2-1 IO Coupler Panel Interface and Function Description
2-1-1 NetworkType IO Coupler

2-1-2 Network Type IO Coupler – MC0EN Panel Interface Description
|
Number |
Name |
Functions |
|
1. |
LED Status Indicators |
Display IO Coupler operational status |
|
2. |
Rotary Switch |
Used to adjust the IP address of the IO Coupler. |
|
3. |
USB Type-C Port |
Used for connecting USB Type-C data cable. |
|
4. |
Slide Switch |
Used for restoring factory settings. |
|
5. |
RJ45 Network Port |
Used for connecting network cables (RJ-45). Interface for connection (used for 10BASE-T/100BASETX). |
▲ Introduction to the Functions of Network-type IO Coupler MC0EN Panel
2-1-3 LED Status Indicators

▲IO Coupler LED Indicator Diagram
|
Number |
Name |
Explanations |
|
1 |
PWR Power Indicator Light: |
Yellow-green Constantly lit when powered on |
|
2 |
RUN Run Indicator Light: |
Yellow-green Flashes 10 times/second: System running Flashes 1 time/second: System running, ready to restore factory default settings |
|
3 |
ERR1 Error Message Light 1: ERR2 Error Message Light 2: |
Red ERR1: Off, ERR2: Off: System normal. ERR1: On, ERR2: Off: ERR_SERVICE persistent task-related error. ERR1: Off, ERR2: On: ERR_IO expansion module-related error. ERR1: On, ERR2: On: ERR_SYS major system error. |
▲Explanation of IO Coupler Panel Indicator Lights
2-1-4 Rotary Switch

▲The position of the rotary switches on the IO Coupler
On the upper half of the IO Coupler body, there are two rotary switches, allowing users to quickly adjust the value of the last byte of the IP address on-site, without the need to connect software for configuration.
Users can also confirm the adjustments by referring to the engraved values on the body of the device during on-site use.
The X1 rotary switch on the top represents the hexadecimal value on the right side,
the X16 rotary switch on the bottom represents the hexadecimal value on the left side.
In addition, the rotary switch ‘Switch’ also supports enabling DHCP mode.
The relevant hexadecimal values and their meanings are described in the following table.
Please note that the IP settings of the IO Coupler will be based on the settings of the rotary switches on the IO Coupler upon reboot. If the IP of the IO Coupler is remotely configured using software during operation, please adjust the rotary switches to the corresponding settings before restarting after power-off.
|
Name |
Meanings |
|
0x00 |
The IP position set by software |
|
0x01 – 0xFE |
Changing the value of the last byte of the IP address |
|
0xFF |
Enabling DHCP mode |
▲Correspondence table for the rotary switches of the IO Coupler
For example: If X1 is set to “7” and X16 is set to “C”, it represents: 7*1 + 12*16 = 199, so the IP address is 192.168.0.199.

2-1-5 USB Type-C Port
You can directly connect the IO Coupler to a computer with the UperIO editing software installed using a USB Type-C data cable (recommended operating system: Windows 7 or above) for communication.

▲ The USB Type-C port of the IO Coupler
2-1-6 Slide Switch
There is a slide switch inside the left side cover plate of the device. By switching S0/S1 and reapplying power, you can restore the factory default settings.
To avoid accidental activation, please follow the procedure below carefully:
1. When powering off, move the slide switch to the ‘On’ position (S1).
2. After powering on, wait for the Run light to flash slowly, once per second. Then, move the slide switch to the ‘Off’ position (S0).
3. At this point, the device will be restored to factory default settings.
Please note that this slide switch is different from the Run/Stop switch on the PLC and does not control the Run/Stop function. Please ensure that its position is set to ‘Off’ (S0) before powering on to ensure the IO Coupler operates correctly.


▲The position of the slide switch on the IO Coupler
2-1-7 RJ45 Network Port
You can communicate with the upper control device through an RJ45 network connection cable. Alternatively, you can communicate with a computer installed with UperIO editing software (Windows 7 or above is recommended) via a network connection.
The RJ45 port in question has no distinction between IN/OUT.


