20-1 Precautions
When performing the required servicing and maintenance, please watch the following requirements because incorrect or careless operations may result in personal injury and equipment damage.
- ⚠ Please confirm that the ambient environment is not exposed to corrosive substances (e.g., chlorides and sulfide gas) and combustible substances (e.g., oil mist and cutting powder) or dusty area to prevent PLC System from failure or causing a fire.
- ⚠ Do not contact the terminal to prevent the terminal from getting oxidized or personnel from electrocution.
- ⚠ Shut down the external power and then dismantle the terminal or the screws to avoid personnel electrocution.
- ⚠ Do not apply heavy force on the cables or drag or clip the cable too hard to prevent cable from damage or terminal from loosening while avoiding electrocution.
- ⚠ Confirm that the input voltage is within the rating scope.
- ⚠ Do not attempt to disassemble or modify the module or repair the module privately; otherwise, it may lead to product failure, fire or personnel injury.
- After replacing the CPU module, confirm that all programs and parameters are being created in the new CPU module and are duly set. Following that, you may start the PLC System to prevent the controlled component from executing a false action.
- Please read the manuals carefully in order to get familiar with the required operation mechanisms when the PLC is running such as procedure change, forced output and RUN/STOP, etc. The purpose is to prevent incorrect output or equipment damage as may be caused by inaccurate operations.
- Before touching the module, please touch the grounding metal first or wear an anti-static bracelet in order to discharge the electrostatic from the human body to prevent it from damaging the module.
- When using a mobile phone or communication device, please keep appropriate distance to prevent from interfering with the system as to cause the false action.
- Do not install the PLC Control System in an environment exposed to direct sunlight or humidity.
- Please confirm that appropriate distance has been maintained between the PLC Control System and the heat source such as coil, heater and resistor, etc. to prevent the component from being exposed to higher temperature.
- Please install an emergency power shutdown system and an over-current protection device as required in order to protect the PLC Control System.
- During the operations and maintenance process, please check the installation stability in order to avoid unexpected vibrations as to damage the PLC Control System and the controlled component.
20-2 19-1 Précautions
- Lors de l’exécution de l’entretien et de l’entretien requis, veuillez respecter les exigences suivantes, car des opérations incorrectes ou négligentes peuvent entraîner des blessures corporelles et des dommages matériels.
- ⚠ Veuillez confirmer que l’environnement ambiant n’est pas exposé à des substances corrosives (par exemple, des chlorures et des gaz sulfurés) et à des substances combustibles (par exemple, du brouillard d’huile et de la poudre de coupe) ou à une zone poussiéreuse pour éviter que le système PLC ne tombe en panne ou ne provoque un incendie.
- ⚠ Ne pas toucher le terminal pour éviter que le terminal ne s’oxyde ou que le personnel ne s’électrocute.
- ⚠ Coupez l’alimentation externe puis démontez le terminal ou les vis pour éviter l’électrocution du personnel.
- ⚠ N’appliquez pas de force excessive sur les câbles, ne tirez pas et ne coupez pas trop fort le câble pour éviter qu’il ne soit endommagé ou que la borne ne se desserre tout en évitant l’électrocution.
- ⚠ Vérifiez que la tension d’entrée est dans la plage nominale.
- ⚠ N’essayez pas de démonter ou de modifier le module ou de réparer le module en privé ; sinon, cela peut entraîner une défaillance du produit, un incendie ou des blessures corporelles.
- Après avoir remplacé le module CPU, vérifiez que tous les programmes et les paramètres sont créés dans le nouveau module CPU et sont dûment définis. Ensuite, vous pouvez démarrer le système PLC pour empêcher le composant contrôlé d’exécuter une fausse action.
- Veuillez lire attentivement les manuels afin de vous familiariser avec les mécanismes de fonctionnement requis lorsque l’API est en cours d’exécution, comme le changement de procédure, la sortie forcée et RUN/STOP, etc. Le but est d’éviter une sortie incorrecte ou des dommages à l’équipement qui peuvent être causés par des opérations inexactes.
- Avant de toucher le module, veuillez d’abord toucher le métal de mise à la terre ou porter un bracelet antistatique afin de décharger l’électricité statique du corps humain pour éviter qu’il n’endommage le module.
- Lorsque vous utilisez un téléphone cellulaire ou un appareil de communication, veuillez garder une distance appropriée pour éviter d’interférer avec le système et de provoquer une fausse action.
- N’installez pas le système de contrôle PLC dans un environnement exposé à la lumière directe du soleil ou à l’humidité.
- Veuillez confirmer qu’une distance appropriée a été maintenue entre le système de contrôle PLC et la source de chaleur telle que la bobine, le radiateur et la résistance, etc. pour éviter que le composant ne soit exposé à une température plus élevée.
- Veuillez installer un système d’arrêt d’urgence de l’alimentation et un dispositif de protection contre les surintensités au besoin afin de protéger le système de contrôle PLC.
