{"id":3425,"date":"2026-11-17T21:35:01","date_gmt":"2026-11-17T13:35:01","guid":{"rendered":"https:\/\/resource.fatek.com\/index.php\/2026\/11\/17\/fbs-hw-en-020\/"},"modified":"2026-11-17T21:35:01","modified_gmt":"2026-11-17T13:35:01","slug":"fbs-hw-en-020","status":"publish","type":"post","link":"https:\/\/resource.fatek.com\/index.php\/2026\/11\/17\/fbs-hw-en-020\/","title":{"rendered":"Chapter 20 Temperature Measurement of FBs-PLC and PID Control"},"content":{"rendered":"<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-020\/fbs-hw-en-020-001.png\" \/><\/p>\n<p>FBs-PLC provides two kinds of temperature modules to meet the great temperature measurement applications. One kind of these modules are directly interfacing with the thermocouple, and the others are interfacing with the RTD sensor.  The modules FBs-2TC\/FBs-6TC\/FBs-16TC support 2\/6\/16 temperature channels correspondingly to connect the J,K,T,E,N,B,R,S type of thermocouple. The modules FBs-6RTD\/FBs-16RTD support 6\/16 temperature channels correspondingly to connect the PT-100,PT-1000 type of RTD sensor.  The total temperature inputs can be expanded up to 32 channels at the most. <\/p>\n<p>By the time domain multiplexing design method, each temperature module occupies 1 point of register input and 8 points of digital output for I\/O addressing.  The update rate for temperature reading value can be set as normal (Update time is 4 second, the resolution is 0.1\u00b0) or fast (Update time is 2 second, the resolution is 1\u00b0). <\/p>\n<p> The WinProladder provides the very user friendly table editing operation interface to configure the temperature measurement, for example, selecting the temperature module, type of sensor, and assign the registers to store the reading values\u2026  As to the temperature control, it has the convenient instruction FUN86(TPCTL) to perform the PID operation to control the heating or cooling of the temperature process. <\/p>\n<p>20.1Specifications of Temperature Measuring Modules of FBs-PLC <\/p>\n<h4> 20.1.1 Thermocouple Input of FBs-PLC <\/h4>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"9\">\n<p>Specifications<\/p>\n<p>Items <\/p>\n<p>Number of input points <\/p>\n<p>Thermocouple type and temperature <br \/>measurement range <\/p>\n<p>I\/O Points Occupied <br \/>Software Filter <br \/>Average Samples <br \/>Compensation <br \/>Resolution <br \/>Conversion Time <br \/>Overall Precision <br \/>Isolation <br \/>Internal Power <br \/>Consumption <br \/>Power Input <br \/>Indicator(s) <br \/>Operating Temperature Storage Temperature Dimensions <\/p>\n<\/td>\n<td colspan=\"3\">\n<p>Module <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>FBs-2TC <\/p>\n<\/td>\n<td>\n<p>FBs-6TC <\/p>\n<\/td>\n<td>\n<p>FBs-16TC <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>2 Points <\/p>\n<\/td>\n<td>\n<p>6 Points <\/p>\n<\/td>\n<td>\n<p>16 Points <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"3\">\n<p> J(\u2212200\uff5e900\u00b0C)          E(\u2212190\uff5e1000\u00b0C)  K(\u2212190\uff5e1300\u00b0C)         T(\u2212190\uff5e380\u00b0C)  R(0\uff5e1800\u00b0C)            B(350\uff5e1800\u00b0C)  S(0\uff5e1700\u00b0C)            N(\u2212200\uff5e1000\u00b0C) <\/p>\n<p> 1 IR(Input Register)\u30018 DO(Discrete Output) <\/p>\n<p>Moving Average <\/p>\n<p>NO 1\u30012\u30014\u30018 Configurable <\/p>\n<p>Built-in cold junction compensation <\/p>\n<p>0.1\u00b0C <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>1 or 2 Sec. <\/p>\n<\/td>\n<td>\n<p>2 or 4 Sec. <\/p>\n<\/td>\n<td>\n<p>3 or 6 Sec. <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"3\">\n<p>\t\u00b1(1%+1\u00b0C) <br \/>Transformer(Power) and photocouple(Signal) isolation (per-channel isolation)<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"2\">\n<p>5V\uff0c32mA <\/p>\n<\/td>\n<td>\n<p>5V\uff0c35mA <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"3\">\n<p>24VDC-15%\/+20%\u30012VA max <br \/>\t\t5VPWR LED <br \/>\t\t\t0\uff5e60 \u00b0C <br \/>-20\uff5e80\u00b0C <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"2\">\n<p>40(W)x90(H)x80(D) mm <\/p>\n<\/td>\n<td>\n<p>90(W) x90(H) x80(D) mm<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-020\/fbs-hw-en-020-002.png\" \/><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-020\/fbs-hw-en-020-003.png\" \/><\/p>\n<h4> 20.1.2 RTD Input of FBs-PLC <\/h4>\n<p>Specifications Module <\/p>\n<p>Items \tFBs-6RTD \tFBs-16RTD <\/p>\n<p>Number of input points 6 Points \t16 Points<\/p>\n<p>RTD type and  3-wire RTD sensor JIS(\u03b1=0.00392) or DIN(\u03b1=0.00385) <\/p>\n<p>temperature \t Pt-100(\u2212200\uff5e850\u00b0C) <\/p>\n<p>measurement range I\/O Points Occupied <\/p>\n<p>\t Pt-1000(\u2212200\uff5e600\u00b0C) <br \/> 1 IR(Input Register)\u30018 DO(Discrete Output) <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>Software Filter <\/p>\n<\/td>\n<td colspan=\"3\">\n<p>Moving Average <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Average Samples <\/p>\n<\/td>\n<td colspan=\"3\">\n<p>NO 1\u30012\u30014\u30018 Configurable <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Resolution <\/p>\n<\/td>\n<td colspan=\"3\">\n<p>0.1\u00b0C <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Conversion Time <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>1 or 2 Sec. <\/p>\n<\/td>\n<td>\n<p>2 or 4 Sec. <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Overall Precision <\/p>\n<\/td>\n<td colspan=\"3\">\n<p>\u00b11% <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Isolation <\/p>\n<\/td>\n<td colspan=\"3\">\n<p>Transformer(Power) and photocouple(Signal) isolation (per-channel isolation)<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Internal Power <\/p>\n<\/td>\n<td colspan=\"2\" rowspan=\"2\">\n<p>5V\uff0c35mA <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>5V\uff0c35mA <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Consumption <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Power Input <\/p>\n<\/td>\n<td colspan=\"3\">\n<p>24VDC-15%\/+20%\u30012VA max <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Indicator(s) <\/p>\n<\/td>\n<td colspan=\"3\">\n<p>5VPWR LED <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Operating Temperature <\/p>\n<\/td>\n<td colspan=\"3\">\n<p>0\uff5e60 \u00b0C <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Storage Temperature <\/p>\n<\/td>\n<td colspan=\"3\">\n<p> -20\uff5e80\u00b0C <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Dimensions <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>40(W)x90(H)x80(D) mm <\/p>\n<\/td>\n<td>\n<p>90(W) x90(H) x80(D)mm <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"4\">\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td><\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>20.1.3 NTC Temperature Input Module <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"2\">\n<p>Item <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>Module <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Specifications <\/p>\n<\/td>\n<td colspan=\"3\">\n<p>FBs-6NTC <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Input point <\/p>\n<\/td>\n<td colspan=\"3\">\n<p>6 points <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Sensor Type <\/p>\n<\/td>\n<td colspan=\"3\">\n<p>2K, 5K, 10K, 20K\u2126(@25\u2103)NTC sensor <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>I\/O Address Occupied <\/p>\n<\/td>\n<td colspan=\"3\">\n<p>1 IR (Input Register), 8 DO (Discrete Output) <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Software Filter <\/p>\n<\/td>\n<td colspan=\"3\">\n<p>Moving average <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Average Samples <\/p>\n<\/td>\n<td colspan=\"3\">\n<p>1\u30012\u30014\u30018\u300116 configurable <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Resolution <\/p>\n<\/td>\n<td colspan=\"3\">\n<p>0.1\u00b0C <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Conversion Time <\/p>\n<\/td>\n<td colspan=\"3\">\n<p>1 or 2 Sec. <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Accuracy <\/p>\n<\/td>\n<td colspan=\"3\">\n<p>\u00b11% <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Isolation <\/p>\n<\/td>\n<td colspan=\"3\">\n<p>Transformer(Power) and photo-coupler(Signal) <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Internal power consumption <\/p>\n<\/td>\n<td colspan=\"3\">\n<p>5V\uff0c35mA <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Supply power <\/p>\n<\/td>\n<td colspan=\"3\">\n<p>24VDC-15%\/+20%\u30012VA <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Indicator(s) <\/p>\n<\/td>\n<td colspan=\"3\">\n<p>5V PWR LED <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Operating Temperature <\/p>\n<\/td>\n<td colspan=\"3\">\n<p>0\uff5e60 \u00b0C <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Storage Temperature <\/p>\n<\/td>\n<td colspan=\"3\">\n<p>-20\uff5e80\u00b0C <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Dimension <\/p>\n<\/td>\n<td colspan=\"3\">\n<p>90(W) x90(H) x80(D)mm <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-020\/fbs-hw-en-020-004.png\" \/><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-020\/fbs-hw-en-020-005.png\" \/><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-020\/fbs-hw-en-020-006.png\" \/><\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p> 20.2 The Procedure of Using FBs Temperature Module <\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<\/table>\n<\/div>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p> 20.2.1 Temperature Measurement Procedure <\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>Start <\/p>\n<p>Connect Modules to the expansion interface on PLC in <\/p>\n<p>series and connect an external 24VDC source and temperature measure input wires.