EtherCAT Function and Configuration

This section describes the EtherCAT related function and configuration. EtherCAT is an industrial Ethernet technology developed by Beckhoff Automation in Germany. The connection type is a network system with one master station and multiple slave stations. It is also a configuration tool based on EtherCAT Slave Information (ESI). Currently, the PDO is designed in fixed type and it is not opened for the user to set manually. Indicated below is the setting page:

Listed below is the PDO setting:

PDO Type

Index

Name

RxPDO

0x6040

Control word

0x607A

Target position

0x60FF

Target velocity

0x6071

Target Torque

0x6060

Mode Of Operation

0x60B8

Touch Probe Function

TxPDO

0x6041

Status Word

0x6064

Actual Position

0x606C

Velocity actual value

0x6077

Actual Torque

0x6061

Mode Of Operation Display

0x60FD

Digital inputs

0x603F

Error code

0x60BA

Touch Probe Pos1 Pos Value

Provided below are the parameters and the unit required for the cyclic synchronous position, speed and torque control modes.

Target under Cyclic Synchronous Position Control (CSP) Mode:

Index

Name

Unit

Type

Access

PDO Mapping

603Fh

Error Code

–

U16

RO

TxPDO

6040h

Control Word

–

U16

RW

RxPDO

6041h

Status Word

–

U16

RO

TxPDO

6062h

Position Demand Value

pulse

I32

RO

TxPDO

6064h

Position Actual Value

pulse

I32

RO

TxPDO

6065h

Following Error Window

pulse

U32

RW

No

6072h

Max Torque

0.1%

U16

RW

RxPDO

6077h

Torque Actual Value

0.1%

I16

RO

TxPDO

607Ah

Target Position

pulse

I32

RW

RxPDO

6080h

Max Motor Speed

r/min

U32

RW

RxPDO

60B0h

Position Offset

pulse

I32

RW

RxPDO

60B1h

Velocity Offset

Command unit/s

I32

RW

RxPDO

60B2h

Torque Offset

0.1%

I16

RW

RxPDO

60F4h

Following Error Actual value

pulse

I32

RO

TxPDO

60FDh

Digital Inputs

–

U32

RO

TxPDO

Target under Cyclic Synchronous Speed Control (CSV) Mode:

Index

Name

Unit

Type

Access

PDO Mapping

603Fh

Error Code

–

U16

RO

TxPDO

6040h

Control Word

–

U16

RW

RxPDO

6041h

Status Word

–

U16

RO

TxPDO

6072h

Max Torque

0.1%

U16

RW

RxPDO

6080h

Max Motor Speed

r/min

U32

RW

RxPDO

60B1h

Velocity Offset

Command unit/s

I32

RW

RxPDO

60B2h

Torque Offset

0.1%

I16

RW

RxPDO

60FFh

Target Velocity

Command unit/s

I32

RW

RxPDO

Target under Cyclic Synchronous Torque Control (CST) Mode:

Index

Name

Unit

Type

Access

PDO Mapping

603Fh

Error Code

–

U16

RO

TxPDO

6040h

Control Word

–

U16

RW

RxPDO

6041h

Status Word

–

U16

RO

TxPDO

6071h

Target Torque

0.1%

U16

RW

RxPDO

6072h

Max Torque

0.1%

U16

RW

RxPDO

6080h

Max Motor Speed

r/min

U32

RW

RxPDO

60B2h

Torque Offset

0.1%

I16

RW

RxPDO

Was this page helpful?