- Pendant le processus d’exploitation et de maintenance, veuillez vérifier la stabilité de l’installation afin d’éviter des vibrations inattendues susceptibles d’endommager le système de contrôle PLC et le composant contrôlé.
20-3 Daily Maintenance
The connection terminal may present loosening signs after running the PLC System for a longer time. To maintain the PLC System at normal operating status, the inspection should be executed according to daily maintenance items after confirming that the ambient environment meets the environmental specifications that are specified in Chapter 3. When discovering any abnormal signs, please make improvements immediately according to the specified troubleshooting method.
20-3-1 Maintenance Tools
- Screwdriver
- Stain removing alcohol
- Cleaning cotton rag
- Swab
20-3-2 Daily Maintenance Items
Daily maintenance items
|
No. |
Inspection Item |
Job Content |
Judgment Standard |
Action |
|
|
1 |
Appearance cleanliness |
Visual inspection |
If there are any stains. |
Wipe off the stains. |
|
|
2 |
Appearance completeness |
Visual inspection |
If there is any damage. |
Wipe off the stains. |
|
|
3 |
Back board and DIN Rail installation status |
If the back board and the DIN rail are securely installed. |
The back board and the DIN rail must be securely installed. |
Check if the back board and the rail are properly installed. |
|
|
4 |
Locking status of module connection area |
If the locking of module connection area is detaching or loosening. |
The locking device of the module connection area must be located at the locking position. |
Move the locking device of the module connection area back to the locking position. |
|
|
5 |
Appearance of wiring cable |
If the wiring cable is damaged. |
The wiring cable shall be intact without any damage. |
Replace the wiring cable. |
|
|
6 |
Connection status of each terminal |
If the terminal is loosening. |
The terminal cannot present any loosening sign. |
Connect the terminal properly. |
|
|
7 |
Power module |
PWR lamp |
If the PWR lamp is ON. |
The PWR lamp must be ON. |
For detailed troubleshooting, please refer to “Expansion Module Troubleshooting” section. |
|
8 |
Expansion module |
PWR lamp |
If the PWR lamp is ON. |
The PWR lamp must be ON. |
|
|
RUN lamp |
If the RUN lamp is ON. |
The RUN lamp must be ON. |
|||
|
ERR lamp |
If the ERR lamp is OFF. |
The ERR lamp must be OFF. |
|||
|
ALM lamp |
If the ALM lamp is OFF. |
The ALM lamp must be OFF. |
|||
* Remove the expansion module and then use a swab to wipe off the dust and stains present in inaccessible corners.
20-4 Regular Maintenance
When the routine daily maintenance is required, the module should be serviced cyclically according to the actual operating environment. The inspection should be executed according to daily maintenance items after confirming that the ambient environment meets the environmental specifications that are specified in Chapter 3. When discovering any abnormal signs, please make improvement immediately according to the specified troubleshooting method.
20-4-1 Maintenance Tools
- Screwdriver
- Stain removing alcohol
- Cleaning cotton rag
- Swab
- Multimeter
- Temperature gauge
- Hygrometer
20-4-2 Regular Maintenance Items
Regular maintenance items table.
|
No. |
Inspection Item |
Job Content |
Judgment Standard |
Action |
|
1 |
Environmental temperature and humidity |
Measure with temperature gauge and hygrometer. |
Must meet the environmental specifications established for the respective module. |
Confirm the reasons causing the environmental change and then remove the problem. |
|
2 |
Air |
Measure the corrosive gas |
Corrosive gas should not be detected. |
|
|
3 |
Power voltage |
Measured the supplied AC power. |
Must meet the power module specifications. |
Confirm the power supply system. |
|
4 |
Dust/stain attaching status |
Check the appearance |
If any dust and stain. |
Wipe off the dust and the stains. |
|
5 |
Module installation status |
Check if the module is securely installed. |
The module must be securely installed. |
For correct installation method, please refer to “Installation and Wiring” section. |
|
6 |
Locking status of connection area between modules |
If the locking of module connection area is detaching or loosening. |
The locking device of the module connection area must be located at the locking position. |
Move the locking device of the module connection area back to the locking position. |
|
7 |
Terminal connection status |
Check by plugging and unplugging the connection port. |
The terminal cannot present any loosening signs. |
Connect the terminal properly. |
|
8 |
Appearance of wiring cable |
If the wiring cable is presenting any damage signs. |
The wiring cable should be intact without any damage. |
Replace the wiring cable. |
|
9 |
PLC System diagnosis |
Check the error record. |
Caused by careless error. |
For detailed troubleshooting, please refer to “Expansion Module Troubleshooting” section. |
|
10 |
Max. scanning time |
Check the status value of R35371 through the monitoring page. |
The maximum scanning time must be without the scope allowed by the system specifications. |
Check the reasons causing the extension of scanning time. |
* Remove the expansion module and then use a swab to wipe off the dust and stains present in inaccessible corners.
Tip: press ← → to switch chapters, Ctrl+K to search