Posted in

By

12 of 15Updated 2026-11-1710 min read中文版

This section describes the operating procedure required for executing the PLC online and offline as well as the PLC program starting and stopping operations. Provided below are detailed operation methods required for executive the respective communication

11-1 Connection

It allows the user to connect with the PLC function for changing current online parameters and creating online list, etc.

From the function bar [PLC] → [Connection Parameter], you can set the default connection parameter, which can be used directly for subsequent connections without additional settings.

D:\patrick\更換手冊圖片\圖_en\238.PNG

Fig. 240: Connection Parameter

Page

Connection Type

Attribute

Description

Network Connection

Select the network interface card users want to use.

Basic

Ethernet

Type

Network online type, in TCP or UDP.

IP Address

Connected PLC network address

Communication Port

Connected PLC network port.

Network Connection Info

Display the current network interface card information.

Search

Search the PLC network address existing on the network.

USB

USB

Select the M-PLC USB port that is currently connected to the computer.

Advanced

Timeout (ms)

PLC response timeout setting, the setting range is 100-30000 ms.

Retest Frequency

Communication failure retest time setting, the setting range is 0-10 times

Command Delay (ms)

The delay time setting of each communication, the setting range 0-1000 ms.

Other Settings

Connection List

A list of frequently used connections can be set, and the connection information can be quickly brought in by clicking the drop-down menu option.

Connection Test

Use the current parameters to perform a quick connection test to confirm that the connection parameters are valid parameters.

Be sure to ask before connecting

When checked, the connection parameter window will be displayed before each connection action. If it is not checked, the previous connection parameters will be used to directly connect.

Connection List

Click [Connection Parameter List] → [Connection List] in scroll-down menu and you will be allowed to create the Connection List.

Fig. 241: Connection Parameter List

Connection Test

Click [Connection Parameter List] → [Connection Test] to perform a quick connection test with the current parameter.

[

11-2 Offline Edit

Under PLC online status, click “PLC” → “Offline edit” in function toolbar and you will be allowed to execute the offline editing.

11-3 Upload

Such function allows users to upload the PLC project to PC for preparing backup copy or for inspection.

The operation process differs depending on whether the project is opened or not, as detailed below:

11-2-1 Upload with Open Project

  1. Select the tab page [PLC] → [Upload], and use the set connection parameters to connect.
  2. After connecting, compare the currently opened project with the PLC project.
  3. When the comparison is the same, [The current project matches the connected PLC] will show.

  1. When the compare is not matched, a compare window will be displayed to allow the user to select the part to be uploaded.

D:\patrick\更換手冊圖片\圖_en\242.PNG

Fig. 242: Selecting the uploaded data

  1. Click [Upload] to start uploading until the progress window is completed.

11-2-2 Upload with Closed Project

  1. Select the tab page [PLC] → [Upload]
  2. Ask “Do you open the relevan project?”
    1. Click [Yes] → The action is the same as Section 11-3-1.
    2. Click [No] → The connection parameters will be forcibly asked, and the connection will be performed using the set connection parameters.

D:\patrick\更換手冊圖片\圖_en\241.PNG

Fig. 243: Opening the relevant project

  1. After connecting, the user can choose the data to be uploaded.

D:\patrick\更換手冊圖片\圖_en\244.PNG

Fig. 244: Uploading the data

  1. Click [Upload] to start uploading until the progress window is completed.

11-4 Download

Such function allows the user to download the PLC project being planned in PC to the PLC.

  1. Select the tab page [PLC] → [Upload], and use the set connection parameters to connect.
  2. After connecting, compare the currently opened project with the PLC project.
  3. When the compare is the same, [The current project matches the connected PLC] will show.

  1. When the compare is not matched, a compare window will be displayed to allow the user to select the part to be downloaded.

D:\patrick\更換手冊圖片\圖_en\245.PNG

Fig. 245: Selecting the data to be downloaded

  1. If the compare is different, and there are syntax errors or inconsistent modules, only the upload function is provided.

