This chapter will introduce how to open, save projects, and some related settings, allowing users to quickly understand how to use them
6-1 Create Project
6-1-1 Create a New Project
To create a new project for editing controller programs. First, use the mouse to click on 〔File〕 at the top left corner of UperIO. →〔Open New Project〕


▲Open New Project
After clicking〔Create a New Project〕, the following window appear. Set the project name and the model of the coupler, then click〔OK〕 to open the new project.

▲Create New Project
|
Function |
Explanation |
|
Project Name |
Please define a name for this project for easier management the file in the future. |
|
Series |
According to corresponding series from the drop-down menu and choose the one based on the actual series used. |
|
Model |
Based on the drop-down menu, select the corresponding model based on the actual machine type used. The program will automatically display the specifications and descriptions of this model below. |
▲Settings for Creating a New Project
6-1-2 Project Editing
Click on〔Hardware Configuration〕to enter editing mode. In the toolbox on the right, you can select modules and drag them onto the main module of the coupler. During the dragging process, the expected position for configuration will appear in yellow, as shown in the figure below. When dragging a module behind the current module, it will automatically be placed at the end of the module. Double-clicking a module in the toolbox will also automatically add the module to the end of the currently configured modules.
▲Project Editing

Users can also drag and adjust the position of newly added modules themselves to accommodate the actual configuration of the coupler.
6-1-3 Project Download
This feature allows users to download the Coupler project planned with UperIO to the Coupler for execution.
※Notice: The project download function can only be executed when the software is offline.
6-1-4 Download Parameter Settings
Clicking on “Download Parameter” will show the user with options for Ethernet and USB connection methods.

▲Download Parameter Settings
|
Function |
Explanation |
|
Network Connection |
Select the desired network interface card. |
|
Information of Network Connection |
Display current network interface card information. |
|
Type |
Network Communication Protocol |
|
IP Address |
Coupler IP |
|
Search |
Search for the network address of the existing Coupler on the network. |
|
Port |
Coupler port |
▲Explanation of Download Parameter Setting
Users can adjust the connection parameters themselves on the advanced settings page.

▲Advanced Settings for Download Parameters
Clicking on USB will display the currently connected Couplers via USB for the user to select.

▲USB Project Download Settings
Click on “Connection Test” in the bottom left corner allows you to perform a connection test to confirm if the connection is normal.
6-1-5 Download Project
Click on Download to compare the current open project with the project in the coupler.

▲Download Project
When the file is matching, it will show[The current project is same as the device.]

▲Matching Prompt
When the file is not matching, it will show the comparison window. Allow user to select which project to download.

▲Coupler is Not Matching with Project
After clicking “Download,” the download process will begin and continue until the progress window is completed.

▲Download Completed
6-1-6 Open Old Project
Click〔File〕 in the top left corner→〔Open Project〕, you can open previously edited projects。

6-1-7 Save Project
Click〔File〕 in the top left corner→〔Save Project〕, you can use this function to save the edited project to the disk.

6-1-8 Save As Project
Click〔File〕 in the top left corner→〔Save as project〕when the opened project has been edited, you can save the edited project as another project name to the disk.

6-1-9 Close Project
Click〔File〕 in the top left corner→〔Close Project〕, the project will be closed.

6-1-10 Quit
Click〔File〕 in the top left corner→〔Quit〕,close UperlO software.

6-2 View
This section will introduce the method of quickly and easily configuring the IO Coupler application with the same configuration using images, and setting the corresponding information. Detailed explanations are provided in the following sections.
6-2-1 Examples of Module Configuration
Display

▲Module Display

▲Function Bar_View
|
Function |
Description |
|
Auto Fit |
Automatically scale the module to the appropriate position. |
|
Decive Dimension |
The dimensions of the device will be indicated. |
|
Select Info |
Information about the selected device, such as ID, firmware version, hardware version, serial number, and description, will be displayed. |
|
Device Monitor |
The status of the selected module will be shown on the right side. |
|
Power Consumption |
Calculate the current power consumption of all extension components. |
|
Mapping Table |
Query the current IO mapping to Modbus TCP and Ethernet/IP locations. |
▲Function Bar_View Description
6-2-2 Decice Dimension
Click on the function bar [View] → [Device Dimension], and the dimensions of each module will be displayed on the screen, as shown in the figure below:

