2-1 IO Coupler Panel Interface and Function Description

2-1-1 NetworkType IO Coupler

Chapter 2 IO Coupler Interface and Peripheral Functions - 1

2-1-2 Network Type IO Coupler – MC0EN Panel Interface Description

Number

Name

Functions

1.

LED Status Indicators

Display IO Coupler operational status

2.

Rotary Switch

Used to adjust the IP address of the IO Coupler.

3.

USB Type-C Port

Used for connecting USB Type-C data cable.

4.

Slide Switch

Used for restoring factory settings.

5.

RJ45 Network Port

Used for connecting network cables (RJ-45). Interface for connection (used for 10BASE-T/100BASETX).

▲ Introduction to the Functions of Network-type IO Coupler MC0EN Panel

2-1-3 LED Status Indicators

Chapter 2 IO Coupler Interface and Peripheral Functions - 2

▲IO Coupler LED Indicator Diagram

Number

Name

Explanations

1

PWR

Power Indicator Light:

Yellow-green

Constantly lit when powered on

2

RUN

Run Indicator Light:

Yellow-green

Flashes 10 times/second: System running

Flashes 1 time/second: System running, ready to restore factory default settings

3

ERR1

Error Message Light 1:

ERR2

Error Message Light 2:

Red

ERR1: Off, ERR2: Off: System normal.

ERR1: On, ERR2: Off: ERR_SERVICE persistent task-related error.

ERR1: Off, ERR2: On: ERR_IO expansion module-related error.

ERR1: On, ERR2: On: ERR_SYS major system error.

▲Explanation of IO Coupler Panel Indicator Lights

2-1-4 Rotary Switch

Chapter 2 IO Coupler Interface and Peripheral Functions - 3

▲The position of the rotary switches on the IO Coupler

On the upper half of the IO Coupler body, there are two rotary switches, allowing users to quickly adjust the value of the last byte of the IP address on-site, without the need to connect software for configuration.

Users can also confirm the adjustments by referring to the engraved values on the body of the device during on-site use.

The X1 rotary switch on the top represents the hexadecimal value on the right side,

the X16 rotary switch on the bottom represents the hexadecimal value on the left side.

In addition, the rotary switch ‘Switch’ also supports enabling DHCP mode.

The relevant hexadecimal values and their meanings are described in the following table.

Please note that the IP settings of the IO Coupler will be based on the settings of the rotary switches on the IO Coupler upon reboot. If the IP of the IO Coupler is remotely configured using software during operation, please adjust the rotary switches to the corresponding settings before restarting after power-off.

Name

Meanings

0x00

The IP position set by software

0x01 – 0xFE

Changing the value of the last byte of the IP address

0xFF

Enabling DHCP mode

▲Correspondence table for the rotary switches of the IO Coupler

For example: If X1 is set to “7” and X16 is set to “C”, it represents: 7*1 + 12*16 = 199, so the IP address is 192.168.0.199.

Chapter 2 IO Coupler Interface and Peripheral Functions - 4

2-1-5 USB Type-C Port

You can directly connect the IO Coupler to a computer with the UperIO editing software installed using a USB Type-C data cable (recommended operating system: Windows 7 or above) for communication.

Chapter 2 IO Coupler Interface and Peripheral Functions - 5

▲ The USB Type-C port of the IO Coupler

2-1-6 Slide Switch

There is a slide switch inside the left side cover plate of the device. By switching S0/S1 and reapplying power, you can restore the factory default settings.

To avoid accidental activation, please follow the procedure below carefully:

1. When powering off, move the slide switch to the ‘On’ position (S1).

2. After powering on, wait for the Run light to flash slowly, once per second. Then, move the slide switch to the ‘Off’ position (S0).

3. At this point, the device will be restored to factory default settings.

Please note that this slide switch is different from the Run/Stop switch on the PLC and does not control the Run/Stop function. Please ensure that its position is set to ‘Off’ (S0) before powering on to ensure the IO Coupler operates correctly.

Chapter 2 IO Coupler Interface and Peripheral Functions - 6

Chapter 2 IO Coupler Interface and Peripheral Functions - 7

▲The position of the slide switch on the IO Coupler

2-1-7 RJ45 Network Port

You can communicate with the upper control device through an RJ45 network connection cable. Alternatively, you can communicate with a computer installed with UperIO editing software (Windows 7 or above is recommended) via a network connection.

The RJ45 port in question has no distinction between IN/OUT.