<\/p>\n<p>Executing the WinProladder and configure the <br \/>configuration table address\u3001Temperature register address and working register in \u201cTemp. configuration\u201d windows then you can read temperature value from register directly.<\/p>\n<p>End <\/p>\n<p>&#8212;&#8212;-Please refer to section 20.6 for setting and wiring. <\/p>\n<p>&#8212;&#8212;-Please refer to section 20.3<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p> 20.2.2 Closed Loop PID Temperature Control <\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>Start <\/p>\n<p>Connect Modules to the expansion interface on PLC in <\/p>\n<p>series and connect an external 24VDC source and temperature measure input wires.<\/p>\n<p>Using convenient instruction of PID temperature <\/p>\n<p>&#8212;&#8212;-Please refer to section 20.6 for setting and wiring. <\/p>\n<p>control(FUN86) combine to  \u201cTemp. configuration\u201d Table <br \/>to get the current value of temperature and let it be as so <\/p>\n<p>called Process Variable (PV); after the calculation of <br \/>software PID expression, it will respond the error with an output signal according to the setting of Set Point (SP),the error&#8217;s integral and the rate of change of the process variable. Through the closed loop operation, the steady state of the process may be expected. <\/p>\n<p>End <\/p>\n<p>&#8212;&#8212;-Please refer to FUN86 explanation of instructions and program example.<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p> 20.3 The Procedures to Configure the Temperature Measurement <\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>Click the item \u201cI\/O Configuration\u201d which in Project Windows <strong>: <\/strong><\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td colspan=\"3\">\n<p> Project name <\/p>\n<\/td>\n<td colspan=\"4\" rowspan=\"2\"><\/td>\n<\/tr>\n<tr>\n<td rowspan=\"5\"><\/td>\n<td><\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td><\/td>\n<td>\n<p> S<\/p>\n<\/td>\n<td>\n<p>stem Co<\/p>\n<\/td>\n<td>\n<p>nfigurat<\/p>\n<\/td>\n<td>\n<p>on <\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td><\/td>\n<td><\/td>\n<td><\/td>\n<td><\/td>\n<td><\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td><\/td>\n<td><\/td>\n<td><\/td>\n<td><\/td>\n<td><\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td><\/td>\n<td><\/td>\n<td><\/td>\n<td><\/td>\n<td><\/td>\n<td><\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p> I\/O Configuration  \u00c6 Select  \u201cTemp. Configuration\u201d <\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-020\/fbs-hw-en-020-007.jpg\" \/><\/p>\n<p>1.\ufe5dStarting Address of Configuration Table\ufe5e<strong>: <\/strong>Assign the starting of registers to store the temperature configuration table, \tthere will allow the following inputs. <\/p>\n<p> a. Space (Without temperature configuration table)<br \/> b. Rxxxx or Dxxxxx<br \/> The configuration table will occupy 4+N of registers, where N is the number of modules.<\/p>\n<p> As shown the sample above, R5000~R5005 stores the table<\/p>\n<p>2.\ufe5d.Starting Address of Temp. Register\ufe5e<strong>: <\/strong>Assign the starting of registers to store the current temperature reading values, there will allow the following inputs, Rxxxx or Dxxxxx ; 1 channel of temperature occupies 1 register as shown the sample above, R0~R31 stores the reading values. The resolution of reading value is 0.1\u00b0.<\/p>\n<p>For example. R0=1234, it means 123.4\u00b0<\/p>\n<p>3.\ufe5dStarting Address of Working Register\ufe5e<strong>: <\/strong>Assign the starting of registers to reserve the working registers, there will allow the following inputs Rxxxx or Dxxxxx <br \/>As shown the sample above, D0~D11 are the working registers<\/p>\n<p>\u3010Temperature module installation information and setup\u3011<\/p>\n<p>4.\ufe5dModule #1 ~ # 8\ufe5e<strong>: <\/strong>Display the name of the installed temperature module and the analog starting address of it&#8217;s own, <\/p>\n<p>there are the following modules\u3002<\/p>\n<p>\u25cb16TC (6 channels of thermocouple input)<\/p>\n<p>\u25cb26RTD (6 channels of RTD input)<\/p>\n<p>\u25cb316TC (16 channels of thermocouple input)<\/p>\n<p>\u25cb416RTD (16 channels of RTD input) <\/p>\n<p>\u25cb52TC (2 channels of thermocouple input) <\/p>\n<p>\u24656NTC (6 channels NTC temperature input) <\/p>\n<p>\u203bThe Sensor Type field is used to assign and display the sensor type, the detail Sensor Type please refer to section 20.1 <\/p>\n<p>5.\ufe5dUnit of Temperature\ufe5e<strong>: <\/strong>Assign the unit of temperature, there have the following selections <\/p>\n<p>\u25cb1Celsius <\/p>\n<p>\u25cb2Fahrenheit <\/p>\n<p>6.\ufe5dTimes of Average\ufe5e<strong>: <\/strong>Assign the times of average for temperature measurement, there have the following selections, <\/p>\n<p>No \/ 2 \/ 4 \/ 8. <\/p>\n<p>7.\ufe5dScan Rate\ufe5e<strong>: <\/strong>Assign the update rate of temperature reading value, there will have the following selections <strong>:<\/strong> Normal <\/p>\n<p>(Update time is 4 second, the measurement resolution is 0.1\u00b0), Fast (Update time is 2 second, the <\/p>\n<p>measurement resolution is 1\u00b0). The resolution of reading value is always 0.1\u00b0. <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p> 20.3.1 The Internal Format of Temperature Configuration Table <\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p> This introduction is for trouble shooting or HMI or SCADA User, because they may modify through registers. <\/p>\n<p>Winproladder\u2019s User can ignore this introduction. When you configure temperature configuration table with Winproladder, <\/p>\n<p>these value of registers will be finished. When SR+0 = A556h, it means valid temperature configuration table. But if SR+0 <\/p>\n<p>= other values, it means invalid temperature configuration table. <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p> Address <\/p>\n<\/td>\n<td>\n<p> High Byte <\/p>\n<\/td>\n<td>\n<p> Low Byte <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p> SR + 0 <\/p>\n<\/td>\n<td>\n<p> A5H <\/p>\n<\/td>\n<td>\n<p> 56H <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p> SR + 1 <\/p>\n<\/td>\n<td colspan=\"2\">\n<p> Quantity of temperature modules (1~8) <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p> SR + 2 <\/p>\n<\/td>\n<td colspan=\"2\">\n<p> Starting address of reading values <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p> SR + 3 <\/p>\n<\/td>\n<td colspan=\"2\">\n<p> Starting address of working registers <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p> SR + 4 <\/p>\n<\/td>\n<td>\n<p> Type of sensor (#1) <\/p>\n<\/td>\n<td>\n<p> Module name (#1) <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p> SR + 5 <\/p>\n<\/td>\n<td>\n<p> Type of sensor (#2) <\/p>\n<\/td>\n<td>\n<p> Module name (#2) <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p> SR + 6 <\/p>\n<\/td>\n<td>\n<p> Type of sensor (#3) <\/p>\n<\/td>\n<td>\n<p> Module name (#3) <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p> SR + 7 <\/p>\n<\/td>\n<td>\n<p> Type of sensor (#4) <\/p>\n<\/td>\n<td>\n<p> Module name (#4) <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p> SR + 8 <\/p>\n<\/td>\n<td>\n<p> Type of sensor (#5) <\/p>\n<\/td>\n<td>\n<p> Module name (#5) <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p> SR + 9 <\/p>\n<\/td>\n<td>\n<p> Type of sensor (#6) <\/p>\n<\/td>\n<td>\n<p> Module name (#6) <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td><\/td>\n<td><\/td>\n<td><\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>\u203b