2.1 FBS-PLC MemoryAllocation

Remark:

DISCRETE

X(256)

X255

SRAM

X0

Save status

FBS-PACK

X0

1. When the Read Only Register (ROR)

X255

has been configured by the user, the

Y(256)

Y0

Y0

contents of R5000~R8071 (depends

Y255

Y255

T(256)

T0

T0

on the quantity of configuration) will

T255

C0

T255

C0

be loaded from the ROR’s during

C(256)

STATUS

TR(40)

C255

S0

Load status

C255

S0

each time of power up or changing

AREA

from STOP to RUN mode.

(4096)

S(1000)

M(2002)

S999

M0

S999

M0

The user can access the ROR through

the corresponding R5000~R8071.

Write operation of function

instructions are prohibited in this

REGISTER

T(256)

M2001

T0

Save Register

M2001

T0

ROR area of corresponding R5000~

C(256)

T255

T255

R8071. The others of R5000~R8071

C0

C0

C255

C255

that have not been configured for

R0

R0

R(3840)

ROR, they can work as general

R3839

R3839

purpose registers.

2.There is a dedicated area of program

D0

D0

memory to store the contentsof

AREA

D(4096)

D4095

Load Register

D4095

Read Only Register.

(20040W)

IR , OR

R3840

R3840

ROR can be configured up to 3072

SR(328)

R4167

R4167

words in maximum.

R or ROR

R5000

R5000

(3072)

F0

F0

F(8192)

F8191 F8191

LADDER LADDER

PROGRAM PROGRAM

(20KW) (20KW)

Save Program

LADDER

LABEL

Load Program

LABEL

PROGRAM

(1KW)

(1KW)

AREA

(32KW)

ROR ROR

(3KW) (3KW)

DOC DOC

(8KW) (8KW)

Memory Buffer in PLC PP/Winproladder

2.2Digital and Register Allocations

〝*〞is default, user configurable

Item

Range

Remarks

X

Input contact (DI)

X0~X255 (256)

Corresponding to external digital input

Y

Output relay (DO)

Y0~Y255 (256)

Corresponding to external digital output

TR

Temporary relay

TR0~TR39 (40)

M

Internal
relay

Non-retentive

M0~M799 (800)*

Can be configured as retentive type

M1400~M1911 (512)

Retentive

M800~M1399 (600)*

Can be configured as non-retentive type

Special Relay

M1912~M2001 (90)

S

Step
Relay

Non-Retentive

S0~S499 (500)*

S20~S499 can be configured as retentive type

Retentive

S500~S999 (500)*

Can be configured as non-retentive type

T

Timer “Time-Up” status contact

T0~T255 (256)

C

Counter “Counter-Up” status contact

C0~C255 (256)

TMR

Time current
value register

0.01STime Base

T0~T49 (50)*

T0~T255 numbers for each time base can be adjusted.

0.1S Time Base

T50~T199 (150)*

1S Time Base

T200~T255 (56)*

CTR

Counter current value register

Retentive

C0~C139 (140)*

Can be configured as non-retentive type

Non-Retentive

C140~C199 (60)*

Can be configured as retentive type

Retentive

C200~C239 (40)*

Can be configured as non-retentive type

Non-Retentive

C240~C255 (16)*

Can be configured as retentive type

HR
DR

Data
Register

Retentive

R0~R2999 (3000)*

Can be configured as non-retentive type

D0~D3999 (4000)

Non-Retentive

R3000~R3839 (840)*

Can be configured as retentive type

HR
ROR

Retentive

R5000~R8071 (3072) *

When not configured as ROR, it can serve normal register (for read/write)

Read Only
Register (ROR)

R5000~R8071 can be set as ROR ~ default setting is (0)*

ROR is stored in special ROR area and not occupy program space

File Register

F0~F8191 (8192)

Save/retrieved via dedicated instruction

IR

Input Register

R3840~R3903 (64)