Chapter 2 IO Coupler Interface and Peripheral Functions - 8

Chapter 2 IO Coupler Interface and Peripheral Functions - 9

▲Network Port Pinout Diagram

Number

Name

Description

Terminal number

Direction

Description

1

Link / Activity

Connection status indicator light:

orange color

Solid Off: Invalid Link。

Flashing: Dark for 80 ms, then bright for 80 ms:TX/RX Activity。

Solid On: Invalid Link。

1

TD+

Transmit data (+)

2

TD-

Transmit data (-)

3

RD+

Receive data (+)

4

2

IP Status

IP status indicator light:

green color

Solid Off: No IP Address Obtained

Flashing once per second in DHCP mode: Obtaining IP Address

Solid On: IP Address Obtained

5

-

6

RD-

Receive data (-)

7

-

8

-

2-2 IO COUPLER Specifications

2-2-1 General specifications

Model

MC0EN

Power consumption

DC24V±20% 80mA

Operating

environment

Operating

temperature

0~55℃

Operating

humidity

5~95%RH(No condensation)

Atmospheric

environment

No significant dust, should not be exposed to corrosive gases

Storage

temperature

-25~70℃

Altitude

Below 2000 meters

Pollution

level

Degree II

Seismic

resistance

5 to 8.4Hz Half-amplitude: 3.5mm

8.4 to 150 Hz Constant acceleration: 19.6m/s2 (2G)

3 directions of X, Y, Z: 10times (IEC61131-2 compliants)

Impact

resistance

10G, three times for each direction of 3 axes

Immunity to

interference

1500Vp-p,Pulse width 1us

Voltage

tolerance

1500 VAC 1 minute between power terminals and input/output terminals, and between all external terminals and the casing.

Applicable standards

CE*、UL* *applying

▲General specifications for IO Couplers

2-2-2 IO Coupler specifications.

Network type IO Coupler specifications

Model and item

MC0EN

Communication protocol

Modbus TCP/IP, EtherNet/IP adapter

Maximum expandable modules

Up to 16 expansion modules are supported.

(Only local IO expansion, does not support advanced or high-speed expansion modules)

Through the I/O Bus extension module, it can support up to 64 units.

Expanded I/O connection quantity

Digital input points

1024

Digital output points

1024

Analog input/output channels

Total channels 256

Expanded I/O module data length

Input: Below 1024 Bytes

Output: Below 512 Bytes

Ethernet/IP Number of connections

16

Ethernet/IP Supported functions

Periodic communication (Class1)

Message communication (Class 3, UCMM)

Ethernet/IP Periodic communication

Input: Below 128 Bytes

Output: Below 64 Bytes

Ethernet/IP Message communication

Receive: Below 504 Bytes

Transmit: Below 504 Bytes

Modbus TCP Number of connections

16

(Shared with FATEK Protocol. If connecting IO Coupler via ethernet port, then the number of connections will be 15)

Communication interface

ETHERNET

10/100 Base-T,RJ-45 sockets*2,supports switch function

Transmission line

10Mbps:UTP or STP of category 3 or above (STP recommended)

100Mbps: UTP or STP of category 5 or above (STP recommended)

Transmission distance

Distance between devices within 100 meters

Topology

Daisy chain, Star, Tree

TCP/IP Maximum number of connections

16

Peripheral devices

(USB) port

Specifications

USB 2.0 specification – Type C connector (Device side)

Transmission

speed

Up to 12 Mbps

Transmission distance

Up to 2 meters

2-2-3 IO Coupler Dimensional Drawing

Chapter 2 IO Coupler Interface and Peripheral Functions - 10

▲Front view dimension diagram of IO Coupler

Chapter 2 IO Coupler Interface and Peripheral Functions - 11

▲Side view dimension diagram of IO Coupler

2-3 End Module

2-3-1 Specifications and Functions of End Module

Please connect to the far right of the IO Coupler series expansion module or special expansion module.

When using branch modules, the End Module must also be installed on the far-right side. Failure to connect may result in errors and abnormal operation.

Chapter 2 IO Coupler Interface and Peripheral Functions - 12

▲Three-dimensional view of the End Module

2-4 Management

This chapter will introduce how to connect to the IO Coupler and how to set the IO Coupler.

2-4-1 Connection Method

Click the Search button. Software will search according to the currently selected USB or Ethernet and individual network cards in the “Management Window” If Ethernet is selected, it will search all network cards. Additionally, a search menu will appear below the search button, allowing users to choose between USB or Ethernet for Coupler search. Once the search is completed, the results will be displayed in the management window.