The temperature configuration table occupies (4\uff0bN) registers in total ; where N is the quantity of modules. <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p> 20.3.2 The Internal Format of Working Registers <\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>Supposing the starting address is WR<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p> Address<\/p>\n<\/td>\n<td>\n<p> High Byte<\/p>\n<\/td>\n<td>\n<p> Low Byte <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p> WR+0 <\/p>\n<\/td>\n<td>\n<p> Execute Code <\/p>\n<\/td>\n<td>\n<p> XXXXH <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p> WR+1 <\/p>\n<\/td>\n<td colspan=\"2\">\n<p> Sensor abnormal indicator (Sensor 0 \uff5e Sensor 15) <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p> WR+2 <\/p>\n<\/td>\n<td colspan=\"2\">\n<p> Sensor abnormal indicator (Sensor 16 \uff5e Sensor 31) <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p> WR+3 <\/p>\n<\/td>\n<td>\n<p> Total amount of TP channel <\/p>\n<\/td>\n<td>\n<p> Qty of Temperature Module <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p> WR+4 <\/p>\n<\/td>\n<td>\n<p> Type of sensor of Module #1 <\/p>\n<\/td>\n<td>\n<p> D.O. of TP Module #1 <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p> WR+5 <\/p>\n<\/td>\n<td>\n<p> Channel No. of Module #1 <\/p>\n<\/td>\n<td>\n<p> A.I. of TP Module #1 <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p> WR+6 <\/p>\n<\/td>\n<td colspan=\"2\">\n<p> Reading start of Temperature Module #1 <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p> WR+7 <\/p>\n<\/td>\n<td colspan=\"2\">\n<p> Current channel of Temperature Module #1 <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td><\/td>\n<td colspan=\"2\"><\/td>\n<\/tr>\n<tr>\n<td>\n<p> WR+(N\u00d74)+0 <\/p>\n<\/td>\n<td>\n<p> Sensor of Module #N <\/p>\n<\/td>\n<td>\n<p> D.O. of TP Module #N <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p> WR+(N\u00d74)+1 <\/p>\n<\/td>\n<td>\n<p> Channel No. of Module #N <\/p>\n<\/td>\n<td>\n<p> A.I. of TP Module #N <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p> WR+(N\u00d74)+2 <\/p>\n<\/td>\n<td colspan=\"2\">\n<p> Reading start of Temperature Module #N <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p> WR+(N\u00d74)+3 <\/p>\n<\/td>\n<td colspan=\"2\">\n<p> Current channel of Temperature Module #N <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>Notes <strong>: <\/strong><br \/>1. Lower byte of WR+0 <strong>:<\/strong> Tells the mismatch between the configuration table &amp; installed temperature board\t b0=1\uff0cmeans module #1<br \/>\t\t\uff0e<\/p>\n<p>\uff0e<\/p>\n<p>\uff0e<\/p>\n<p>\t\tb7=1\uff0cmeans module #8 <br \/>\t 2. Upper byte of WR+0 <strong>:<\/strong> Execute Code <br \/>\t\t\t = 00H,Idle <br \/>\t\t\t\t = FFH,TP channel \uff1e 32, w\/o temperature measurement \t\t\t\t = FEH, lower byte of WR+3 = 0 or \uff1e 8, same as above <br \/>\t\t\t\t = 56H,already read all TP channels, measurement in progress \u203b  The working table occupies (N\u00d74)\uff0b4 registers in total ; where N is the quantity of modules <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p> 20.3.3 Description of Related Special Registers for Temperature Measurement <\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<\/table>\n<\/div>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>sensor&#8217;s installation status <\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>z R4010 : Each bit of R4010 to tell the status of the sensor&#8217;s installation. <\/p>\n<p>Bit0=1 means that 1st point of temperature sensor is installed. Bit1=1 means that 2nd point of temperature sensor is installed. <\/p>\n<p>\u2027<br \/>\u2027<br \/>Bit15=1 means that 16th point of temperature sensor is installed. <\/p>\n<p>(The default of R4010 is FFFFH) <\/p>\n<p>z R4011 : Each bit of R4011 to tell the status of the sensor&#8217;s installation. Bit0=1 means that 17th point of temperature sensor is installed. Bit1=1 means that 18th point of temperature sensor is installed. <\/p>\n<p>\u2027<\/p>\n<p>\u2027<br \/>Bit15=1 means that 32th point of temperature sensor is installed. <\/p>\n<p>\t(The default of R4011 is FFFFH) <br \/>z When the temperature sensor is installed (the corresponding bit of R4010 or R4011 must be 1), the system \twill perform the line broken detection to the sensor. If there is line broken happened to the sensor, there \twill have the warning and the line broken value will be displayed. <\/p>\n<p>z When the temperature sensor is not installed (the corresponding bit of R4010 or R4011 must be 0), the system won\u2019t perform the line broken detection to the sensor and there will not have the warning; the temperature value will be displayed as 0. <\/p>\n<p>z Depends on the sensor&#8217;s installation, the ladder program may control the corresponding bit of R4010 and \tR4011 to perform or not to perform the line broken detection. <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p> 20.4 I\/O Addressing of Temperature Module <\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>By the time domain multiplexing design method, each temperature module occupies 1 point of input register and 8 points of digital output for I\/O addressing. For correct I\/O access, the I\/O addressing of extension modules following the temperature module must be added the I\/O quantity which the corresponding module should have. The WinProladder provides the easy and convenient way to calculate the I\/O address for the extension modules through the on-line &quot;I\/O Numbering&quot; operation.<\/p>\n<h3> 20.5 Temperature Modules Hardware Description <\/h3>\n<p> FBs-2TC, FBs-6TC, FBs-16TC, FBs-6RTD, FBs-16RTD, and FBs-6NTC Temperature modules contains 3 PCBs overlapping one another. The lowest one is the power supply unit (isolated power supply). The middle one is the I\/O board (connectors are on this layer). The upper one is the control board (control\/expansion I\/O connections) as described below.<strong>:<\/strong><\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p> 20.5.1 FBs-2TC\u30016TC\u300116TC Outlook of Top View <\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-020\/fbs-hw-en-020-008.png\" \/><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-020\/fbs-hw-en-020-009.png\" \/><\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"3\">\n<p>2<\/p>\n<\/td>\n<td>\n<p>1<\/p>\n<\/td>\n<td rowspan=\"3\">\n<p>6<\/p>\n<\/td>\n<td>\n<p>7<\/p>\n<\/td>\n<td>\n<p>8<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p><strong>+ 24V IN &#8211;<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>T0+<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>T1+<\/strong><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>T0-<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>T1-<\/strong><\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p> 2TC <\/p>\n<p>4<\/p>\n<p><strong>POW<\/strong><\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>3<\/p>\n<\/td>\n<td>\n<p><strong>FBs-2TC<\/strong><\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>5<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"3\">\n<p>2<\/p>\n<\/td>\n<td>\n<p>1<\/p>\n<\/td>\n<td rowspan=\"3\">\n<p>6<\/p>\n<\/td>\n<td>\n<p>7<\/p>\n<\/td>\n<td>\n<p>8<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p><strong>+ 24V IN &#8211;<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>T0+<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>T1+<\/strong><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>T0-<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>T1-<\/strong><\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p> 6TC <\/p>\n<p>4<\/p>\n<p><strong>POW<\/strong><\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"3\">\n<p>3<\/p>\n<\/td>\n<td rowspan=\"3\">\n<p><strong>T2+<\/strong><\/p>\n<\/td>\n<td rowspan=\"3\">\n<p><strong>T2-<\/strong><\/p>\n<\/td>\n<td rowspan=\"3\">\n<p><strong>T3+<\/strong><\/p>\n<\/td>\n<td rowspan=\"3\">\n<p><strong>T3-<\/strong><\/p>\n<\/td>\n<td rowspan=\"3\">\n<p><strong>T4+<\/strong><\/p>\n<\/td>\n<td colspan=\"2\">\n<p><strong>FBs-6TC<\/strong><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"2\">\n<p><strong>T5+<\/strong><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>T4-<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>T5-<\/strong><\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>5<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>9<\/p>\n<\/td>\n<td>\n<p>10<\/p>\n<\/td>\n<td>\n<p>11<\/p>\n<\/td>\n<td>\n<p>12<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-020\/fbs-hw-en-020-010.png\" \/><\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td><\/td>\n<td>\n<p> 