  1. Click [Download] to start downloading until the progress window is completed.

11-5 Run/Stop PLC

Run PLC

When operated under online monitoring status, click [PLC] → [Run] in function toolbar or you may press “F9” quick key.

Fig. 246: Running PLC

Stop PLC

When operated under online monitoring status and when PLC is under Running Mode, click [PLC] → [Stop] in function toolbar.

Fig. 247: Stopping PLC

11-6 Clear PLC

When operated under online status, click [PLC] → [Clear PLC Data] in function toolbar, and [Clear All (Initialization)], [Clear Program Only], [Clea Registers Only], and [Clear Coils Only] options will appear as below:

D:\patrick\更換手冊圖片\圖_en\248.PNG

Fig. 248: Clearing PLC data

Function

Description

Clear All

Clear all PLC data and restore factory settings

Clear Program Only

Clear the program data in the PLC, including motion control data.

Clea Registers Only

Reset all register values ​​in the PLC.

Clear Coils Only

Reset all coils ​​in the PLC.

11-7 PLC Status

When operated under online status, click [PLC] → [PLC Status] in function toolbar and the data will appear as below:

Fig. 249: PLC status

Function

Description

Station Number

Station number of the connected main unit.

Main Unit Type

Type of the connected main unit.

Main Unit Status

Working status of the connected main unit.

PLC OS Version

Firmware version of the connected main unit.

MC OS Version

Motion control firmware version of the connected main unit.

HW Version

Hardware version of the connected main unit.

Memory Pack

Whether the connected main unit is installed with a memory card.

Syntax Check

Program syntax checking condition of the connected main unit.

Data Password

Whether to set data password on the connected main unit.

Program ID

Whether to set Program ID on the connected main unit.

PLC ID

Whether to set PLC ID on the connected main unit.

Upload Protection

Whether to set upload protection on the connected main unit.

Download Protection

Whether to set download protection on the connected main unit.

Calendar

Whether the connected main unit is installed with RTC.

Total Capacity of Program

Total program capacity of the connected main unit.

Used Capacity of Program

Used program capacity of the connected main unit.

Free Capacity of Program

Free program capacity of the connected main unit.

MAC Address

MAC address of the connected main unit.

HWID

HWID of the connected main unit.

iMonitor Status

The iMonitor status of the connected main unit, including offline, online, connecting and error status.

11-8 PLC Setting

11-8-1 PLC ID Setting

When the PLC ID set by the PLC is different from the Program ID, the PLC cannot operate normally. The PLC ID can be set through the execution function bar [PLC]→[PLC Setting]→[PLC ID]. The ID rule is setting with 8 uppercase alphanumeric letters.

D:\patrick\更換手冊圖片\圖_en\250.PNG

Fig. 250: Setting PLC ID

11-8-2 RTC Setting

When the PLC is under “Online” and “Run” status, the user will be allowed to click [PLC] → [PLC Setting] → [RTC]. After that, the following window will appear for the user to set up the perpetual calendar time required for the PLC.

Fig. 251: Setting RTC

Function

Description

Current Time

Date and time of the currently connected main unit.

Setting Time

To set the date and time to the currently connected main unit.

Use Time of PC

When checked, the current computer time will be used as the setting time.

Setup to PLC

When clicked, the setting time will be written directly to the currently connected main unit.

11-8-3 Firmware Update

Select the function bar [PLC] → [PLC Setting] → [Firmware Update], and select the corresponding firmware file and start updating, until the progress window is closed and the prompt window showing the completion of the update is displayed. Wait until the light is displayed normally and then just restart the main unit. The extension of the firmware update file is *.os.

Fig. 252: Firmware Update

11-9 Quick Control

The Quick Control operation is for the convenience of the user. When the connection parameters are set correctly, the PLC can be connected to perform some operations without complete synchronization of data.