Chapter 2 IO Coupler Interface and Peripheral Functions - 13

▲Search Coupler

※Notice: UperIO can only connect to one IO Coupler at a time, and only one connection method can be used at a time.

※Notice: When using Ethernet for connection, UperIO can only connect to one IO Coupler per network card.

Right-clicking the tree diagram of USB or Ethernet and individual network cards will bring up a search menu. Clicking on the menu will initiate the search. If selecting Ethernet, it will search all network cards.

Chapter 2 IO Coupler Interface and Peripheral Functions - 14

▲Network Scan

The search results will be displayed in the Coupler management window. User can right-click to connect or left-click on the target Coupler to connect.

Chapter 2 IO Coupler Interface and Peripheral Functions - 15

▲Coupler Connection

2-4-2 Coupler Settings

Double-clicking the Coupler icon with the left mouse button will open the Coupler setting page. This section will use MC0EN as an example.

Chapter 2 IO Coupler Interface and Peripheral Functions - 16

▲Coupler Connection

a. General Setting

Chapter 2 IO Coupler Interface and Peripheral Functions - 17

▲Coupler Setting Window

Category

Function

Explanation

Parameter

Device Name

Display the module name of the Coupler, which cannot be modified.

Device Description

User-defined Name

Client Idle Timeout Setting

Enable/Disable

Enable or Disable Client Idle Timeout

Client Timeout (seconds)

Set the time that automatically disconnected from the client, if no messages are received from them, in seconds.

IP Setting

IP Acquisition Mode

Set the IP acquisition mode, which includes Static and DHCP modes.

IP Address

Setting of Internet Address.

Subnet Mask

Setting of Subnet Mask

Default Gateway

Defaulted Setting of Gateway

Primary DNS

Server

Preferred DNS server setting

Secondary DNS

Server

Other DNS server setting

Mac address

Display Mac address

Firmware

Firmware Version

Display Firmware version

Update

Upgrade Firmware

▲General setting of Coupler

b. Access Rights

Access rights can restrict the connection IP of the client side. To prevent unauthorized users from stealing data. Double-click the blank field or right-click to add authorized connection IPs and ranges.

Chapter 2 IO Coupler Interface and Peripheral Functions - 18

▲Setting of Coupler Access Rights

c. Security

Set a password for protection. If a password is set, it must be entered before connecting to change the settings of the Coupler and its expansion modules. This prevents malicious individuals from altering related settings. To remove an existing password, simply enter the old password during modification and leave the new password field blank.

Chapter 2 IO Coupler Interface and Peripheral Functions - 19

▲Setting of Coupler Security

d. Service Ports Number

Chapter 2 IO Coupler Interface and Peripheral Functions - 20

▲Setting of Coupler Service Port Number

Category

Function

Explanation

Detail Introduction

Fatek Protocol

Primary Port

Default Network Port Setting of Fatek Protocol

Ethernet Communication Port for Downloading Projects

Secondary Port

Default Network Port Setting of Fatek Protocol

Ethernet Network Communication Port for Project Download

Modbus Protocol

Primary Port

Default Network Port Setting of Modbus Protocol

Selected this communication port when connecting to the Human-Machine Interface

Secondary Port

Default Network Port Setting of Modbus Protocol

Selected this communication port when connecting to the Human-Machine Interface

Chapter 2 IO Coupler Interface and Peripheral Functions - 21

Chapter 2 IO Coupler Interface and Peripheral Functions - 22

▲UperIO Parameter Setting for Downloading

▲Human-Machine Modbus Connection Settings for the Coupler

▲Explanation of Service Port Setting

2-4-3 Backup

Users can backup the configuration and settings of the current or project file’s expansion modules to the coupler. In the future, when an expansion module needs to be repaired, after replacing the module, there is no need to reconfigure it. The coupler will directly import the backed-up expansion module settings into the new module.

Chapter 2 IO Coupler Interface and Peripheral Functions - 23

a. Save as Project

Clicking ‘Save as Project’ allows the current configuration of the coupler to be saved as a project on the computer. In the future, you can use the UperIO software to open the project directly, modify the configuration settings, and download the project to the coupler.

b. Backup Current Expansion Module Configuration

Backup the configuration and settings of the currently connected modules to the coupler. This makes it convenient for future repairs of expansion modules, where the replacement can be done directly without the need for reconfiguration. The coupler will directly import the backed-up expansion module settings into the new module.

c. Backup Expansion Modules in the Project

Backup the project that already includes the configuration of expansion modules to the coupler. This makes it convenient for future configuration on-site, as you can first save the configuration and settings of the expansion modules to the coupler. When the coupler is connected to the expansion modules, the settings of the expansion modules will be imported directly.