16TC <\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td><\/td>\n<td><\/td>\n<td><\/td>\n<\/tr>\n<\/table>\n<\/div>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"3\">\n<p>2<\/p>\n<\/td>\n<td>\n<p>1<\/p>\n<\/td>\n<td>\n<p>6<\/p>\n<\/td>\n<td>\n<p>7<\/p>\n<\/td>\n<td rowspan=\"3\">\n<p><strong>T2+<\/strong><\/p>\n<\/td>\n<td>\n<p>8<\/p>\n<\/td>\n<td>\n<p>9<\/p>\n<\/td>\n<td>\n<p>10<\/p>\n<\/td>\n<td>\n<p>11<\/p>\n<\/td>\n<td>\n<p>12<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p><strong>+ 24V IN &#8211;<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>T0+<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>T1+<\/strong><\/p>\n<\/td>\n<td rowspan=\"2\">\n<p><strong>T2-<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>T3+<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>T4+<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>T5+<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>T6+<\/strong><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>T0-<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>T1-<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>T3-<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>T4-<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>T5-<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>T6-<\/strong><\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p><strong>PROGRAMMABLE<\/strong><\/p>\n<\/td>\n<td rowspan=\"2\">\n<p><strong>POW<\/strong><\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>4<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>CONTROLLER<\/strong><\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>3<\/p>\n<p><strong>FBs-16TC<\/strong><\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p><strong>T7+<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>T8+<\/strong><\/p>\n<\/td>\n<td rowspan=\"2\">\n<p><strong>T9+<\/strong><\/p>\n<\/td>\n<td colspan=\"7\" rowspan=\"2\">\n<p><strong>T10+ <\/strong>\t<strong>T11+ <\/strong>\t<strong>T12+ <\/strong>\t<strong>T13+ <\/strong>\t<strong>T14+ <\/strong>\t<strong>T15+<\/strong><\/p>\n<p><strong>T9-T10-<\/strong>\t<strong>T11-T12-T13-T14-<\/strong>\t<strong>T15-<\/strong><\/p>\n<\/td>\n<td rowspan=\"3\">\n<p>5<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>T7-<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>T8-<\/strong><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>13<\/p>\n<\/td>\n<td>\n<p>14<\/p>\n<\/td>\n<td colspan=\"2\">\n<p>15<\/p>\n<\/td>\n<td>\n<p>16<\/p>\n<\/td>\n<td>\n<p>17<\/p>\n<\/td>\n<td>\n<p>18<\/p>\n<\/td>\n<td>\n<p>19<\/p>\n<\/td>\n<td>\n<p>20<\/p>\n<\/td>\n<td>\n<p>21<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>\u25cb1External power input terminal\uff1aPower supply for analogue circuit of FBs-XXTC module, supply voltage is <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>\t24VDC\u00b120%<br \/>\u25cb2Protecting ground terminal\uff1aConnect to the shielding of signal cable.<\/p>\n<p>\u25cb3Expansion input cable\uff1aIt should be connected to the front expansion unit, or the expansion output of main unit.\u25cb4 Expansion output connector\uff1aProvides the connection for next expansion unit.<\/p>\n<p>\u25cb5Power indicator\uff1a Indicates whether the power supply at analogue circuit and external input power source are normal.<\/p>\n<p>\u25cb6 Input terminal for 1st  TC input\uff1aThe TC input of channel 0(T0+\u3001T0-)<br \/>\u25cb7 Input terminal for 2nd  TC input\uff1aThe TC input of channel 1(T1+\u3001T1-)<br \/>\u25cb8\uff5e\u25cb21Input terminal for (3rd\uff5e16th ) TC input\uff1aThe TC input of channel 2\uff5echannel 15(T2+\u3001T2-\uff5eT15+\u3001T15-)<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-020\/fbs-hw-en-020-011.png\" \/><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-020\/fbs-hw-en-020-012.png\" \/><\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p> 20.5.2  FBs-6RTD\u300116<\/p>\n<\/td>\n<td>\n<p>RTD Outlook of Top View <\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p> 6RTD <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"2\">\n<p>2<\/p>\n<\/td>\n<td>\n<p>1<\/p>\n<\/td>\n<td>\n<p>6<\/p>\n<\/td>\n<td>\n<p>7<\/p>\n<\/td>\n<td colspan=\"2\">\n<p>8<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>+ 24V IN &#8211;<\/strong><\/p>\n<\/td>\n<td>\n<p>\t<strong>P0+ COM<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>P0-<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>P1+<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>P1-<\/strong><\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>4<\/p>\n<p><strong>POW<\/strong><\/p>\n<p>3 <br \/><strong>FBs-6RTD<\/strong><\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p><strong>P2+<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>P2-<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>P3+<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>P3-<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>P4+<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>P4-<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>P5+<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>P5-<\/strong><\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>5<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>9<\/p>\n<\/td>\n<td>\n<p>1011<\/p>\n<\/td>\n<td>\n<p>12<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"3\">\n<p>2<\/p>\n<\/td>\n<td>\n<p>1<\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>6<\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>7<\/p>\n<\/td>\n<td colspan=\"2\">\n<p>8<\/p>\n<\/td>\n<td colspan=\"2\">\n<p>9<\/p>\n<\/td>\n<td colspan=\"2\">\n<p>10<\/p>\n<\/td>\n<td colspan=\"2\">\n<p>11<\/p>\n<\/td>\n<td colspan=\"2\">\n<p>12<\/p>\n<\/td>\n<td colspan=\"2\">\n<p>13<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p><strong>+ 24V IN &#8211;<\/strong><\/p>\n<\/td>\n<td rowspan=\"2\">\n<p><strong>P1+<\/strong><\/p>\n<\/td>\n<td rowspan=\"2\">\n<p><strong>P1-<\/strong><\/p>\n<\/td>\n<td rowspan=\"2\">\n<p><strong>P2+<\/strong><\/p>\n<\/td>\n<td rowspan=\"2\">\n<p><strong>P2-<\/strong><\/p>\n<\/td>\n<td rowspan=\"2\">\n<p><strong>P3+<\/strong><\/p>\n<\/td>\n<td rowspan=\"2\">\n<p><strong>P3-<\/strong><\/p>\n<\/td>\n<td rowspan=\"2\">\n<p><strong>P4+<\/strong><\/p>\n<\/td>\n<td rowspan=\"2\">\n<p><strong>P4-<\/strong><\/p>\n<\/td>\n<td rowspan=\"2\">\n<p><strong>P5+<\/strong><\/p>\n<\/td>\n<td rowspan=\"2\">\n<p><strong>P5-<\/strong><\/p>\n<\/td>\n<td rowspan=\"2\">\n<p><strong>P6+<\/strong><\/p>\n<\/td>\n<td rowspan=\"2\">\n<p><strong>P6-<\/strong><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>\t<strong>P0+ COM<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>P0-<\/strong><\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p> 16RTD <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p><strong>PROGRAMMABLE<\/strong><\/p>\n<\/td>\n<td rowspan=\"2\">\n<p><strong>POW<\/strong><\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>4<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>CONTROLLER<\/strong><\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>3 <br \/>\t<strong>FBs-16RTD<\/strong><\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p><strong>P7+<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>P7-<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>P8+<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>P8-<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>P9+<\/strong><\/p>\n<\/td>\n<td colspan=\"5\">\n<p><strong>P10+ <\/strong>\t<strong>P11+ <\/strong>\t<strong>P12+ P13+ P14+ <\/strong>\t<strong>P15+<\/strong><\/p>\n<p><strong>P9-<\/strong>\t<strong>P10-P11-P12-<\/strong>\t<strong>P13-<\/strong>\t<strong>P14-P15-<\/strong><\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>5<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"2\">\n<p>14<\/p>\n<\/td>\n<td colspan=\"4\">\n<p>1516<\/p>\n<\/td>\n<td>\n<p>1718<\/p>\n<\/td>\n<td>\n<p>19<\/p>\n<\/td>\n<td>\n<p>2021<\/p>\n<\/td>\n<td>\n<p>22<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-020\/fbs-hw-en-020-013.png\" \/><\/p>\n<p>\u25cb1External power input terminal \uff1aPower supply for analogue circuit of FBs-XXRTD module, supply voltage is <\/p>\n<p>24VDC\u00b120%<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>\u25cb2Protecting ground terminal\uff1aConnect to the shielding signal cable.<\/p>\n<p>\u25cb3 Expansion input cable\uff1aIt should be connected to the front expansion unit, or the expansion output of main unit.<\/p>\n<p>\u25cb4Expansion output connector\uff1aProvides the connection for next expansion unit.<\/p>\n<p>\u25cb5Power indicator\uff1a Indicates whether the power supply at analogue circuit and external input power source are normal.