▲Device Dimension
6-2-3 Module Information
Click on the function bar [View] → [Select Info], then left-click on the module you want to view, and the information of the selected module, such as version number, terminal point count, remarks, etc., will be displayed, as shown in the figure below:

▲Module Info
6-2-4 Device Monitor
Click on the function bar [View] → [Device Monitor], and the device monitoring window will appear on the right side:

▲Device Monitor
In the information section, you can select the resources you want to display, such as [Digital Data], [Logic Data], [Status Data].
a. Digital Data
Click [Digital Data D] in the information section above [Device Monitor], and only digital data will be displayed in the module list. When you hover the mouse over the value, if the switch appears blue as shown in the figure below, you can directly modify the switch of that register.

▲Digital Data in Device Monitor
b. Logic Data
Click [Logic Data A] in the information section above [Device Monitor], and only logical data will be displayed in the module list. When you hover the mouse over the value, if the data appears blue as shown in the figure below, you can modify the value of that register. You can also quickly change the value display format using [Dec] and [Hex] on the right side of the register.

▲Logic Data in Device Monitor
c. Status Data
Click [Status Data S] in the information section above [Device Monitor], and only status data will be displayed in the module list. When the data appears gray as shown in the figure below, the value of that register cannot be modified. However, you can still quickly change the value display format using [Dec] and [Hex] on the right side of the register.

▲Status Data in Device Monitor
6-2-5 Power Consumption
Click on the function bar [View] → [Power Consumption], and a power consumption calculation window will appear in the lower right corner, as shown in the figure below:

▲Power Consumption
|
Function |
Description |
|
Module |
Select the currently used power module. |
|
Power Supply |
The amount of electricity provided by this power module. |
|
Usage |
Display the total electricity consumption of all current modules. |
|
External |
Display the total electricity expected to be provided by external power sources. |
|
Power Remain |
The remaining electricity after deducting the supplied electricity from the power module. |
▲Power Consumption Description
Some modules, like the M04DA shown in the diagram, require additional power supply. Users can decide whether to power them from the host or use an external power source.
If you choose to use an external power supply, clicking on will set the power source to external and recalculate the current power requirement. This is shown in the figure below:


▲External Power Supply
6-2-6 Module Settings
Double-clicking on the expansion component with the left mouse button will bring up the corresponding module’s settings window.

▲Module Settings
While each module’s equipment information may differ slightly in terms of names and descriptions, the displayed information is the same. The following diagram uses M04AD as an example to introduce the relevant content of equipment information.

▲Device Info(M04AD)
|
Information |
Description |
|
Model Name |
The name of this module, which is a factory setting and cannot be edited. |
|
ID |
Automatically displays the current number of this module based on the device’s overall sorting. |
|
Description |
The functional description of this module, which is a factory setting and cannot be edited. |
|
Frimware Version |
You can click the upgrade button on the right to upgrade the firmware of all existing modules in the IO Coupler. This function can only be used in [Management].
|
|
Hardware Version |
The current hardware version of this module, which is a factory setting and cannot be edited. |
|
Serial Number |
The current serial number of this module, which is a factory setting and cannot be edited. |
▲Device Info
The configuration settings for each module will display the corresponding parameter content. The following will mainly use M04AD as an example to explain how to operate the configuration settings.
Users can enable or disable the corresponding channels and modify detailed parameters. For detailed parameter definitions, please refer to the relevant manual.

▲Configuration (M04AD)
When in the [Management], the AI and AO modules have calibration functions. The following will use M04AD as an example to introduce this process.

▲Module Calibration management (M04AD)
Clicking on the [Calibration] option in the [Configuration Settings] section at the bottom will open the calibration window for the corresponding module. First, select the channel you want to calibrate on the left side, then choose the desired settings in the calibration settings, and follow the corresponding steps to complete the calibration.
At the bottom left of the module, there are options for export and import, allowing users to quickly export and import pre-configured settings.

▲Module Settings Export and Import
Copy and Paste
In the configuration settings, right-clicking on the [Channel] allows you to perform functions such as copy, paste, and restore.

▲Right-click functions for channels
|
Function |
Description |
|
Reset to Default |
Restore all current settings of the channel to the initial default values. |
|
Copy |
Copy all settings of the currently selected channel. |
|
Paste |
Paste the previously copied channel settings. |
▲Right-click function description
Tip: press ← → to switch chapters, Ctrl+K to search