▲Network Port Pinout Diagram
|
Number |
Name |
Description |
Terminal number |
Direction |
Description |
|
1 |
Link / Activity Connection status indicator light: |
orange color Solid Off: Invalid Link。 Flashing: Dark for 80 ms, then bright for 80 ms:TX/RX Activity。 Solid On: Invalid Link。 |
1 |
TD+ |
Transmit data (+) |
|
2 |
TD- |
Transmit data (-) |
|||
|
3 |
RD+ |
Receive data (+) |
|||
|
4 |
|||||
|
2 |
IP Status IP status indicator light: |
green color Solid Off: No IP Address Obtained Flashing once per second in DHCP mode: Obtaining IP Address Solid On: IP Address Obtained |
5 |
- |
|
|
6 |
RD- |
Receive data (-) |
|||
|
7 |
- |
||||
|
8 |
- |
2-2 IO COUPLER Specifications
2-2-1 General specifications
|
Model |
MC0EN |
|
|
Power consumption |
DC24V±20% 80mA |
|
|
Operating environment |
Operating temperature |
0~55℃ |
|
Operating humidity |
5~95%RH(No condensation) |
|
|
Atmospheric environment |
No significant dust, should not be exposed to corrosive gases |
|
|
Storage temperature |
-25~70℃ |
|
|
Altitude |
Below 2000 meters |
|
|
Pollution level |
Degree II |
|
|
Seismic resistance |
5 to 8.4Hz Half-amplitude: 3.5mm 8.4 to 150 Hz Constant acceleration: 19.6m/s2 (2G) 3 directions of X, Y, Z: 10times (IEC61131-2 compliants) |
|
|
Impact resistance |
10G, three times for each direction of 3 axes |
|
|
Immunity to interference |
1500Vp-p,Pulse width 1us |
|
|
Voltage tolerance |
1500 VAC 1 minute between power terminals and input/output terminals, and between all external terminals and the casing. |
|
|
Applicable standards |
CE*、UL* *applying |
|
▲General specifications for IO Couplers
2-2-2 IO Coupler specifications.
Network type IO Coupler specifications
|
Model and item |
MC0EN |
||
|
Communication protocol |
Modbus TCP/IP, EtherNet/IP adapter |
||
|
Maximum expandable modules |
Up to 16 expansion modules are supported. (Only local IO expansion, does not support advanced or high-speed expansion modules) Through the I/O Bus extension module, it can support up to 64 units. |
||
|
Expanded I/O connection quantity |
Digital input points |
1024 |
|
|
Digital output points |
1024 |
||
|
Analog input/output channels |
Total channels 256 |
||
|
Expanded I/O module data length |
Input: Below 1024 Bytes Output: Below 512 Bytes |
||
|
Ethernet/IP Number of connections |
16 |
||
|
Ethernet/IP Supported functions |
Periodic communication (Class1) Message communication (Class 3, UCMM) |
||
|
Ethernet/IP Periodic communication |
Input: Below 128 Bytes Output: Below 64 Bytes |
||
|
Ethernet/IP Message communication |
Receive: Below 504 Bytes Transmit: Below 504 Bytes |
||
|
Modbus TCP Number of connections |
16 (Shared with FATEK Protocol. If connecting IO Coupler via ethernet port, then the number of connections will be 15) |
||
|
Communication interface |
ETHERNET |
10/100 Base-T,RJ-45 sockets*2,supports switch function |
|
|
Transmission line |
10Mbps:UTP or STP of category 3 or above (STP recommended) 100Mbps: UTP or STP of category 5 or above (STP recommended) |
||
|
Transmission distance |
Distance between devices within 100 meters |
||
|
Topology |
Daisy chain, Star, Tree |
||
|
TCP/IP Maximum number of connections |
16 |
||
|
Peripheral devices (USB) port |
Specifications |
USB 2.0 specification – Type C connector (Device side) |
|
|
Transmission speed |
Up to 12 Mbps |
||
|
Transmission distance |
Up to 2 meters |
||
2-2-3 IO Coupler Dimensional Drawing

▲Front view dimension diagram of IO Coupler

▲Side view dimension diagram of IO Coupler
2-3 End Module
2-3-1 Specifications and Functions of End Module
Please connect to the far right of the IO Coupler series expansion module or special expansion module.
When using branch modules, the End Module must also be installed on the far-right side. Failure to connect may result in errors and abnormal operation.