<\/p>\n<p>\u25cb6Common terminal for 3-wires RTD input\uff1aTo connect to the common wire of each 3-wires RTD input.<\/p>\n<p>\u25cb7Input terminal for 1st  RTD input\uff1aThe RTD input of channel 0(P0+\u3001P0-)<\/p>\n<p>\u25cb8\uff5e\u25cb22Input terminal for (2nd\uff5e16th ) RTD input\uff1aThe RTD input of channel 1\uff5e15 (P1+\u3001P1-\uff5eP15+\u3001P15-) <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td><\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>20.5.3  FBs-6NTC Outlook of Top View <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"3\">\n<p>2<\/p>\n<\/td>\n<td>\n<p>1<\/p>\n<\/td>\n<td rowspan=\"3\">\n<p>6<\/p>\n<\/td>\n<td>\n<p>7<\/p>\n<\/td>\n<td>\n<p>8<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p><strong>+ 24V IN &#8211;<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>R0+<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>R1+<\/strong><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p><strong>R0-<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>R1-<\/strong><\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p> 6NTC <\/p>\n<p>4<\/p>\n<p><strong>POW<\/strong><\/p>\n<p>3<\/p>\n<p><strong>FBs-6NTC<\/strong><\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p><strong>R2+<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>R2-<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>R3+<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>R3-<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>R4+<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>R4-<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>R5+<\/strong><\/p>\n<\/td>\n<td>\n<p><strong>R5-<\/strong><\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>5<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>9<\/p>\n<\/td>\n<td>\n<p>10<\/p>\n<\/td>\n<td>\n<p>11<\/p>\n<\/td>\n<td>\n<p>12<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-020\/fbs-hw-en-020-014.png\" \/><\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>\u25cb1External power input terminal: Power supply for analogue circuit of FBs-6NTC module, supply voltage is 24VDC\u00b120%<\/p>\n<p>\u25cb2Protecting ground terminal: Connect to the shielding signal cable. <\/p>\n<p>\u25cb3 Expansion input cable\uff1aIt should be connected to the front expansion unit, or the expansion output of main unit.<\/p>\n<p>\u25cb4Expansion output connector: Provides the connection for next expansion unit. <\/p>\n<p>\u25cb5Power indicator\uff1a Indicates whether the power supply at analogue circuit and external input power source are normal. <\/p>\n<p>\u25cb6  Input terminal for 1st  NTC input\uff1aThe NTC input of channel 0(R0+\u3001R0-) <\/p>\n<p>\u25cb7 Input terminal for (2nd\uff5e6th ) NTC input\uff1aThe NTC input of channel 1\uff5e5 (R1+\u3001R1- \uff5eR5+\u3001R5-) <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p> 20.6Wiring of the Temperature Modules <\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<\/table>\n<\/div>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p> 20.6.1 Wiring of the Thermocouple Input Module <\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<\/table>\n<\/div>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"5\">\n<p>FBs-xxTC<\/p>\n<\/td>\n<td rowspan=\"5\">\n<p>+<\/p>\n<\/td>\n<td>\n<p>24V+<\/p>\n<\/td>\n<td>\n<p>+<\/p>\n<\/td>\n<td colspan=\"2\">\n<p>24VDC<\/p>\n<\/td>\n<td>\n<p>Inputs<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>24V<\/p>\n<\/td>\n<td colspan=\"3\">\n<p>External power supply<\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>J(K) type thermocouple <br \/>thermocouple<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"2\" rowspan=\"3\">\n<p>J(K) extension cable extension cable<\/p>\n<\/td>\n<td rowspan=\"3\">\n<p>+<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>TC0+<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>TC0<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"2\">\n<p>+<\/p>\n<\/td>\n<td>\n<p>TC1+<\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>+<\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>J(K) type thermocouple <\/p>\n<p>thermocouple<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>TC1<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>Thermocouple <\/p>\n<p>Input<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"2\">\n<p>+<\/p>\n<\/td>\n<td>\n<p>TCn+<\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>+<\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>J(K) type thermocouple <\/p>\n<p>thermocouple<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>TCn<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>Multiplexer<\/p>\n<p>extension cable J(K) extension cable<\/p>\n<p>(Shielding must be connected to FG)<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-020\/fbs-hw-en-020-015.png\" \/><\/p>\n<p>If it&#8217;s FBs-6TC, n is 5<\/p>\n<p>If it&#8217;s FBs-16TC, n is 15<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-020\/fbs-hw-en-020-016.png\" \/><\/p>\n<h4> 20.6.2 Wiring of the RTD Input Module <\/h4>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"5\">\n<p>FBs-xxRTD<\/p>\n<\/td>\n<td rowspan=\"5\">\n<p>+<\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>24V+<\/p>\n<\/td>\n<td colspan=\"3\">\n<p>Inputs<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>+<\/p>\n<\/td>\n<td colspan=\"2\">\n<p>24VDC<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>24V<\/p>\n<\/td>\n<td colspan=\"3\">\n<p>External power supply<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"3\" rowspan=\"2\">\n<p>Red line<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>P0+<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"6\">\n<p>+<\/p>\n<\/td>\n<td rowspan=\"6\">\n<p>+<\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>P0<\/p>\n<\/td>\n<td colspan=\"3\">\n<p>White line<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"3\">\n<p>RTD Sensor<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>COM<\/p>\n<\/td>\n<td colspan=\"3\">\n<p>White line<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"3\">\n<p>Red line<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>P1+<\/p>\n<\/td>\n<td colspan=\"2\" rowspan=\"2\">\n<p>White line<\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>RTD Sensor<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>P1<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>White line<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"2\">\n<p>+<\/p>\n<\/td>\n<td>\n<p>Pn+<\/p>\n<\/td>\n<td>\n<p>Red line<\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>RTD Sensor<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Pn<\/p>\n<\/td>\n<td>\n<p>White line<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>White line<\/p>\n<p>Multiplexer<\/p>\n<p>If it&#8217;s FBs-6RTD, n is 5<\/p>\n<p>If it&#8217;s FBs-16RTD, n is 15<\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-020\/fbs-hw-en-020-017.png\" \/><\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>20.6.3 Wiring of the NTC Module <\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>RO+ <\/p>\n<p>P0+<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>t<\/p>\n<\/td>\n<td>\n<p>RO- P0-<\/p>\n<p>R1+ P1+<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"2\">\n<p>t<\/p>\n<\/td>\n<td>\n<p>R1- P1-<\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>FBs-NTC6 FBs-6NTC <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>R5+ P5+<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>t<\/p>\n<\/td>\n<td>\n<p>P5-<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>20.7  Instructions Explanation and Program Example for Temperature Measurement \tand PID Temperature Control of FBs-PLC <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p> The followings are the instructions explanation and program example for temperature measurement and PID <\/p>\n<p>temperature control of FBs-PLC. <\/p>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-020\/fbs-hw-en-020-018.png\" \/><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-020\/fbs-hw-en-020-019.png\" \/><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-020\/fbs-hw-en-020-020.png\" \/><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-020\/fbs-hw-en-020-021.png\" \/><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-020\/fbs-hw-en-020-022.png\" \/><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-020\/fbs-hw-en-020-023.png\" \/><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-020\/fbs-hw-en-020-024.png\" \/><\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>FUN86 TPCTL <\/p>\n<\/td>\n<td>\n<p>Convenient Instruction of PID Temperature