Motion Probe

The probe function is used to precisely capture the position of an axis or detect specific events during motion.

18-1 Probe Number

The touch probe triggers through an external DI signal of the drive or Z signal of the encoder, based on the user’s configuration of either the rising or falling edge.

0: Off

1: Input with external signal

2: Use encoder Z-phase signal

18-2 Probe Mode

0: Single trigger, Rising trigger

1: Continuous trigger, Rising trigger

2: Single trigger, Falling trigger

3: Continuous trigger, Falling trigger

18-3 Information of Probe Register

Special registers and special relays used for the probe function.

No.

Name

Description

M10617+ 40*(n-1)

Axis Probe 1 Function ON

High Pos: ON
Low Pos: Off

M10618+ 40*(n-1)

Axis Probe 1 Function Reset

Rising Trigger

M10619+ 40*(n-1)

Axis Probe 2 Function ON

High Pos: ON
Low Pos: Off

M10620+ 40*(n-1)

Axis Probe 2 Function Reset

Rising Trigger

M11262+ 40*(n-1)

Axis Probe 1 Triggering Status

High Pos: Status ON

Low Pos: StatusOFF

M11263+ 40*(n-1)

Axis Probe 2 Triggering Status

High Pos: Status ON

Low Pos: StatusOFF

DR37042+ 150*(n-1)

Axis Driver Probe 1 Coordinates

Displays probe coordinates for axis drive feedback

DR37044+ 150*(n-1)

Axis Driver Probe 2 Coordinates

Displays probe coordinates for axis drive feedback