Chapter 2 IO Coupler Interface and Peripheral Functions - 24

▲Backup Coupler Options

2-5 Hardware Installation and Wiring

This section introduces the assembly of the power module and IO Coupler, as well as the method for installing the mounting rail and wiring.

2-5-1 Installation

When connecting each module, please ensure that the power is disconnected and observe safety precautions.

Chapter 2 IO Coupler Interface and Peripheral Functions - 25

⚠ Attention

The End module must be installed on the last module on the far right side at all times.

Installation Position

Orientation: When installed inside the cabinet, the front panel of the CPU module must be horizontally facing forward.

Chapter 2 IO Coupler Interface and Peripheral Functions - 26

▲Module Installation Position Diagram

Clearance between Modules and Surroundings

IO COUPLERs are mounted vertically in a forward position, allowing for natural air convection cooling. Ensure there is a gap of at least 50mm above and below the IO Coupler for heat dissipation, as illustrated in the diagram below:

Chapter 2 IO Coupler Interface and Peripheral Functions - 27

▲Installation Gap Diagram

When the ambient temperature exceeds the working environment, consider methods such as forced air cooling or increasing the gap between the device and its surroundings to improve ventilation and reduce temperature. When using expansion modules, to mitigate heat effects, maintain a gap of at least 50mm between the upper and lower modules.

a. Module Assembly

IO Coupler and modules are interconnected with each other. Below, we’ll illustrate how to assemble the IO Coupler and power module as an example.

1. Release the side sliders located on the top and bottom of the right-hand module.

Place your fingers on the protruding part of the side slider and slide it towards yourself, which means sliding towards the front of the module, to put the module in the installation state.

Chapter 2 IO Coupler Interface and Peripheral Functions - 28

2. Insert the hooks of the right module into the hooks of the left module by pushing them to the left.

Align the left and right modules to keep them parallel, ensuring that the connectors on both sides are properly aligned for connection.

3. Lock the side sliders on the top and bottom of the right module.

Place your fingers on the protruding part of the side slider and push outward, away from yourself, towards the back of the module. This action locks the module in place.

Chapter 2 IO Coupler Interface and Peripheral Functions - 29

4. Finally, install the End module at the far right end of the row of modules.

Chapter 2 IO Coupler Interface and Peripheral Functions - 30

⚠Attention

Please make sure to securely use the side sliders to correctly fix the adjacent modules. If not properly fixed, it may cause looseness in the connection between modules, leading to abnormal operation of the PLC. After fixing, please test with your hand to ensure the connection is stable.

b. Securing DIN Rail

This section will explain how to install connected modules onto the D I N rail and how to remove them.

Installing onto the D I N rail

Chapter 2 IO Coupler Interface and Peripheral Functions - 31

1. Hook the upper groove of the D I N rail onto the upper mounting hook of each module.

2. Use a flat-head screwdriver to push the bottom mounting hook to the pulled-out position until you hear a “click” sound. Then, press the module against the D I N rail until it is snug, and push the bottom mounting hook back to the inserted position.

Chapter 2 IO Coupler Interface and Peripheral Functions - 32

In difficult installation scenarios, please remove all side sliders first. Once installed on the D I N rail, proceed with locking by reattaching the side sliders.

Chapter 2 IO Coupler Interface and Peripheral Functions - 33

Check whether the bottom mounting hook of the lower D I N rail is in the inserted (locked) position.

Chapter 2 IO Coupler Interface and Peripheral Functions - 34

Removal procedure

1. Use a flat-head screwdriver to flip the bottom mounting hooks to the unlocked position.

2. Following the reverse order of installation, remove the D I N rail from the modules.

c. Panel Assembly Precautions

When the IO Coupler is installed inside a control panel, it is essential to provide an appropriate operating environment.

Temperature control

Chapter 2 IO Coupler Interface and Peripheral Functions - 35

The environmental temperature within the control cabinet must be maintained within the range of 0°C to 55°C.

■ If necessary, the following methods can be adopted to maintain the appropriate temperature.

■ Provide sufficient space to ensure good air circulation.

■ Avoid installing the IO Coupler near devices that generate high heat, such as heaters, transformers, or high-power resistors.

■ If the environmental temperature exceeds 55°C, install cooling fans or air conditioning.

Operation and Maintenance

■ Try to isolate the IO Coupler from high-voltage equipment and power machinery as much as possible to ensure the safety of operation and maintenance tasks.

