The number of I/O can be expanded by adding expansion modules.

The hardware limitations.

① The maximum connection numbers of modules are 64, whenever which modules you use.

The numbers of limit connection expansion modules of each section is 16.

3-1 Digital I/O Expansion and I/O Numbering

While the various expansion modules other than the IO Coupler have the same printed labels on the input/output terminals, these labels are only relative I/O numbers, different from the absolute I/O numbers on IO Coupler. The number of a terminal only represents its order on the expansion module.

For example, the first contact is 1, the second 2, etc. All numbers on the expansion module begin with 1. The actual number of digital input contact or the output replay, however, is determined by summing the numbers on all previous expansion modules and the CPU module. See the following figure and its calculation.

Chapter 3 Local I/O expansion Modules - 1

▲Expansion Module Digital I/O Number

As shown in the above figure,10 output points on the 2nd expansion module M16X. Because the top X numbers of the previous unit are 15 , respectively, the number of input contact X25 on second expansion unit should be:

X( 15+10 ) = X25

⚠Caution

The IO Coupler’s extended I/O cable length must not exceed 5 meters. Otherwise, excessive signal delay or excessive noise pickup may occur, potentially leading to incorrect I/O operations, which could damage the equipment or cause injury. This limitation is due to the IO Coupler’s inability to detect such issues, and it is the user’s responsibility to ensure compliance and manage this limitation.

3-2 Expansion Module Configuration Settings

The Expansion Module Configuration of the IO Coupler is implemented in the “UperIO”→【Management】→【Expansion Module】→【Configuration】.

The Management is designed to concurrently display the outline dimensions, Module Information (Module ID and Firmware Version), Power Consumption and Module Resources (occupying the register) of different expansion modules, as indicated below.

Chapter 3 Local I/O expansion Modules - 2

▲Device View

When being installed in different types of expansion modules, the Expansion Module Configuration of the IO Coupler will display different types of configuration pages, as indicated below.

The Expansion Module Configuration of the IO Coupler is saved in the expansion module directly. Even if the CPU module is damaged, such expansion module can still operate independently to show the corresponding processing action. In this way, it not only improves the system stability but also intensifies the system security.

Chapter 3 Local I/O expansion Modules - 3

▲Configuration

⚠Caution

The expansion module configuration of IO Coupler is saved in the project and the expansion module instead of being saved in the IO Coupler. Before replacing the expansion module, you need to set the expansion module configuration in the expansion module or save the project on the IO Coupler and then the IO Coupler will write the expansion module configuration being saved to the corresponding expansion module.

3-3 Mapping Table

To facilitate users in checking the current IO mapping to Modbus TCP and Ethernet/IP, they can click on the “Mapping Table” on the Ribbon. This will display detailed information about the current IO mapping. Users can switch between protocols as shown in the image below.

Chapter 3 Local I/O expansion Modules - 4

Chapter 3 Local I/O expansion Modules - 5

▲Modbus Mapping Table

The detailed IO mapping is as follows:

Mobus TCP:

Modbus Address

Mapping

Attribute

000001 – 001024

DO channels

Read and Write

100001 – 101024

DI channels

Read-Only

300001 – 300512

AI channels

Read-Only

300513 – 302267

System Info

Read-Only

400001 – 400256

AO channels

Read and Write

400257 – 400270

System Info

Read and Write

▲Modbus TCP description

Ethernet/IP

Class ID = 0x04

Instance Number

Instance Size

Member Number

Member Size

Modules Per Instance

Mapping Module

Attribute

16

(ID:100 – 115)

8 Bytes

64

1 Bit

4

DI

Read-Only

16

(ID:116 – 131)

8 Bytes

64

1 Bit

4

DO

Read and write

8

(ID:132 – 139)

128 Bytes

32

4 Bytes

8

AI

Read-Only

8

(ID:140 – 147)

64 Bytes

32

2 Bytes

8

AO

Read and write

▲Ethernet/IP

3-4 System Information

The detailed mapping is as follows:

System Info (RO)

Size (Word)

Modbus Address

description

Product Model

1

300513

Serial Number

8

300514 – 300521

Firmware Version

2

300522 – 300523

Hardware Version

1

300524

MAC Address

3

300525 – 300527

System Status

Indicator

1

300528

BIT0: Expansion Module Detection Error

System Error Indicator

2

300529 – 300530

BIT0: Coupler Normal Operation or Error Occurrence

BIT4: Watchdog Reset Detection

BIT9: System Stack Error

BIT15: System Service Error Indicator

Expansion AI Points

1

300531

Expansion AO Points

1

300532

Expansion DI Points

1

300533

Expansion DO Points

1

300534

Expansion Module Heartbeat Detection

(Rack 1-4)

4

300535 – 300538

System Debug

Registers

65

300539 – 300603

System Registers, used for internal debugging during major system crashes

I/O module status

1664

300604 – 302267

Expansion Module Status Registers

For example, with AIH, in addition to channel values, it includes error codes, maximum value hold, etc., with a total of 13 registers. AIH has the most status registers among modules, so the maximum mapping space required is estimated based on 64 AI units.

52 B(MAX: AIH) * 64 = 3328 B = 1664 Regs

▲System Info

System Info (Read and Write)

Size

Modbus Address

description

IP Address

2

400257、400258

e.g.:192.168.0.39

Modbus display with 〔Hex〕:

400257:A8C0

400258:2700

Subnet Mask

2

400259、400260

e.g.:255.255.255.0

Modbus display with 〔Hex〕:

400259:FFFF

400260:00FF

Gateway Address

2

400261、400262

e.g.:192.168.0.1

Modbus display with 〔Hex〕:

400261:A8C0

400262:0100

IP Acquisition Mode

1

400263

e.g.: static

Modbus display with 〔Hex〕:

400263:0000

Primary DNS Server

2

400264、400265

e.g.:168.95.1.1

Modbus display with 〔Hex〕:

400264:5FA8

400265:0101

Secondary DNS Server

2

400266、400267

e.g.:208.91.112.52

Modbus display with 〔Hex〕:

400266:5BD0

400267:3470

User-defined FATEK Port

1

400268

e.g.:503

Modbus display with 〔Hex〕:

400268:01F7

User-defined Modbus TCP Port

1

400269

e.g.:504

Modbus display with 〔Hex〕:

400269:01F8

Connection Idle Timeout

1

400270

e.g.:10 secs

Modbus display with 〔Hex〕:

400270:000A

▲Modbus address relate to IO Coupler setting

3-5 Expansion Module Firmware Update

The expansion module firmware of the IO Coupler is updated in the “UperIO”【Management】→【Expansion Module】→【Device information】” profile.

In this regard, the equipment information displays the module name, module ID, module description, module firmware version, module hardware version and module serial number of the expansion module, as indicated below:

Chapter 3 Local I/O expansion Modules - 6

▲Device Information

The expansion module firmware update of IO Coupler can be updated individually or multiple expansion modules can be updated at the same time.

Chapter 3 Local I/O expansion Modules - 7

▲Firmware update