3-1 Modbus Address Mapping Table

Component Name

M PLC

FBS

Device Range

Modbus Address Range

Device Range

Modbus Address Range

Contact Setting

Output Relay [Y]

Y0 – Y1023

000001−001024

Y0 – Y255

000001 – 000256

Input Contact [X]

X0 – X1023

010001−011024

X0 – X255

001001 – 001256

Internal Relay [M]

M0 – M25599

020001−045600

M0 – M2001

002001 – 004002

Step Relay [S]

S0 – S3103

050001−053104

S0 – S999

006001 – 007000

Timer Contact [T]

T0 – T1023

054001−055024

T0 – T255

009001 – 009256

Counter Contact [C]

C0 – C1279

056001−057280

C0 – C255

009501 – 009756

Register Setting

Data Register [R]

R0 – R47319

400001−447320

R0 – R4167

400001 – 404168

R5000 – R5998

405001 – 405999

Data Register [D]

D0 – D7999

448001−456000

D0 – D2998

406001 – 408999

Timer Current Value [T]

T0 – T1023

460001−461024

T0 – T255

409001 – 409256

16-bit Counter Value [C]

C0 – C1023

462001−463024

C0 – C199

409501 – 409700

32-bit Counter Value [C]

C1024 – C1279

464001−464512

C200 – C255

409701 – 409812