The number of I/O can be expanded by adding expansion modules.
The hardware limitations.
① The maximum connection numbers of modules are 64, whenever which modules you use.
The numbers of limit connection expansion modules of each section is 16.
3-1 Digital I/O Expansion and I/O Numbering
While the various expansion modules other than the IO Coupler have the same printed labels on the input/output terminals, these labels are only relative I/O numbers, different from the absolute I/O numbers on IO Coupler. The number of a terminal only represents its order on the expansion module.
For example, the first contact is 1, the second 2, etc. All numbers on the expansion module begin with 1. The actual number of digital input contact or the output replay, however, is determined by summing the numbers on all previous expansion modules and the CPU module. See the following figure and its calculation.

▲Expansion Module Digital I/O Number
As shown in the above figure,10 output points on the 2nd expansion module M16X. Because the top X numbers of the previous unit are 15 , respectively, the number of input contact X25 on second expansion unit should be:
X( 15+10 ) = X25
|
⚠Caution |
|
The IO Coupler’s extended I/O cable length must not exceed 5 meters. Otherwise, excessive signal delay or excessive noise pickup may occur, potentially leading to incorrect I/O operations, which could damage the equipment or cause injury. This limitation is due to the IO Coupler’s inability to detect such issues, and it is the user’s responsibility to ensure compliance and manage this limitation. |
3-2 Expansion Module Configuration Settings
The Expansion Module Configuration of the IO Coupler is implemented in the “UperIO”→【Management】→【Expansion Module】→【Configuration】.
The Management is designed to concurrently display the outline dimensions, Module Information (Module ID and Firmware Version), Power Consumption and Module Resources (occupying the register) of different expansion modules, as indicated below.

▲Device View
When being installed in different types of expansion modules, the Expansion Module Configuration of the IO Coupler will display different types of configuration pages, as indicated below.
The Expansion Module Configuration of the IO Coupler is saved in the expansion module directly. Even if the CPU module is damaged, such expansion module can still operate independently to show the corresponding processing action. In this way, it not only improves the system stability but also intensifies the system security.

▲Configuration
|
⚠Caution |
|
The expansion module configuration of IO Coupler is saved in the project and the expansion module instead of being saved in the IO Coupler. Before replacing the expansion module, you need to set the expansion module configuration in the expansion module or save the project on the IO Coupler and then the IO Coupler will write the expansion module configuration being saved to the corresponding expansion module. |
3-3 Mapping Table
To facilitate users in checking the current IO mapping to Modbus TCP and Ethernet/IP, they can click on the “Mapping Table” on the Ribbon. This will display detailed information about the current IO mapping. Users can switch between protocols as shown in the image below.


▲Modbus Mapping Table
The detailed IO mapping is as follows:
Mobus TCP:
|
Modbus Address |
Mapping |
Attribute |
|
000001 – 001024 |
DO channels |
Read and Write |
|
100001 – 101024 |
DI channels |
Read-Only |
|
300001 – 300512 |
AI channels |
Read-Only |
|
300513 – 302267 |
System Info |
Read-Only |
|
400001 – 400256 |
AO channels |
Read and Write |
|
400257 – 400270 |
System Info |
Read and Write |
▲Modbus TCP description
Ethernet/IP
Class ID = 0x04
|
Instance Number |
Instance Size |
Member Number |
Member Size |
Modules Per Instance |
Mapping Module |
Attribute |
|
16 (ID:100 – 115) |
8 Bytes |
64 |
1 Bit |
4 |
DI |
Read-Only |
|
16 (ID:116 – 131) |
8 Bytes |
64 |
1 Bit |
4 |
DO |
Read and write |
|
8 (ID:132 – 139) |
128 Bytes |
32 |
4 Bytes |
8 |
AI |
Read-Only |
|
8 (ID:140 – 147) |
64 Bytes |
32 |
2 Bytes |
8 |
AO |
Read and write |
▲Ethernet/IP
3-4 System Information
The detailed mapping is as follows:
|
System Info (RO) |
Size (Word) |
Modbus Address |
description |
|
Product Model |
1 |
300513 |
|
|
Serial Number |
8 |
300514 – 300521 |
|
|
Firmware Version |
2 |
300522 – 300523 |
|
|
Hardware Version |
1 |
300524 |
|
|
MAC Address |
3 |
300525 – 300527 |
|
|
System Status Indicator |
1 |
300528 |
BIT0: Expansion Module Detection Error |
|
System Error Indicator |
2 |
300529 – 300530 |
BIT0: Coupler Normal Operation or Error Occurrence BIT4: Watchdog Reset Detection BIT9: System Stack Error BIT15: System Service Error Indicator |
|
Expansion AI Points |
1 |
300531 |
|
|
Expansion AO Points |
1 |
300532 |
|
|
Expansion DI Points |
1 |
300533 |
|
|
Expansion DO Points |
1 |
300534 |
|
|
Expansion Module Heartbeat Detection (Rack 1-4) |
4 |
300535 – 300538 |
|
|
System Debug Registers |
65 |
300539 – 300603 |
System Registers, used for internal debugging during major system crashes |
|
I/O module status |
1664 |
300604 – 302267 |
Expansion Module Status Registers For example, with AIH, in addition to channel values, it includes error codes, maximum value hold, etc., with a total of 13 registers. AIH has the most status registers among modules, so the maximum mapping space required is estimated based on 64 AI units. 52 B(MAX: AIH) * 64 = 3328 B = 1664 Regs |
▲System Info
|
System Info (Read and Write) |
Size |
Modbus Address |
description |
|
IP Address |
2 |
400257、400258 |
e.g.:192.168.0.39 Modbus display with 〔Hex〕: 400257:A8C0 400258:2700 |
|
Subnet Mask |
2 |
400259、400260 |
e.g.:255.255.255.0 Modbus display with 〔Hex〕: 400259:FFFF 400260:00FF |
|
Gateway Address |
2 |
400261、400262 |
e.g.:192.168.0.1 Modbus display with 〔Hex〕: 400261:A8C0 400262:0100 |
|
IP Acquisition Mode |
1 |
400263 |
e.g.: static Modbus display with 〔Hex〕: 400263:0000 |
|
Primary DNS Server |
2 |
400264、400265 |
e.g.:168.95.1.1 Modbus display with 〔Hex〕: 400264:5FA8 400265:0101 |
|
Secondary DNS Server |
2 |
400266、400267 |
e.g.:208.91.112.52 Modbus display with 〔Hex〕: 400266:5BD0 400267:3470 |
|
User-defined FATEK Port |
1 |
400268 |
e.g.:503 Modbus display with 〔Hex〕: 400268:01F7 |
|
User-defined Modbus TCP Port |
1 |
400269 |
e.g.:504 Modbus display with 〔Hex〕: 400269:01F8 |
|
Connection Idle Timeout |
1 |
400270 |
e.g.:10 secs Modbus display with 〔Hex〕: 400270:000A |
▲Modbus address relate to IO Coupler setting
3-5 Expansion Module Firmware Update
The expansion module firmware of the IO Coupler is updated in the “UperIO”【Management】→【Expansion Module】→【Device information】” profile.
In this regard, the equipment information displays the module name, module ID, module description, module firmware version, module hardware version and module serial number of the expansion module, as indicated below:

▲Device Information
The expansion module firmware update of IO Coupler can be updated individually or multiple expansion modules can be updated at the same time.

▲Firmware update