13.1 The selection and calculation method for regenerative resistors.
When the direction of the motor’s torque and speed is opposite, the power generated from the load side will be
transmitted back to the drive, and the regenerative resistors is needed to dissipate the rally power to avoid drive failure.
1. Find the inertia and speed of the servo Motor according to the table below
|
Voltage |
Motor Wattage |
Rated speed (rev/min) |
motor inertia (×10-4 Kg*m2) |
|
AC 220V |
100W(brakeless) |
3000 |
0.067 |
|
100W(braked) |
3000 |
0.067 |
|
|
200W(brakeless) |
3000 |
0.26 |
|
|
200W(braked) |
3000 |
0.28 |
|
|
400W(brakeless) |
3000 |
0.49 |
|
|
400W(braked) |
3000 |
0.51 |
|
|
750W(brakeless) |
3000 |
1.51 |
|
|
750W(braked) |
3000 |
1.71 |
|
|
1KW(brakeless) |
2000 |
13.88 |
|
|
1KW(braked) |
2000 |
15.78 |
|
|
1.5KW(brakeless) |
2000 |
18.57 |
|
|
1.5KW(braked) |
2000 |
20.24 |
|
|
2KW(brakeless) |
2000 |
23.69 |
|
|
2KW(braked) |
2000 |
25.36 |
|
|
AC 380V |
400W(brakeless) |
3000 |
0.49 |
|
400W(braked) |
3000 |
0.51 |
|
|
750W(brakeless) |
3000 |
1.51 |
|
|
750W(braked) |
3000 |
1.71 |
|
|
1KW(brakeless) |
1500 |
16.04 |
|
|
1KW(braked) |
1500 |
17.71 |
|
|
2KW(brakeless) |
2000 |
23.69 |
|
|
2KW(braked) |
2000 |
25.36 |
|
|
2.9KW(brakeless) |
1500 |
56.8 |
|
|
2.9KW(braked) |
1500 |
65.3 |
|
|
4KW(brakeless) |
2000 |
56.8 |
|
|
4KW(braked) |
2000 |
65.3 |
|
|
5.5KW(brakeless) |
2000 |
78.2 |
|
|
5.5KW(braked) |
2000 |
86 |
|
|
7.5KW(brakeless) |
1500 |
130 |
|
|
7.5KW(braked) |
1500 |
140 |
|
|
13KW(brakeless) |
1500 |
272.8 |
|
|
15KW(brakeless) |
1500 |
248 |
2. Calculate the rotational energy(ES) generated during servo operation using the formula.
ES = J × (nM)2/182 (Joules)
J = JM + JL
JM:Servo motor moment of inertia (kg·m2)
JL:Load moment of inertia at motor shaft (kg·m2)
nM:Servo motor operating motor speed (min-1)
3. Calculation Procedure for Regenerative Resistor Capacity

WK = ES /(0.2 × T)
Note: 1. The 0.2 in the equation for calculating WK is the value when the regenerative resistor’s utilized load ratio is 20%.
WK:Required regenerative resistor capacity (W)
ES:rotational energy
T:Servomotor repeat operation cycle (s)
If the value of WK does not exceed the capacity of the built-in regenerative resistor of the ServoDrive, an External Regenerative Resistor is not required. For details on the built-in regenerative resisters, refer to the ServoDrive specifications. If the value of WK exceeds the capacity of the built-in regenerative resistor, install an External Regenerative Resistor with a capacity equal to the value for W calculated above