Control <\/p>\n<\/td>\n<td>\n<p>FUN86 TPCTL <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"3\">\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td colspan=\"13\">\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-020\/fbs-hw-en-020-025.png\" \/><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-020\/fbs-hw-en-020-026.png\" \/><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-020\/fbs-hw-en-020-027.png\" \/><\/p>\n<\/td>\n<td rowspan=\"2\"><\/td>\n<td>\n<p>Md <strong>:<\/strong>Selection of PID method <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"3\">\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-020\/fbs-hw-en-020-028.png\" \/><\/p>\n<\/td>\n<td><\/td>\n<td><\/td>\n<td colspan=\"5\" rowspan=\"14\">\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td><\/td>\n<\/tr>\n<\/table>\n<\/div>\n<\/td>\n<td colspan=\"4\" rowspan=\"14\">\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-020\/fbs-hw-en-020-029.png\" \/><\/p>\n<\/td>\n<td rowspan=\"14\">\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-020\/fbs-hw-en-020-030.png\" \/><\/p>\n<\/td>\n<td>\n<p> =0, Modified minimum overshoot method <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"3\"><\/td>\n<td rowspan=\"3\"><\/td>\n<td rowspan=\"3\"><\/td>\n<td>\n<p> =1, Universal PID method<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>Yn \uff1aStarting address of PID ON\/OFF output; <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"11\">\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-020\/fbs-hw-en-020-031.png\" \/><\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"10\"><\/td>\n<td rowspan=\"10\"><\/td>\n<td rowspan=\"11\">\n<p>K <\/p>\n<\/td>\n<td>\n<p>it takes Zn points.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Sn \uff1aStarting point of PID control of this instruction; <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Sn = 0\uff5e31.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Zn \uff1aNumber of the PID control of this instruction; <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>1\u2264 Zn \u226432 and 1 \u2264 Sn+Zn \u2264 32<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Sv \uff1aStarting register of the set point; <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>it takes Zn registers. (Unit in 0.1\u00b0)<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Os \uff1aStarting register of the in-zone offset; <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>it takes Zn registers. (Unit in 0.1\u00b0)<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>PR \uff1aStarting register of the gain (Kc); <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"5\">\n<p>Range <\/p>\n<\/td>\n<td>\n<p>Y <\/p>\n<\/td>\n<td>\n<p>HR <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>ROR <\/p>\n<\/td>\n<td colspan=\"4\">\n<p>DR <\/p>\n<\/td>\n<td>\n<p>it takes Zn registers.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"6\">\n<p>Y0 <\/p>\n<\/td>\n<td>\n<p>R0 <\/p>\n<\/td>\n<td colspan=\"4\">\n<p>R5000 <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>D0 <\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>0\uff5e1<\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>IR \uff1aStarting register of integral tuning constant (Ki);it <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"6\">\n<p>\u2223<\/p>\n<\/td>\n<td>\n<p>\u2223<\/p>\n<\/td>\n<td colspan=\"2\">\n<p>\u2223<\/p>\n<\/td>\n<td colspan=\"4\">\n<p>\u2223<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"4\">\n<p>Operand <\/p>\n<\/td>\n<td colspan=\"2\">\n<p>Y255 <\/p>\n<\/td>\n<td>\n<p>R3839 <\/p>\n<\/td>\n<td colspan=\"3\">\n<p>R8071 <\/p>\n<\/td>\n<td colspan=\"3\">\n<p>D3999 <\/p>\n<\/td>\n<td>\n<p>takes Zn registers.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"13\">\n<p>Md <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>DR \uff1aStarting register of derivative tuning constant <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"4\" rowspan=\"2\">\n<p>Yn <\/p>\n<\/td>\n<td colspan=\"9\" rowspan=\"2\">\n<p>\u25cb<\/p>\n<\/td>\n<td rowspan=\"3\">\n<p>0\uff5e31<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"2\">\n<p>(Td); it takes Zn registers.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"13\">\n<p>Sn <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"13\">\n<p>Zn <\/p>\n<\/td>\n<td rowspan=\"9\">\n<p>1\uff5e32<\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>OR \uff1aStarting register of the PID analog output; <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"6\" rowspan=\"2\">\n<p>Sv <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>\u25cb<\/p>\n<\/td>\n<td colspan=\"2\" rowspan=\"2\">\n<p>\u25cb* <\/p>\n<\/td>\n<td colspan=\"4\" rowspan=\"2\">\n<p>\u25cb<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>it takes Zn registers.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"6\">\n<p>Os <\/p>\n<\/td>\n<td>\n<p>\u25cb<\/p>\n<\/td>\n<td colspan=\"2\">\n<p>\u25cb* <\/p>\n<\/td>\n<td colspan=\"4\">\n<p>\u25cb<\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>WR\uff1aStarting of working register for this instruction. <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"6\">\n<p>PR <\/p>\n<\/td>\n<td>\n<p>\u25cb<\/p>\n<\/td>\n<td colspan=\"2\">\n<p>\u25cb* <\/p>\n<\/td>\n<td colspan=\"4\">\n<p>\u25cb<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"6\">\n<p>IR <\/p>\n<\/td>\n<td>\n<p>\u25cb<\/p>\n<\/td>\n<td colspan=\"2\">\n<p>\u25cb* <\/p>\n<\/td>\n<td colspan=\"4\">\n<p>\u25cb<\/p>\n<\/td>\n<td>\n<p>It takes 9 registers and can\u2019t be repeated in <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"6\">\n<p>DR <\/p>\n<\/td>\n<td>\n<p>\u25cb<\/p>\n<\/td>\n<td colspan=\"2\">\n<p>\u25cb* <\/p>\n<\/td>\n<td colspan=\"4\">\n<p>\u25cb<\/p>\n<\/td>\n<td rowspan=\"3\">\n<p>using.<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"6\">\n<p>OR <\/p>\n<\/td>\n<td>\n<p>\u25cb<\/p>\n<\/td>\n<td colspan=\"2\">\n<p>\u25cb* <\/p>\n<\/td>\n<td colspan=\"4\">\n<p>\u25cb<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"6\">\n<p>WR <\/p>\n<\/td>\n<td>\n<p>\u25cb<\/p>\n<\/td>\n<td colspan=\"2\">\n<p>\u25cb* <\/p>\n<\/td>\n<td colspan=\"4\">\n<p>\u25cb<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"3\">\n<p>\u25cfBy employing the temperature module and table editing method to get the current value of temperature and let it be as so called Process Variable (PV); after the calculation of software PID expression, it will respond the <\/p>\n<p>error with an output signal according to the setting of Set Point (SP),the error&#8217;s integral and the rate of change <\/p>\n<p>\tof the process variable. Through the closed loop operation, the steady state of the process may be expected.\u25cfConvert the output of PID calculation to be the time proportional on\/off (PWM) output, and via transistor output to control the SSR for heating or cooling process; this is a good performance and very low cost solution.<\/p>\n<p>\u25cfThrough the analog output module (D\/A module), the output of PID calculation may control the SCR or proportional valve to get more precise process control.<\/p>\n<p>\u25cf Digitized PID expression is as follows:<\/p>\n<p>n <br \/>Mn = [ Kc \u00d7 En ] + \u2211 [ Kc \u00d7 Ki \u00d7 Ts \u00d7 En ] + [ Kc \u00d7 Td \u00d7 ( P Vn \u2212P Vn-1 ) \/ Ts ] 0 <br \/>M n\uff1aOutput at time \u201cn\u201d.<\/p>\n<p>K c\uff1aGain (Range: 1\uff5e9999\uff1bPb=1000 \/ Kc \u00d70.1%, Unit in 0.1%) <br \/>K i\uff1aIntegral tuning constant (Range:0\uff5e9999, equivalent to 0.00\uff5e99.99 Repeat\/Minute) <br \/>T d\uff1aDerivative tuning constant (Range:0\uff5e9999, equivalent to 0.00\uff5e99.99 Minute) <br \/>PV n \uff1aProcess variable at time \u201cn\u201d<br \/>PV n\u22121 \uff1aProcess variable when loop was last solved <br \/>E n \uff1aError at time \u201cn\u201d ; E= SP \u2013 PVn <br \/>T s \uff1aSolution interval for PID calculation (Valid value are 10, 20, 40, 80,160, 320; the unit is in 0.1Sec)<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>FUN86 TPCTL <\/p>\n<\/td>\n<td>\n<p>Convenient Instruction of PID Temperature Control <\/p>\n<\/td>\n<td>\n<p>FUN86 TPCTL <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"3\">\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p> Principle of PID parameter adjustment <\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>\u25cfAs the gain (Kc) adjustment getting larger, the larger the proportional contribution to the output.  This can obtain a sensitive and rapid control reaction.  However, when the gain is too large, it may cause oscillation. Do the best to adjust \u201cKc\u201d larger (but not to the extent of making oscillation), which could increase the process reaction and reduce the steady state error.