▲Three-dimensional view of the End Module
2-4 Management
This chapter will introduce how to connect to the IO Coupler and how to set the IO Coupler.
2-4-1 Connection Method
Click the Search button. Software will search according to the currently selected USB or Ethernet and individual network cards in the “Management Window” If Ethernet is selected, it will search all network cards. Additionally, a search menu will appear below the search button, allowing users to choose between USB or Ethernet for Coupler search. Once the search is completed, the results will be displayed in the management window.

▲Search Coupler
※Notice: UperIO can only connect to one IO Coupler at a time, and only one connection method can be used at a time.
※Notice: When using Ethernet for connection, UperIO can only connect to one IO Coupler per network card.
Right-clicking the tree diagram of USB or Ethernet and individual network cards will bring up a search menu. Clicking on the menu will initiate the search. If selecting Ethernet, it will search all network cards.

▲Network Scan
The search results will be displayed in the Coupler management window. User can right-click to connect or left-click on the target Coupler to connect.

▲Coupler Connection
2-4-2 Coupler Settings
Double-clicking the Coupler icon with the left mouse button will open the Coupler setting page. This section will use MC0EN as an example.

▲Coupler Connection
a. General Setting

▲Coupler Setting Window
|
Category |
Function |
Explanation |
|
Parameter |
Device Name |
Display the module name of the Coupler, which cannot be modified. |
|
Device Description |
User-defined Name |
|
|
Client Idle Timeout Setting |
Enable/Disable |
Enable or Disable Client Idle Timeout |
|
Client Timeout (seconds) |
Set the time that automatically disconnected from the client, if no messages are received from them, in seconds. |
|
|
IP Setting |
IP Acquisition Mode |
Set the IP acquisition mode, which includes Static and DHCP modes. |
|
IP Address |
Setting of Internet Address. |
|
|
Subnet Mask |
Setting of Subnet Mask |
|
|
Default Gateway |
Defaulted Setting of Gateway |
|
|
Primary DNS Server |
Preferred DNS server setting |
|
|
Secondary DNS Server |
Other DNS server setting |
|
|
Mac address |
Display Mac address |
|
|
Firmware |
Firmware Version |
Display Firmware version |
|
Update |
Upgrade Firmware |
▲General setting of Coupler
b. Access Rights
Access rights can restrict the connection IP of the client side. To prevent unauthorized users from stealing data. Double-click the blank field or right-click to add authorized connection IPs and ranges.

▲Setting of Coupler Access Rights
c. Security
Set a password for protection. If a password is set, it must be entered before connecting to change the settings of the Coupler and its expansion modules. This prevents malicious individuals from altering related settings. To remove an existing password, simply enter the old password during modification and leave the new password field blank.

▲Setting of Coupler Security
d. Service Ports Number

▲Setting of Coupler Service Port Number
|
Category |
Function |
Explanation |
Detail Introduction |
|
Fatek Protocol |
Primary Port |
Default Network Port Setting of Fatek Protocol |
Ethernet Communication Port for Downloading Projects |
|
Secondary Port |
Default Network Port Setting of Fatek Protocol |
Ethernet Network Communication Port for Project Download |
|
|
Modbus Protocol |
Primary Port |
Default Network Port Setting of Modbus Protocol |
Selected this communication port when connecting to the Human-Machine Interface |
|
Secondary Port |
Default Network Port Setting of Modbus Protocol |
Selected this communication port when connecting to the Human-Machine Interface |
|
|
|
|
▲UperIO Parameter Setting for Downloading |
▲Human-Machine Modbus Connection Settings for the Coupler |
▲Explanation of Service Port Setting
2-4-3 Backup
Users can backup the configuration and settings of the current or project file’s expansion modules to the coupler. In the future, when an expansion module needs to be repaired, after replacing the module, there is no need to reconfigure it. The coupler will directly import the backed-up expansion module settings into the new module.