Corresponding to external numeric input

OR

Output Register

R3904~R3967 (64)

Corresponding to external numeric output

SR

Special system register

R3968~R4167 (197) D4000~D4095 (96)

0.1 mS High-Speed Timer Register

R4152~R4154 (3)

HSC
Registers

Hardware (4sets)

DR4096~DR4110 (4×4)

Software(4sets)

DR4112~DR4126 (4×4)

Calendar Registers

Minute

Second

R4129

R4128

Day

Hour

R4131

R4130

Year

Month

R4133

R4132

Week

R4134

FR

File Registers

F0~F8191(8192)

XR

Index Registers

V,Z (2)、P0~P9 (10)

Remark: During power up or changing operation mode from STOP→RUN, all contents in non-retentive relays or registers will be cleared to 0; the retentive relays or registers will remain the same state as before.

2.3Special Relay Details

Relay No.

Function

Description

1. Stop, Prohibited Control

M1912

M1913

M2001

Emergency Stop control

Disable external outputs control

Disable/Enable status retentive control

y If 1, PLC will be stopped (but not enter STOP mode) and all outputs OFF.

This bit will be cleared when power up or changing operation mode from STOP→RUN.

y All external outputs are turn off but the
status of Y0~Y255 inside the PLC will not be affected.

yIf M2001 is 0 or enabled, the Disable/Enable status of all contacts will be reset to enable during power up or changing operation mode from STOP→RUN.

yIf M2001 is disabled and force ON, the Disable/Enable status & ON/OFF state of all contacts will remain as before during power up or changing operation mode from STOP→RUN.

While testing, it may disable and force ON M2001 to keep the ON/OFF state of disabled contacts, but don’t forget to enable the M2001 after testing.

2. CLEAR Control

M1914
M1915
M1916
M1917
M1918

M1919

Clear Non-Retentive Relays Clear Retentive Relays
Clear Non-Retentive Registers Clear Retentive Registers
Master Control (MC) Selection

Function output control

y Cleared When at 1
y Cleared When at 1
y Cleared When at 1
y Cleared When at 1
y If 0, the pulse activated functions within the master control loop will only be executed once at first 0→1 of master control loop.

If 1, the pulse activated functions within the master control loop will be executed every time while changing 0→1 of master control loop.

yIf 0, the functional outputs of some function instructions will memory the output state, even these instructions not been executed.

If 1, the functional output of some function instructions without the memory ability.

※ M1918/M1919 can be set to 0 or 1 at will around the whole program to meet the control requirements.

Relay No.

Function

Description

3. Pulse Signals

◤M1920

0.01S Clock pulse

c

c

T(M1920)=0.01S

◤M1921

0.1S Clock pulse

◤M1922

1S Clock pulse

◤M1923

60S Clock pulse

T(M1921)=0.1S

T(M1922)=1S

◤M1924

Initial pulse (first scan) d

T(M1923)=60S

◤M1925

Scan clock pulses e

d

◤M1926

=0, PLC is working at STOP mode

e

t is the scan time

=1, PLC is working at RUN mode

◤M1927

CTS input status of communication

y 0:CTS True (ON)

y 1:CTS False (OFF)

port 1

y When communication port 1 is used to connect with the printer

or modem, it can use this signal and a timer to detect whether the printer or the modem is ready.

4. Error Messages

◤M1928

Reserved

y 1: Indicating no expansion unit or exceed the limit on number of

◤M1929

Reserved

◤M1930

No expansion unit or exceed the limit

◤M1931

on number of I/O points

I/O points

Immediate I/O not in the main unit

y 1: Indicating that Immediate I/O not in the main unit range and

◤M1932

range

the main unit cannot RUN

Unused

◤M1933

System stack error

y 1: Indicating that system stack error

◤M1934

│Reserved

◤M1935

5.Port3~Port4 Controls(MC/MN)

M1936

Port 3 busy indicator

y 0:Port 3 Busy

y 1:Port 3 Ready

M1937

Port 3 finished indicator

y 1:Port 3 finished all communication transactions

M1938

Port 4 busy indicator

y 0:Port 4 Busy

y 1:Port 4 Ready

M1939

Port 4 finished indicator

y 1:Port 4 finished all communication transactions

Relay No.