<\/p>\n<p>\u25cfIntegral item may be used to eliminate the steady state error. The larger the number ( Ki, integral tuning constant, Ki=1\/Ti ), the larger the integral contribution to the output. When there is steady state error, adjust the \u201cKi\u201d larger to decrease the error. <\/p>\n<p>When the \u201cKi\u201d = 0, the integral item makes no contribution to the output.<\/p>\n<p>For example <strong>:<\/strong> if the reset time is 5 minutes, Ki=1\/Ti=100\/5=20\uff1bIt means integral tuning constant is 0.2 Repeat\/Minute<\/p>\n<p>\u25cf  Derivative item may be used to make the process smoother and not too over shoot.  The larger the number (Td, derivative tuning constant), the larger the derivative contribution to the output.  When there is too over shoot, adjust the \u201cTd\u201d larger to decrease the amount of over shoot. <\/p>\n<p>When the \u201cTd\u201d = 0, the derivative item makes no contribution to the output.<\/p>\n<p>For example <strong>:<\/strong> if the rate time is 1 minute, then the Td = 100; if the differential time is 2 minute, then the Td = 200.<\/p>\n<p>\u25cf Properly adjust the PID parameters can obtain an excellent result for temperature control.<\/p>\n<p>\u25cf The default solution interval for PID calculation is 4 seconds (Ts=40).<\/p>\n<p>\u25cf The default of gain value (Kc) is 110, where Pb=1000\/110\u00d70.1%\u22520.91%; the system full range is 1638\u00b0, it \tmeans the value SP\uff0d14.8\u00b0 (1638\u00d70.91\u225214.8) will let PID operation enter proportional band control.<\/p>\n<p>\u25cf The default of integral tuning constant is 17<\/p>\n<p>\u25cf The default of derivative tuning constant is50, it means the rate time is 0.5 minutes (Td=50).<\/p>\n<p>\u25cf When changing the PID solution interval, it may tune the parameters Kc, Ki, Td again.<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p> Instruction guide <\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>\u25cfFUN86 will be enabled after reading all temperature channels.<\/p>\n<p>\u25cf When execution control \u201cEN\u201d = 1, it depends on the input status of H\/C for PID operation to make heating (H\/C=1) or cooling (H\/C=0) control.  The current values of measured temperature are through the multiplexing temperature module ; the set points of desired temperature are stored in the registers starting from Sv.  With the calculation of software PID expression, it will respond the error with an output signal according to the setting of set point, the error&#8217;s integral and the rate of change of the process variable. Convert the output of PID calculation to be the time proportional on\/off (PWM) output, and via transistor output to control the SSR for heating or cooling process; where there is a good performance and very low cost solution.  It may also apply the output of PID calculation (stored in registers starting from OR), by way of D\/A analog output module, to control SCR or proportional valve, so as to get more precise process control.<\/p>\n<p>\u25cf When the setting of Sn, Zn (0 U Sn U 31 and 1 U Zn U 32, as well as 1 U Sn + Zn U 32) comes error, this \tinstruction will not be executed and the instruction output \u201cERR\u201d will be ON.<\/p>\n<p>\u25cf This instruction compares the current value with the set point to check whether the current temperature falls within deviation range (stored in register starting from Os).  If it falls in the deviation range, it will set the in-zone bit of that point to be ON; if not, clear the in-zone bit of that point to be OFF, and make instruction output \u201cALM\u201d to be ON.<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>FUN86 TPCTL <\/p>\n<\/td>\n<td>\n<p>Convenient Instruction of PID Temperature Control <\/p>\n<\/td>\n<td>\n<p>FUN86 TPCTL <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"3\">\n<p>\u25cf In the mean time, this instruction will also check whether highest temperature warning (the register for the set point of highest temperature warning is R4008).  When successively scanning for ten times the current values of measured temperature are all higher than or equal to the highest warning set point, the warning bit will set to be ON and instruction output \u201cALM\u201d will be ON.  This can avoid the safety problem aroused from temperature out of control, in case the SSR or heating circuit becomes short.<\/p>\n<p>\u25cf This instruction can also detect the unable to heat problem resulting from the SSR or heating circuit runs open, or the obsolete heating band.  When output of temperature control turns to be large power (set in R4006 register) successively in a certain time (set in R4007 register), and can not make current temperature fall in desired range, the warning bit will set to be ON and instruction output \u201cALM\u201d will be ON.<\/p>\n<p>\u25cf WR: Starting of working register for this instruction. It takes 9 registers and can\u2019t be repeated in using. <\/p>\n<p> The content of the two registers WR+0 and WR+1 indicating that whether the current temperature falls within the deviation range (stored in registers starting from Os).  If it falls in the deviation range, the in-zone bit of that point will be set ON; if not, the in-zone bit of that point will be cleared OFF.<\/p>\n<p>Bit definition of WR+0 explained as follows: <br \/> Bit0=1, it represents that the temperature of the Sn+0 point is in-zone\u2026  Bit15=1, it represents that the temperature of the Sn+15 point is in-zone. <\/p>\n<p> Bit definition of WR+1 explained as follows: <br \/> Bit0=1, it represents that the temperature of the Sn+16 point is in-zone\u2026  Bit15=1, it represents that the temperature of Sn+31 point is in-zone. <\/p>\n<p> The content of the two registers WR+2 and WR+3 are the warning bit registers, they indiacte that whether \tthere exists the highest temperature warning or heating circuit opened. <\/p>\n<p> Bit definition of WR+2 explained as follows: <br \/> Bit0=1, it means that there exists the highest warning or heating circuit opened at the Sn+0 point&#8230; <\/p>\n<p> Bit15=1, it means that there exists the highest warning or heating circuit opened at the Sn+15 point. <\/p>\n<p> Bit definition of WR+11 explained as follows: <br \/> Bit0=1, it means that there exists the highest warning or heating circuit opened at the Sn+16 point&#8230; <\/p>\n<p> Bit15=1 , it means that there exists the highest warning or heating circuit opened at the Sn+31 point.  Registers of WR+4 \uff5e WR+8 are used by this instruction. <\/p>\n<p>\u25cf It needs separate instructions to perform the heating or cooling control.<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p> Specific registers related to FUN86 <\/p>\n<\/td>\n<td><\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>\u25cf R4003 = A55AH, starting address of temperature reading value is defined by R4004 <br \/>\t= Other values, starting address of temperature reading value is defined by temperature configuration \t\t\tscreen <br \/>\u25cf R4004 = 10000\uff5e13839, is defines R0~R3839 is the starting address of temperature reading value as the \t\t\t\tprocess variables for PID control <br \/>\t\t= 20000\uff5e23999, it defines D0~D3999 is the starting address of temperature reading value as the \t\t\t\tprocess variables for PID control <br \/>\t\t= Other values, starting address of temperature reading value is defined by temperature configuration \t\t\t\tscreen <\/p>\n<p>\u25cf R4005 <strong>:<\/strong> The content of Low Byte to define the solution interval between PID calculation <\/p>\n<p>=0, perform the PID calculation every 1 seconds. <\/p>\n<p> =1, perform the PID calculation every 2 seconds. <\/p>\n<p> =2, perform the PID calculation every 4 seconds. (System default)  =3, perform the PID calculation every 8 seconds.<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>FUN86 TPCTL <\/p>\n<\/td>\n<td>\n<p>Convenient Instruction of PID Temperature Control <\/p>\n<\/td>\n<td>\n<p>FUN86 TPCTL <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"3\">\n<p> =4, perform the PID calculation every 16 seconds. <br \/>\u22655, perform the PID calculation every 32 seconds.<\/p>\n<p>\uff1aThe content of High Byte to define the cycle time of PID ON\/OFF\uff08PWM\uff09output.=0\uff0cPWM cycle time is 1 seconds.  =1\uff0cPWM cycle time is 2 seconds. (System default) <br \/> =2\uff0cPWM cycle time is 4 seconds. <\/p>\n<p> =3\uff0cPWM cycle time is 8 seconds. <\/p>\n<p> =4\uff0cPWM cycle time is 16 seconds. <\/p>\n<p>\u22655\uff0cPWM cycle time is 32 seconds. <\/p>\n<p>Note 1 <strong>:<\/strong> When changing the value of R4005, the execution control \u201cEN\u201d of FUN86 must be set at 0.  