a. Save as Project
Clicking ‘Save as Project’ allows the current configuration of the coupler to be saved as a project on the computer. In the future, you can use the UperIO software to open the project directly, modify the configuration settings, and download the project to the coupler.
b. Backup Current Expansion Module Configuration
Backup the configuration and settings of the currently connected modules to the coupler. This makes it convenient for future repairs of expansion modules, where the replacement can be done directly without the need for reconfiguration. The coupler will directly import the backed-up expansion module settings into the new module.
c. Backup Expansion Modules in the Project
Backup the project that already includes the configuration of expansion modules to the coupler. This makes it convenient for future configuration on-site, as you can first save the configuration and settings of the expansion modules to the coupler. When the coupler is connected to the expansion modules, the settings of the expansion modules will be imported directly.

▲Backup Coupler Options
2-5 Hardware Installation and Wiring
This section introduces the assembly of the power module and IO Coupler, as well as the method for installing the mounting rail and wiring.
2-5-1 Installation
When connecting each module, please ensure that the power is disconnected and observe safety precautions.

|
⚠ Attention |
|
The End module must be installed on the last module on the far right side at all times. |
Installation Position
Orientation: When installed inside the cabinet, the front panel of the CPU module must be horizontally facing forward.

▲Module Installation Position Diagram
Clearance between Modules and Surroundings
IO COUPLERs are mounted vertically in a forward position, allowing for natural air convection cooling. Ensure there is a gap of at least 50mm above and below the IO Coupler for heat dissipation, as illustrated in the diagram below:

▲Installation Gap Diagram
When the ambient temperature exceeds the working environment, consider methods such as forced air cooling or increasing the gap between the device and its surroundings to improve ventilation and reduce temperature. When using expansion modules, to mitigate heat effects, maintain a gap of at least 50mm between the upper and lower modules.
a. Module Assembly
IO Coupler and modules are interconnected with each other. Below, we’ll illustrate how to assemble the IO Coupler and power module as an example.
1. Release the side sliders located on the top and bottom of the right-hand module.
Place your fingers on the protruding part of the side slider and slide it towards yourself, which means sliding towards the front of the module, to put the module in the installation state.

2. Insert the hooks of the right module into the hooks of the left module by pushing them to the left.
Align the left and right modules to keep them parallel, ensuring that the connectors on both sides are properly aligned for connection.
3. Lock the side sliders on the top and bottom of the right module.
Place your fingers on the protruding part of the side slider and push outward, away from yourself, towards the back of the module. This action locks the module in place.

4. Finally, install the End module at the far right end of the row of modules.

|
⚠Attention |
|
Please make sure to securely use the side sliders to correctly fix the adjacent modules. If not properly fixed, it may cause looseness in the connection between modules, leading to abnormal operation of the PLC. After fixing, please test with your hand to ensure the connection is stable. |
b. Securing DIN Rail
This section will explain how to install connected modules onto the D I N rail and how to remove them.
Installing onto the D I N rail

1. Hook the upper groove of the D I N rail onto the upper mounting hook of each module.
2. Use a flat-head screwdriver to push the bottom mounting hook to the pulled-out position until you hear a “click” sound. Then, press the module against the D I N rail until it is snug, and push the bottom mounting hook back to the inserted position.

In difficult installation scenarios, please remove all side sliders first. Once installed on the D I N rail, proceed with locking by reattaching the side sliders.

Check whether the bottom mounting hook of the lower D I N rail is in the inserted (locked) position.

