3-1 Modbus Address Mapping Table
|
Component Name |
M PLC |
FBS |
||
|
Device Range |
Modbus Address Range |
Device Range |
Modbus Address Range |
|
|
Contact Setting |
||||
|
Output Relay [Y] |
Y0 – Y1023 |
000001−001024 |
Y0 – Y255 |
000001 – 000256 |
|
Input Contact [X] |
X0 – X1023 |
010001−011024 |
X0 – X255 |
001001 – 001256 |
|
Internal Relay [M] |
M0 – M25599 |
020001−045600 |
M0 – M2001 |
002001 – 004002 |
|
Step Relay [S] |
S0 – S3103 |
050001−053104 |
S0 – S999 |
006001 – 007000 |
|
Timer Contact [T] |
T0 – T1023 |
054001−055024 |
T0 – T255 |
009001 – 009256 |
|
Counter Contact [C] |
C0 – C1279 |
056001−057280 |
C0 – C255 |
009501 – 009756 |
|
Register Setting |
||||
|
Data Register [R] |
R0 – R47319 |
400001−447320 |
R0 – R4167 |
400001 – 404168 |
|
R5000 – R5998 |
405001 – 405999 |
|||
|
Data Register [D] |
D0 – D7999 |
448001−456000 |
D0 – D2998 |
406001 – 408999 |
|
Timer Current Value [T] |
T0 – T1023 |
460001−461024 |
T0 – T255 |
409001 – 409256 |
|
16-bit Counter Value [C] |
C0 – C1023 |
462001−463024 |
C0 – C199 |
409501 – 409700 |
|
32-bit Counter Value [C] |
C1024 – C1279 |
464001−464512 |
C200 – C255 |
409701 – 409812 |
Tip: press ← → to switch chapters, Ctrl+K to search