Function

Description

6. HSC0~HSC1 Controls (MC/MN)

M1940
M1941
M1942
M1943
M1944
M1945
M1946
M1947
M1948
M1949
M1950
M1951

HSC0 software Mask
HSC0 software Clear
HSC0 software Direction
Reserved
Reserved
Reserved
HSC1 software Mask
HSC1software Clear
HSC1 software Direction
Reserved
Port 3 communication indicator Port 4 communication indicator

y 1: Mask
y 1: Clear
y 0: Count-up, 1: Count-down

y 1: Mask
y 1: Clear
y 0: Count-up, 1: Count-down

y 1: Port 3 has received and transmitted a message y 1: Port 4 has received and transmitted a message

7. RTC Controls

M1952
M1953
◤M1954 ◤M1955

RTC setting
±30 second Adjustment

RTC installation checking

Set value error

8. Communication/Timing/Counting Controls

M1956

M1957

M1958

M1959

M1960

M1961

M1962

M1963

M1964

Selection of Message Frame Interval Detection Time

The CV value control after the timer "Time Up"

Communication port 2 High Speed Link mode selection

Modem dialing signal selection

Port 1 busy indicator

Port 1 finished indicator Port 2 busy indicator

Port 2 finished indicator Modem dialing control

y 0 :Use system default value as Message Frame Interval Detection Time for Modbus RTU communication protocol y 1:Use the high byte value of R4148 as Message Frame Interval Detection Time for Modbus RTU protocol
y 0: The CV value will continue timing until the upper limit is met after “Time Up”
y 1: The CV value will stop at the PV value after “Time Up” (User may control M1957 within the program to control the individual timer )
y 0: Set Port 2 to Normal Speed Link
y 1: Set Port 2 to High Speed CPU Link
※M1958 is only effective at slave station
y 0: Dialing by TONE when Port 1 connecting with Modem.

y 1: Dialing by PULSE when Port 1 connecting wit Modem.

y 0:Port 1 Busy
y 1:Port 1 Ready
y 1:Port 1 finished all communication transactions y 0:Port 2 Busy
y 1:Port 2 Ready
y 1:Port 2 finished all communication transactions y If Port 1 is connected with Modem,
when signal 0→1 will dial the phone number; when signal 1→0 will hang-up the phone.

Relay No.

Function

Description

M1965

M1966

M1967

M1968

M1969

M1970

M1971

M1972

M1973

M1974

M1975

Dialing success flag

Dialing fail flag

Port 2 High Speed Link working

mode selection

Step program status

Indirect addressing illegal write flag

Port 0 status

Port 1 status

Port 2 status

The CV value control after counting

“Count-Up”

RAMP function slope control

CAM function (FUN112) selection

y 1: Indicating that dialing is successful (when Port 1 is connected with Modem).

y 1: Indicating that dialing has failed (when Port 1 is connected with Modem).

y 0: Continuous cycle.

y 1: One cycle only. It will stop when the last communication transaction is completed (only effective at the master station).

y 1: Indicating that there are more than 16 active steps in the step program at the same time.

y 1: Indicating that a function with index addressing attempts to write cross over the boundary of different type of data.

y 1: Port 0 has received and transmitted a message

y 1: Port1 has received and transmitted a message

y 1: Port2 has received and transmitted a message

y 0: Indicating that the CV value will continue counting up to the upper limit after “Time-Up”.

y 1: Indicating that the CV value will stop at the PV value after “Count-Up”(User may control M1973 within the program to control the individual counter)

y 0: Time control for ramping

y 1: Equivalent slope control for ramping

y 1: For the circular applications where the electric CAM switch (FUN112) can support the wrap around situation like the angle from 359° cross to 0°