D:\patrick\更換手冊圖片\圖_en\256.PNG

Fig. 253: Quick Control

11-9-1 Get System Status of PLC

Under the state of offline edit, when the connection parameters are set correctly, click [PLC] → [Quick Control] → [Get System Status of PLC] on the function bar to read various information of the PLC under offline conditions , the content is the same as section 11-7.

11-9-2 Initialize PLC

Under the state of offline edit, when the connection parameters are set correctly, click [PLC] → [Quick Control] → [Initialize PLC] on the function bar to initialize the PLC under offline conditions.

11-9-3 Run PLC

Under the state of offline edit, when the connection parameters are set correctly, click [PLC] → [Quick Control] → [Run PLC] on the function bar to run PLC under offline conditions.

11-9-4 Stop PLC

Under the state of offline edit, when the connection parameters are set correctly, click [PLC] → [Quick Control] → [Stop PLC] on the function bar to stop PLC under offline conditions.

11-9-5 Memory Card Opearation

Under the state of offline edit, when the connection parameters are set correctly, click [PLC] → [Quick Control] → [Memory Card Opearation] on the function bar to configure related PLC settings under offline conditions.

Fig. 254: Memory card configuration

For detailed setting description, please refer to Chapter 14-2.

11-10 Online Edit

The online editing function can directly change the program and project content on UperLogic page, so that users can make on-site adjustments during the final debugging of the program design.

When using the online editing function in the running state of the PLC, if the wrong method was used, it may bring great harm to the device and operators, and users need to carefully check the content during operation.

11-10-1 Starting Online Edit

The process is shown below:

  1. Click to execute the function bar [PLC] → [Online Edit] when the PLC is connected.

Fig. 255: Online Edit

  1. After connecting, compare the current project with the PLC project.
    1. If the comparison is the same, skip directly to Step 4。
    2. When the comparison is different, the compare window will be displayed to prompt the different parts. Since it is necessary to synchronize the project and PLC data to enter the online editing mode, the user can choose to download the project or upload the PLC data for synchronization.

    1. When the comparison is different and the syntax check is wrong or the module list is inconsistent, you can only enter the online editing mode after selecting to upload PLC data for synchronization.

  1. After clicking the sync direction, wait for the progress window to complete.
  2. After the synchronization is completed, it will enter the online editing mode and display the PLC status window.

11-10-2 Trial Run

When editing online, the changed part of the project or program will not be written into the PLC immediately, but must be written to the PLC running section through the trial run mechanism to make the current changed part take effect. Click [PLC] → [Trial Run] in the function bar to perform a test run on the PLC.

Fig. 256: Trial Run

11-10-3 Discard Change

When editing online, if the debugging result after editing is not as expected, the project can be restored to the previous state through [Discard Change]. This operation only restores the project, if you need to restore the PLC data, you need to perform a trial run again.

Click [PLC] → [Discard Change] on the function bar to restore the previous status.

Fig. 257: Discard Change

Function

Description

Content of the Previous Trial Run

Restore to the content of the project at the time of the previous trial run.

Content before Online Editing

Restore to the project content when entering online editing.

11-10-4 Finishing Online Edit

The debugging content during online editing will only exist in the PLC running section, so when you leave the online editing mode, you need to re-download the current project content to the PLC. Please note: this operation will stop the action. Switching from [Online Edit] to [Offline Edit] or [Online Monitor], the following prompt window will appear, allowing the user to select the data to be stored in the PLC.

Function

Description

Current Content

When the current project content is written to the PLC.

Contents of Previous Trial Run

Restore to the content of the project during the previous trial run and write it to the PLC

Content before Online Edit

Restore to the project content when entering online editing and write it to PLC

Restart the PLC after the operation is complete

When checked, restart the PLC after the write to PLC operation is completed

Was this page helpful?

Tip: press ← → to switch chapters, Ctrl+K to search