=\"2\" rowspan=\"3\">\n<p>M Relay Hi-Byte <\/p>\n<\/td>\n<td rowspan=\"34\">\n<p>\uff5e<br \/>\uff5e<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>B4\uff1aWDT Time out\/Normal <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>B5\uff1aID setting\/Not set ID <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"5\">\n<p>STATUS 2 <\/p>\n<\/td>\n<td>\n<p>B6\uff1aUrgent stop\/Normal <\/p>\n<\/td>\n<td>\n<p>STATUS 16 <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>M Relay Lo-Byte <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>B7\uff1a(reserve for future use) <\/p>\n<\/td>\n<td>\n<p>STATUS 17 <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>S Relay Hi-Byte <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Types of Main unit <\/p>\n<\/td>\n<td>\n<p>STATUS 18 <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>S Relay Lo-Byte <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>00H:MA <\/p>\n<\/td>\n<td>\n<p>STATUS 19 <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>L Relay Hi-Byte <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>01H:MC <\/p>\n<\/td>\n<td>\n<p>STATUS 20 <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>L Relay Lo-Byte <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"6\">\n<p>STATUS 3 <\/p>\n<\/td>\n<td>\n<p>Other values: retain<\/p>\n<\/td>\n<td>\n<p>STATUS 21 <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>R Register Hi-Byte <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>I\/O points of main unit <\/p>\n<\/td>\n<td>\n<p>STATUS 22 <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>R Register Lo-Byte <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>00H:10 points <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>STATUS 23 <\/p>\n<\/td>\n<td colspan=\"2\" rowspan=\"2\">\n<p>D Register Hi-Byte <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>01H:14 points <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>STATUS 24 <\/p>\n<\/td>\n<td colspan=\"2\" rowspan=\"2\">\n<p>D Register Lo-Byte <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>02H:20 points <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"7\">\n<p>STATUS 4 <\/p>\n<\/td>\n<td>\n<p>\u02d9 <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>STATUS 25 <\/p>\n<\/td>\n<td colspan=\"2\" rowspan=\"2\">\n<p>Timer Hi-byte <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>\u02d9 <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>STATUS 26 <\/p>\n<\/td>\n<td colspan=\"2\" rowspan=\"2\">\n<p>Timer Lo-byte <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>OS Version of PLC <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>STATUS 27 <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>Counter Hi-Byte <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>40H\uff1aV4.0X <\/p>\n<\/td>\n<td>\n<p>STATUS 28 <\/p>\n<\/td>\n<td colspan=\"2\" rowspan=\"2\">\n<p>Counter Lo-Byte <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>41H\uff1aV4.1X <\/p>\n<\/td>\n<td>\n<p>STATUS 29 <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"3\">\n<p>STATUS 5 <\/p>\n<\/td>\n<td>\n<p>\u2024<\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>\u2024<\/p>\n<\/td>\n<td colspan=\"2\" rowspan=\"2\">\n<p>\u2024<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>\u2024<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Ladder Size Hi-Byte <\/p>\n<\/td>\n<td>\n<p>\u2024<\/p>\n<\/td>\n<td colspan=\"2\">\n<p>\u2024<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>STATUS 6 <\/p>\n<\/td>\n<td>\n<p>Ladder Size Lo-Byte <\/p>\n<\/td>\n<td>\n<p>\u2024<\/p>\n<\/td>\n<td colspan=\"2\">\n<p>\u2024<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>STATUS 7 <\/p>\n<\/td>\n<td>\n<p>Discrete input Hi-Byte <\/p>\n<\/td>\n<td>\n<p>\u2024<\/p>\n<\/td>\n<td>\n<p>\uff5e<br \/>\uff5e<\/p>\n<\/td>\n<td>\n<p>\u2024<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>STATUS 8 <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>Discrete input Lo-Byte <\/p>\n<\/td>\n<td>\n<p>\u2024<\/p>\n<\/td>\n<td colspan=\"2\">\n<p>\u2024<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>\u2024<\/p>\n<\/td>\n<td colspan=\"2\" rowspan=\"7\">\n<p>\u2024<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>STATUS 9 <\/p>\n<\/td>\n<td>\n<p>Discrete output Hi-Byte <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>STATUS 10 <\/p>\n<\/td>\n<td>\n<p>Discrete output Lo-Byte <\/p>\n<\/td>\n<td rowspan=\"5\">\n<p>STATUS 64 <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>STATUS 11 <\/p>\n<\/td>\n<td>\n<p>Analog input Hi-Byte <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>STATUS 12 <\/p>\n<\/td>\n<td>\n<p>Analog input Lo-Byte <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>STATUS 13 <\/p>\n<\/td>\n<td>\n<p>Analog output Hi-Byte <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>STATUS 14 <\/p>\n<\/td>\n<td>\n<p>Analog output Lo-Byte <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-101\/fbs-hw-en-101-018.png\" \/><\/p>\n<p>\u25cfCommand code 53\uff08Read the detailed system status of PLC\uff09<\/p>\n<p>Ex. \tIf the type of PLC is FBs-20MC, OS version is 4.0x, program capacity is 32K words, without MEMORY \tPACK, and ID setting, all the status are normal and in RUN model, then the result of reading the system \tstatus is as following\uff1a<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"5\">\n<p>MASTER <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>S <\/p>\n<\/td>\n<td rowspan=\"8\">\n<p>0 1 5 3 C B <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>E <\/p>\n<\/td>\n<td rowspan=\"10\">\n<p>S <\/p>\n<\/td>\n<td colspan=\"2\" rowspan=\"6\">\n<p>MC <\/p>\n<\/td>\n<td>\n<p>20 <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>OS <\/p>\n<\/td>\n<td colspan=\"2\" rowspan=\"3\">\n<p>Ladder  Size <\/p>\n<\/td>\n<td colspan=\"3\" rowspan=\"6\">\n<p>DI=256 <\/p>\n<\/td>\n<td rowspan=\"13\">\n<p>c<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>point <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"4\">\n<p>V4.0<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"3\">\n<p>CPU <\/p>\n<\/td>\n<td colspan=\"2\" rowspan=\"3\">\n<p>=32KW <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"3\">\n<p>Command <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>X <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>X <\/p>\n<\/td>\n<td>\n<p>STATUS <\/p>\n<\/td>\n<td>\n<p>STATUS <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>STATUS <\/p>\n<\/td>\n<td>\n<p>STATUS <\/p>\n<\/td>\n<td>\n<p>STATUS <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>STATUS <\/p>\n<\/td>\n<td>\n<p>STATUS <\/p>\n<\/td>\n<td>\n<p>STATUS <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>1 <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>2 <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>4 <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>5 <\/p>\n<\/td>\n<td colspan=\"2\" rowspan=\"2\">\n<p>6 <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>7<\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>8 <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"4\">\n<p> 02H 30H 31H 35H 33H 43H 42H 03H <\/p>\n<\/td>\n<td>\n<p>3 <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"4\" rowspan=\"2\">\n<p>PLC <\/p>\n<\/td>\n<td colspan=\"9\" rowspan=\"4\">\n<p>0 1 5 3 0 2 1 0 1 0 2 4 0 8 0 0 0 0 1 0 0 <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>T <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"4\" rowspan=\"2\">\n<p>response <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>X <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>02H 30H 31H 35H 33H 30H 32H 31H 30H 31H 30H 32H 33H 31H 33H 33H 38H 30H 30H 31H 30H 30H <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"4\">\n<p>c<\/p>\n<\/td>\n<td colspan=\"2\" rowspan=\"2\">\n<p>DO=256 <\/p>\n<\/td>\n<td colspan=\"2\" rowspan=\"2\">\n<p>AI=64 <\/p>\n<\/td>\n<td colspan=\"2\" rowspan=\"2\">\n<p>AO=64 <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>MRelay <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>S Relay <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>L Relay <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>R Register <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>d<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"2\">\n<p>= 2002 <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>= 1000 <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>= 0 <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>= 8072 <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>STATUS <\/p>\n<\/td>\n<td>\n<p>STATUS <\/p>\n<\/td>\n<td>\n<p>STATUS <\/p>\n<\/td>\n<td>\n<p>STATUS <\/p>\n<\/td>\n<td>\n<p>STATUS <\/p>\n<\/td>\n<td>\n<p>STATUS <\/p>\n<\/td>\n<td>\n<p>STATUS <\/p>\n<\/td>\n<td>\n<p>STATUS <\/p>\n<\/td>\n<td>\n<p>STATUS <\/p>\n<\/td>\n<td>\n<p>STATUS <\/p>\n<\/td>\n<td>\n<p>STATUS <\/p>\n<\/td>\n<td>\n<p>STATUS <\/p>\n<\/td>\n<td>\n<p>STATUS <\/p>\n<\/td>\n<td>\n<p>STATUS <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>9 <\/p>\n<\/td>\n<td>\n<p>10 <\/p>\n<\/td>\n<td>\n<p>11 <\/p>\n<\/td>\n<td>\n<p>12 <\/p>\n<\/td>\n<td>\n<p>13 <\/p>\n<\/td>\n<td>\n<p>14 <\/p>\n<\/td>\n<td>\n<p>15 <\/p>\n<\/td>\n<td>\n<p>16 <\/p>\n<\/td>\n<td>\n<p>17 <\/p>\n<\/td>\n<td>\n<p>18 <\/p>\n<\/td>\n<td>\n<p>19 <\/p>\n<\/td>\n<td>\n<p>20 <\/p>\n<\/td>\n<td>\n<p>21 <\/p>\n<\/td>\n<td>\n<p>22 <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p> 0 1 0 0 0 0 6 4 0 0 6 4 0 7 D 2 0 3 E 8 0 0 0 0 1 F 8 8 <\/p>\n<p> 30H 31H 30H 30H 30H 30H 36H 34H 30H 30H 36H 34H 30H 37H 44H 32H 30H 33H 45H 38H 30H 30H 30H 30H 31H 46H 38H 38H <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td colspan=\"2\">\n<p>D Register <\/p>\n<\/td>\n<td colspan=\"2\" rowspan=\"2\">\n<p>Timer=256 <\/p>\n<\/td>\n<td colspan=\"2\" rowspan=\"2\">\n<p>Counter=256 <\/p>\n<\/td>\n<td rowspan=\"3\">\n<p>STATUS <\/p>\n<\/td>\n<td rowspan=\"3\">\n<p>STATUS <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>reserve <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"2\">\n<p>= 4096 <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>STATUS <\/p>\n<\/td>\n<td>\n<p>STATUS <\/p>\n<\/td>\n<td>\n<p>STATUS <\/p>\n<\/td>\n<td>\n<p>STATUS <\/p>\n<\/td>\n<td>\n<p>STATUS <\/p>\n<\/td>\n<td>\n<p>STATUS <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>23 <\/p>\n<\/td>\n<td>\n<p>24 <\/p>\n<\/td>\n<td>\n<p>25 <\/p>\n<\/td>\n<td>\n<p>26 <\/p>\n<\/td>\n<td>\n<p>27 <\/p>\n<\/td>\n<td>\n<p>28 <\/p>\n<\/td>\n<td>\n<p>29 <\/p>\n<\/td>\n<td>\n<p>30 <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>d<\/p>\n<p>E  1 0 0 0 0 1 0 0 0 1 0 0 0 0 0 0 \u2027\u2027\u2027\u2027 0 0 0 0 \t\tT X <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p> 30H 43H 30H 30H 30H 31H 30H 30H 30H 31H 30H 30H 30H 30H 30H 30H <\/p>\n<\/td>\n<td>\n<p>30H 30H 30H 30H <\/p>\n<\/td>\n<td>\n<p>03H <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n","protected":false},"excerpt":{"rendered":"<p>This Protocol is each communication port of FATEK PLC t [&hellip;]<\/p>\n","protected":false},"author":1,"featured_media":0,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[33],"tags":[],"class_list":["post-3378","post","type-post","status-publish","format-standard","hentry","category-en-fbs-hw"],"_links":{"self":[{"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/posts\/3378","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/comments?post=3378"}],"version-history":[{"count":0,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/posts\/3378\/revisions"}],"wp:attachment":[{"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/media?parent=3378"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/categories?post=3378"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/tags?post=3378"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}