The next time \twhen execution control \u201cEN\u201d =1, it will base on the latest set point to perform the PID calculation.<\/p>\n<p>Note 2 <strong>:<\/strong> The smaller the cycle time of PWM, the more even can it perform the heating.  However, the error caused by the PLC scan time will also become greater.  For the best control, it can base on the scan time of PLC to adjust the solution interval of PID calculation and the PWM cycle time. <\/p>\n<p>\u25cfR4006\uff1aThe setting point of large power output detection for SSR or heating circuit opened, or heating band obsolete.  The unit is in % and the setting range falls in 80\uff5e100(%); system default is 90(%).<\/p>\n<p>\u25cfR4007\uff1aThe setting time to detect the continuing duration of large power output while SSR or heating circuit opened, or heating band obsolete.  The unit is in second and the setting range falls in 60\uff5e65535 (seconds); system default is 600 (seconds).<\/p>\n<p>\u25cfR4008\uff1aThe setting point of highest temperature warning for SSR, or heating circuit short detection. The unit \tis in 0.1 degree and the setting range falls in 100\uff5e65535; system default is 3500 (Unit in 0.1\u00b0).\u25cfR4012\uff1aEach bit of R4012 to tell the need of PID temperature control. <\/p>\n<p> Bit0=1 means that 1st point needs PID temperature control. <\/p>\n<p> Bit1=1 means that 2nd point needs PID temperature control. <\/p>\n<p>\u2027<\/p>\n<p>\t\u2027<br \/> Bit15=1 means that 16th point needs PID temperature control. <\/p>\n<p>\t (The default of R4012 is FFFFH)<br \/>\u25cfR4013\uff1aEach bit of R4013 to tell the need of PID temperature control. \t Bit0=1 means that 17th point needs PID temperature control. <\/p>\n<p> Bit1=1 means that 18th point needs PID temperature control. <\/p>\n<p>\u2027<\/p>\n<p>\t\u2027<br \/> Bit15=1 means that 32th point needs PID temperature control. <\/p>\n<p> (The default of R4013 is FFFFH) <\/p>\n<p>\u25cfWhile execution control \u201cEN\u201d=1 and the corresponding bit of PID control of that point is ON (corresponding bit of R4012 or R4013 must be 1), the FUN86 instruction will perform the PID operation and respond to the calculation with the output signal.<\/p>\n<p>\u25cfWhile execution control \u201cEN\u201d=1 and the corresponding bit of PID control of that point is OFF <br \/>(corresponding bit of R4012 or R4013 must be 0), the FUN86 will not perform the PID operation and the output of that point will be OFF.<\/p>\n<p>\u25cfThe ladder program may control the corresponding bit of R4012 and R4013 to tell the FUN86 to perform or not to perform the PID control, and it needs only one FUN86 instruction.<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p><img decoding=\"async\" src=\"https:\/\/resource.fatek.com\/wp-content\/uploads\/fatek\/fbs-hw-en-020\/fbs-hw-en-020-032.png\" \/><\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>FUN86 <\/p>\n<\/td>\n<td rowspan=\"2\">\n<p>Convenient Instruction of PID Temperature Control <\/p>\n<\/td>\n<td>\n<p>FUN86 <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>TPCTL <\/p>\n<\/td>\n<td>\n<p>TPCTL <\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p> Program example <\/p>\n<p>08.MOV<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"14\">\n<p>M0<\/p>\n<\/td>\n<td>\n<p>EN<\/p>\n<\/td>\n<td>\n<p>S<\/p>\n<\/td>\n<td>\n<p>:  WM800<\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>ERR<\/p>\n<\/td>\n<td rowspan=\"4\">\n<p>M100<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"3\">\n<p>EN<\/p>\n<\/td>\n<td>\n<p>D<\/p>\n<\/td>\n<td>\n<p>:  R4012<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"2\">\n<p>86.TPCTL<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>MD<\/p>\n<\/td>\n<td>\n<p>:      0<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"10\">\n<p>H\/C<\/p>\n<\/td>\n<td>\n<p>Yn<\/p>\n<\/td>\n<td>\n<p>:    Y30<\/p>\n<\/td>\n<td rowspan=\"10\">\n<p>ALM<\/p>\n<\/td>\n<td rowspan=\"10\">\n<p>M101<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Sn<\/p>\n<\/td>\n<td>\n<p>:      0<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Zn<\/p>\n<\/td>\n<td>\n<p>:     10<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Sv<\/p>\n<\/td>\n<td>\n<p>:   R100<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>Os<\/p>\n<\/td>\n<td>\n<p>:   R110<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>PR<\/p>\n<\/td>\n<td>\n<p>:   R120<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>IR<\/p>\n<\/td>\n<td>\n<p>:   R130<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>DR<\/p>\n<\/td>\n<td>\n<p>:   R140<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>OR<\/p>\n<\/td>\n<td>\n<p>:   R200<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>WR<\/p>\n<\/td>\n<td>\n<p>:   R300<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>08.MOV<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"2\">\n<p>EN<\/p>\n<\/td>\n<td>\n<p>S<\/p>\n<\/td>\n<td>\n<p>:   R300<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>D<\/p>\n<\/td>\n<td>\n<p>:  WM400<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>08.MOV<\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td rowspan=\"2\">\n<p>EN<\/p>\n<\/td>\n<td>\n<p>S<\/p>\n<\/td>\n<td>\n<p>:   R302<\/p>\n<\/td>\n<\/tr>\n<tr>\n<td>\n<p>D<\/p>\n<\/td>\n<td>\n<p>:  WM416<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n<p>Description <\/p>\n<p>\u25cfThe status of M800\uff5eM815 are controlled by the MMI or external inputs to tell which temperature channel \t\tneeds PID control; if the corresponding bit is ON, it means yes; if the bit is OFF, it means no PID control.\u25cf When M0=ON, it will perform the PID heating control of 10 (Zn=10) channels from channel 0 (Sn=0) to \tchannel 9.<\/p>\n<p>\u25cf Y30 \uff5e Y39 : PID ON\/OFF (PWM) output; they must be the transistor outputs.<\/p>\n<p>\u25cf R100\uff5eR109 : Registers of set point (Unit in 0.1\u00b0).<\/p>\n<p>\u25cfR110\uff5eR119 : Registers of deviation zone (Unit in 0.1\u00b0), it determines whether the temperature falls into \tsetting range. <\/p>\n<p> E.g.  Set point is 2000 (200.0\u00b0) and deviation zone is 50 (5.0\u00b0), then <\/p>\n<p> 1950 (195.0\u00b0) \u2266 Current value \u2266 2050 (205.0\u00b0) means the temperature is in zone.  <\/p>\n<p>\u25cf R120\uff5eR129 : Setting point of gain .<\/p>\n<p>\u25cf R130\uff5eR139 : Setting point of integral tuning constant .<\/p>\n<p>\u25cf R140\uff5eR149 : Setting point of derivative tuning constant .<\/p>\n<p>\u25cf R200\uff5eR209 : Output of PID calculation (Value from 0\uff5e16383).<\/p>\n<p>\u25cf R300\uff5eR308 : Working registers, they can&#8217;t be repeated in use.<\/p>\n<p>\u25cf When the setting of Sn, Zn comes error, this instruction will not be executed and output M100 will be ON. <\/p>\n<div class=\"fatek-tw\">\n<table>\n<tr>\n<td>\n<p>FUN86 TPCTL <\/p>\n<\/td>\n<td>\n<p>Convenient Instruction of PID Temperature Control <\/p>\n<\/td>\n<td>\n<p>FUN86 TPCTL <\/p>\n<\/td>\n<\/tr>\n<tr>\n<td colspan=\"3\">\n<p>\u25cf When one of the temperatures is not in zone, or there exists highest temperature warning or heating \tabnormal, the output M101 will be ON. <\/p>\n<p>Note<strong> :<\/strong> When performing the instruction FUN86 of the first time, the system will automatically assign the default value of gain (Kc), integral tuning constant (Ki), and derivative tuning constant (Td) for each channel. They can be changed while application tuning.<\/p>\n<p>\u25cf M400\uff5eM409 : The temperature in zone indicators.<\/p>\n<p>\u25cf M416\uff5eM425 : To tell the highest temperature warning or heating abnormal channel.<\/p>\n<\/td>\n<\/tr>\n<\/table>\n<\/div>\n","protected":false},"excerpt":{"rendered":"<p>FBs-PLC provides two kinds of temperature modules to me [&hellip;]<\/p>\n","protected":false},"author":1,"featured_media":0,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[33],"tags":[],"class_list":["post-3425","post","type-post","status-publish","format-standard","hentry","category-en-fbs-hw"],"_links":{"self":[{"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/posts\/3425","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/comments?post=3425"}],"version-history":[{"count":0,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/posts\/3425\/revisions"}],"wp:attachment":[{"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/media?parent=3425"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/categories?post=3425"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/resource.fatek.com\/index.php\/wp-json\/wp\/v2\/tags?post=3425"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}