M Series PLC provides the single end 24VDC inputs which use the common terminal to save terminals. The response speeds of single-end common input circuits are available in high, medium-low. The single-end input circuit can be set to SINK or SOURCE type by varying the wiring of the common terminal S/S inside PLC and external common wire of input circuits.

5-1 Digital Input Circuit Specifications

Digital Input Circuit Specifications

Item

Specifications

24VDC Single-end input

Note

High Speed (HSC)

Medium-Low Speed

Maximum input frequency

200KHz

1kHz

Input Signal Voltage

24VDC±10%

Input

Current

Threshold

ON Current

>8mA

>4mA

OFF Current

<2mA

<1.5mA

Maximum Input Current

7.6mA

10.5mA

Input Resistance

3.3kΩ

5.6kΩ

Input Status Indication

Displayed by LED: Lit when “ON”, dark when “OFF”

Isolation Type

Transformer/ Photo-coupler Isolation,1500VAC/1 minute

SINK /SOURCE Wiring

Via variation of internal common terminal S/S and external common wiring

CPU Modules

MQ2M0-1616◇

Y0~Y7

Y8~Y15

MQ2M1-1616◇

Y0~Y7

Y8~Y15

MQ2M3-1616◇

Y0~Y7

Y8~Y15

MQ2M6-1616◇

Y0~Y7

Y8~Y15

MA1N0-1616◇

Y0~Y15

MA1N3-1616◇

Y0~Y15

MA1I4-1616◇

Y0~Y15

–

MU2C4-1616◇

Y0~Y15

–

MU2C6-1616◇

Y0~Y15

–

MU3C2-1616◇

Y0~Y15

–

MU3C3-1616◇

Y0~Y15

MU3C4-1616◇

Y0~Y15

–

MU3C5-1616◇

Y0~Y15

–

MU3C6-1616◇

Y0~Y15

–

MS2C4-1616◇

Y0~Y15

–

MS2C5-1616◇

Y0~Y15

–

MS3C6-1616◇

Y0~Y15

ME2C3-1616◇

Y0~Y15

ME2C4-1616◇

Y0~Y15

ME2C5-1616◇

Y0~Y15

ME3C6-1616◇

Y0~Y15

Expansion Modules

M16X

–

X1~X16

M1616XY

–

X1~X16

Noise Filtering Time Constant

DHF(0 ~ 15ms)+AHF(0.47μs)

DHF(0 ~ 70ms)+AHF(0.47ms)

DHF:Digital Hardware Filter

AHF:Analog Hardware Filter

5-2 24VDC Single-End Input Circuit and Wiring for SINK/SOURCE Input

The 24VDC single-end digital input circuits of M Series PLC are available for high and medium-low speed. They all have similar circuit structures but with different response speeds. To save input terminals, the circuit of single-end input is implemented by connecting one end of all input points (photo coupler) inside the PLC to the same internal common point labeled as S/S. The other end of each input circuit is connected to corresponding terminals such as X0, X1, X2, etc. The S/S common terminal and N single-end inputs comprise of N digital inputs (i.e., only N+1 terminals are used for N terminals). Therefore, we call this type of input structure the single-end input. The user also needs to do the same thing when making the connection of external digital input devices. Namely, one end of all input devices (e.g., buttons, switches) are connected together and called the external common wire, while the other ends of input circuits are connected to the input terminals X0, X1, X2, etc., of PLC. Then finish it by connecting the external common wiring and internal common terminal S/S to the positive/negative terminals of the 24VDC power. When connect the internal common terminal S/S to 24V+(positive) and the external common wire to 24V- (negative), then the circuit serve as SINK input. On the contrary, while exchange the wiring of the above internal and external common will serve as a SOURCE input. The above wiring schemes can illustrate below