9. HSC2~HSC7 Controls

M1976
M1977
M1978
M1979
M1980
M1981
M1982

HSC2 software Mask
HSC2 software Clear
HSC2 software Direction HSC3 software Mask
HSC3 software Clear
HSC3 software Direction HSC4 software Mask

y 1: Mask
y 1: Clear
y 0: Count-up, 1: Count-down
y 1: Mask
y 1: Clear
y 0: Count-up, 1: Count-down
y 1: Mask

M1983
M1984
M1985
M1986
M1987
M1988
M1989
M1990

HSC4 software Direction HSC5 software MASK HSC5 software Direction HSC6 software Mask
HSC6 software Direction HSC7 software Mask
HSC7 software Direction Reserved

y 0: Count-up, 1: Count-down
y 1: Mask
y 0: Count-up, 1: Count-down
y 1: Mask
y 0: Count-up, 1: Count-down
y 1: Mask
y 0: Count-up, 1: Count-down

Relay No.

Function

Description

10. PSO0~POS3 Controls

M1991

M1992

M1993

M1994

M1995

Selection of stopping the pulse output

(FUN140)

PSO0 Busy indicator

PSO1 Busy indicator

PSO2 Busy indicator

PSO3 Busy indicator

y 0:Immediately stop while stopping pulse output y 1:Slow down stop while stopping pulse output y 0:PSO0 Busy
y 1:PSO0 Ready
y 0:PSO1 Busy
y 1:PSO1 Ready

y 0:PSO2 Busy
y 1:PSO2 Ready
y 0:PSO3 Busy
y 1:PSO3 Ready

M1996
M1997
M1998
M1999
M2000

PSO0 Finished indicator
PSO1 Finished indicator
PSO2 Finished indicator
PSO3 Finished indicator
Selection of Multi-Axis
synchronization for High Speed Pulse Output (FUN140)

y 1:PSO0 finished the last step of motion y 1:PSO1 finished the last step of motion y 1:PSO2 finished the last step of motion y 1:PSO3 finished the last step of motion y 1: Synchronized Multi-Axis

2.4 Special Registers Details

Register No.

Function

Description

R3840
│
R3903

Input Registers
CH0 : R3840

││
CH63 : R3903

For Analog or Numeric inputs

R3904
│
R3967

Output Registers
CH0 : R3904

││
CH63 : R3967

For Analog or Numeric outputs

R3968
│
R3980

Define stimulate Modbus equipment

R3981
│
R3999

Reserved

R4000

Reserved

R4001

Reserved

R4002

Reserved

R4003
│
R4004

Define FUN86 temperature reading value at starting/end address

Register No.

Function

Description

R4005

High Byte:Period of PWM
=0, 2 seconds
=1, 4 seconds
=2, 8 seconds
=3, 1 second
=4, 16 seconds
≥5, 32 seconds
Low Byte:Period of PID calculation =0, 2 seconds
=1, 4 seconds
=2, 8 seconds
=3, 1 second
=4, 16 seconds
≥5, 32 seconds

For PID temperature control

R4006

Threshold value of output ratio for
heating/cooling loop abnormal detecting (Unit in %)

For PID temperature control

R4007

Threshold value of continuous time for
heating/cooling loop abnormal detecting (Unit in second)

For PID temperature control

R4008

Maximum temperature for heating loop abnormal detecting

For PID temperature control

R4009

Temperature display in Celsius/Fahrenheit

=0, Celsius ;=1,Fahrenhelt

R4010
│
R4011

Installed temperature sensor flag

Each bit represents 1 sensor, if bit value = 1 means installed.

R4012
│
R4013

PID Temperature control flag

Each bit represents 1 temperature point, if bit value = 1 means enable control.