Removal procedure
1. Use a flat-head screwdriver to flip the bottom mounting hooks to the unlocked position.
2. Following the reverse order of installation, remove the D I N rail from the modules.
c. Panel Assembly Precautions
When the IO Coupler is installed inside a control panel, it is essential to provide an appropriate operating environment.
Temperature control

The environmental temperature within the control cabinet must be maintained within the range of 0°C to 55°C.
■ If necessary, the following methods can be adopted to maintain the appropriate temperature.
■ Provide sufficient space to ensure good air circulation.
■ Avoid installing the IO Coupler near devices that generate high heat, such as heaters, transformers, or high-power resistors.
■ If the environmental temperature exceeds 55°C, install cooling fans or air conditioning.
Operation and Maintenance
■ Try to isolate the IO Coupler from high-voltage equipment and power machinery as much as possible to ensure the safety of operation and maintenance tasks.
■ Ideally, install the IO Coupler at a height of 1.0 to 1.6 meters above the ground, as this is most suitable for setting up and operating the IO Coupler.
Enhance the anti-interference performance
When laying communication cables externally, consider the following points.
■ When using multi-core signal cable, do not route I/O lines together with other control cables within the same cable.
■ If a parallel layout is adopted, ensure there is a minimum gap of 300mm between wiring racks.
■ If it’s necessary to lay I/O wiring and power cables in the same cable tray or conduit, use grounded metal barriers or shielding between the cables for isolation.

▲Suggested wiring diagram for interference immunity
2-5-2 Wiring
Wiring precautions
|
⚠ Attention |
|
|
Please ensure that installation or wiring operations are not performed while the power is on, as this may result in electric shock to the operator or damage to the product. |
|
|
Ensure that the grounding symbol marked on the equipment is properly grounded to effectively prevent electric shock and equipment interference, which may lead to incorrect operation of the product. When wiring peripherals to the IO Coupler, make sure to confirm whether the product specifications match the selected IO Coupler. Peripherals that do not match may encounter risks such as terminal configuration mismatch, mismatched power supply, inability to drive the device, or wiring short circuits causing fires and equipment damage. It is essential to ensure that there are no foreign objects such as iron filings or wiring residues in each module. These foreign objects may cause fires, damage, or operational errors. |
|
※ Grounding
(1) It is necessary to use the correct independent grounding method.
(2) Please use a cable with a cross-sectional area greater than or equal to 2mm for grounding.
(3) Place the grounding point close to the IO Coupler and firmly secure the grounding cable.
a. Power Wiring
Power Supply Precautions
1. Please separate the power cords of the power supply module from those of other devices. If there is significant noise, consider adding an isolation transformer.
2. AC 110V, 220V, and DC 24V cables should be routed separately as much as possible. Power cables should be tightly twisted to prevent interference. They should also be connected to the modules with shorter lengths.
3. Do not bundle AC 110V, 220V, and DC 24V cables with the main circuit (high voltage and high current) or I/O signal lines and avoid placing these cables close to each other. If possible, keep these cables separated by at least 100mm.
4. To prevent surges caused by lightning strikes, install surge absorbers as shown in the diagram below.
※ Precautions
1. Separate the ground connected to the surge absorber from the ground of the IO Coupler system.
2. Select a surge absorber with an operating voltage not lower than the maximum allowable input voltage.
b. AC Power Wiring

▲AC Power Circuit
1. Connect the FG (⏚) of the power module to the earth of the power supply as a reference ground to prevent abnormalities in the system.
2. The AC power line L and N are respectively connected to the L and N of the power module.
3. For AC input, the following should be noted:
The AC power input voltage has a wide range (100~240VAC). Connect the power supply to the L and N ends. If AC110V or AC220V is connected to the +24V and -24V input terminals, it will damage the IO Coupler. Users should pay special attention to this.
Use a wire with a diameter of 2mm or more for the grounding terminal of the power supply.
4. The DC power supply of the power module is for the power output side. Do not parallel it with other power supplies.
c. DC Wiring
1. The Remote IO series IO Coupler can be directly powered on via an external 24V DC power supply, as shown in the diagram below. Connect the 3-pin European standard wiring terminal plug to the power socket on the left side of the IO Coupler.

▲DC Power Supply position
2. When connecting the DC power supply, be sure to ensure correct polarity connection to avoid damaging the equipment. Please follow the correct wiring as shown in the diagram below.

▲DC Power Supply Terminals
※ Precautions
1. Separate grounding should be used; if separate grounding is not possible, please use common grounding. However, the length of the wires must be the same in this case.
2. Be sure to ground the FG terminal to avoid noise interference.


▲Grounding Recommendation Diagram
※This termination switch is reserved for future expansion and has no function at present.