■ Ideally, install the IO Coupler at a height of 1.0 to 1.6 meters above the ground, as this is most suitable for setting up and operating the IO Coupler.

Enhance the anti-interference performance

When laying communication cables externally, consider the following points.

■ When using multi-core signal cable, do not route I/O lines together with other control cables within the same cable.

■ If a parallel layout is adopted, ensure there is a minimum gap of 300mm between wiring racks.

■ If it’s necessary to lay I/O wiring and power cables in the same cable tray or conduit, use grounded metal barriers or shielding between the cables for isolation.

Chapter 2 IO Coupler Interface and Peripheral Functions - 36

▲Suggested wiring diagram for interference immunity

2-5-2 Wiring

Wiring precautions

⚠ Attention

Please ensure that installation or wiring operations are not performed while the power is on, as this may result in electric shock to the operator or damage to the product.

Chapter 2 IO Coupler Interface and Peripheral Functions - 37

Ensure that the grounding symbol marked on the equipment is properly grounded to effectively prevent electric shock and equipment interference, which may lead to incorrect operation of the product.

When wiring peripherals to the IO Coupler, make sure to confirm whether the product specifications match the selected IO Coupler. Peripherals that do not match may encounter risks such as terminal configuration mismatch, mismatched power supply, inability to drive the device, or wiring short circuits causing fires and equipment damage.

It is essential to ensure that there are no foreign objects such as iron filings or wiring residues in each module. These foreign objects may cause fires, damage, or operational errors.

Chapter 2 IO Coupler Interface and Peripheral Functions - 38

※ Grounding

(1) It is necessary to use the correct independent grounding method.

(2) Please use a cable with a cross-sectional area greater than or equal to 2mm for grounding.

(3) Place the grounding point close to the IO Coupler and firmly secure the grounding cable.

a. Power Wiring

Power Supply Precautions

1. Please separate the power cords of the power supply module from those of other devices. If there is significant noise, consider adding an isolation transformer.

2. AC 110V, 220V, and DC 24V cables should be routed separately as much as possible. Power cables should be tightly twisted to prevent interference. They should also be connected to the modules with shorter lengths.

3. Do not bundle AC 110V, 220V, and DC 24V cables with the main circuit (high voltage and high current) or I/O signal lines and avoid placing these cables close to each other. If possible, keep these cables separated by at least 100mm.

4. To prevent surges caused by lightning strikes, install surge absorbers as shown in the diagram below.

※ Precautions

1. Separate the ground connected to the surge absorber from the ground of the IO Coupler system.

2. Select a surge absorber with an operating voltage not lower than the maximum allowable input voltage.

b. AC Power Wiring

Chapter 2 IO Coupler Interface and Peripheral Functions - 39

▲AC Power Circuit

1. Connect the FG (⏚) of the power module to the earth of the power supply as a reference ground to prevent abnormalities in the system.

2. The AC power line L and N are respectively connected to the L and N of the power module.

3. For AC input, the following should be noted:

The AC power input voltage has a wide range (100~240VAC). Connect the power supply to the L and N ends. If AC110V or AC220V is connected to the +24V and -24V input terminals, it will damage the IO Coupler. Users should pay special attention to this.

Use a wire with a diameter of 2mm or more for the grounding terminal of the power supply.

4. The DC power supply of the power module is for the power output side. Do not parallel it with other power supplies.

c. DC Wiring

1. The Remote IO series IO Coupler can be directly powered on via an external 24V DC power supply, as shown in the diagram below. Connect the 3-pin European standard wiring terminal plug to the power socket on the left side of the IO Coupler.

Chapter 2 IO Coupler Interface and Peripheral Functions - 40

▲DC Power Supply position

2. When connecting the DC power supply, be sure to ensure correct polarity connection to avoid damaging the equipment. Please follow the correct wiring as shown in the diagram below.

Chapter 2 IO Coupler Interface and Peripheral Functions - 41

▲DC Power Supply Terminals

※ Precautions

1. Separate grounding should be used; if separate grounding is not possible, please use common grounding. However, the length of the wires must be the same in this case.

2. Be sure to ground the FG terminal to avoid noise interference.

Chapter 2 IO Coupler Interface and Peripheral Functions - 42

Chapter 2 IO Coupler Interface and Peripheral Functions - 43

▲Grounding Recommendation Diagram

※This termination switch is reserved for future expansion and has no function at present.

Chapter 2 IO Coupler Interface and Peripheral Functions - 44