R4014

Reserved

R4015

Averaging of temperature value =0, no average on temperature =1, average by two readings =2, average by four readings =3, average by eight readings

R4016

Reserved

R4017

Reserved

R4018

Reserved

R4019

Number of PASSWORD Retry

R4020

Control FUN148 instruction forbid to clockwise/anti-clockwise.

R4021
│
R4024

Reserved

R4025

Total Expansion Input Registers

Register No.

Function

Description

R4026
R4027
R4028

Total Expansion Output Registers Total Expansion Digital Inputs
Total Expansion Digital Outputs

R4029

Reserved for system

R4030
│
R4039

Tables to save or read back the data registers into or from ROM Pack

When the ROM Pack being used to save the ladder program and data registers, these tables describes which registers will be written into the ROM Pack. The addressed registers will be initialized from ROM Pack while power up.

R4040

Reply delay time settings for Port 0 and Port 1

Low Byte:For Port 0 (Unit in mS) High Byte:For Port 1 (Unit in mS)

R4041

Reply delay time settings for Port 2 and Port 3

Low Byte:For Port 2 (Unit in mS) High Byte:For Port 3 (Unit in mS)

R4042

Reply delay time settings for Port 4

Low Byte:For Port 4 (Unit in mS) High Byte:Reserved for system

R4043

Port 3 Communication Parameters Register

Set Baud Rate, Data bit…of Port 3

R4044

Port 4 Communication Parameters Register

Set Baud Rate, Data bit…of Port 4

R4045

Transmission Delay & Receive Time-out interval time Setting,

while Port 3 being used as the master of

FUN151 or FUN150

Low Byte:Port 3 Receive Time-out interval time (Unit in 10mS)

High Byte:Port 3 Transmission Delay

(Unit in 10mS)

R4046

Power up initialization mode selection of data registers that has been written into ROM
Pack.

=5530H: Don’t initialize the addressed data registers been written into ROM Pack while power up =Others : initialize the addressed data registers been written into ROM Pack while power up

R4047

Communication protocol setting for Port1~Port4

Set the FATEK or Modbus RTU/ASCII communication protocol

R4048

Transmission Delay & Receive Time-out interval time Setting,

while Port 4 being used as the master of

FUN151 or FUN150

Low Byte:Port 4 Receive Time-out interval time (Unit in 10mS)

High Byte:Port 4 Transmission Delay

(Unit in 10mS)

R4049

CPU Status Indication

=A55AH, Force CPU RUN
=0, Normal Stop
=1, Function(s) existed that CPU does not support =2, PLC ID not matched with Program ID
=3, Ladder checksum error
=4, System STACK error
=5, Watch-Dog error
=6, Immediate I/O over the CPU limitation
=7, Syntax not OK
=8, Qty of expansion I/O modules exceeds
=9, Qty of expansion I/O points exceeds
=10, CRC error of system FLASH ROM

R4050

Port 0 Communication Parameters Register

Set Baud Rate of Port 0

R4051

Reserved

R4052

Indicator while writing ROM Pack

Register No.

Function

Description

R4053

Reserved

R4054

Define the master station number of the High-Speed CPU Link network (FUN151 Mode 3)

If the master station number is 1,it can ignore this register.

To set the master station number other than 1 should:

Low Byte : Station number
High Byte: 55H

R4055

PLC station number

y If high byte is not equal 55H, R4055 will show the station number of this PLC

y If want to set PLC station number then R4055 should set to:

Low Byte : Station number

High Byte: 55H

R4056

High Byte :Reserved
Low Byte: High speed pulse output frequency dynamic control

Low Byte: =5AH, can dynamically change the output frequency of High Speed Pulse Output

R4057

Power off counter

The value will be increased by 1 while power up

R4058

Error station number while Port 2 in High Speed CPU Link

Used by FUN151 Mode 3 of Port 2

R4059

Error code while Port 2 in High Speed CPU LINK mode

Used by FUN151 Mode 3 of Port 2 High byte Low Byte

R4059

Err code

Err count

H

Error code: 0AH, No response 01H, Framing Error 02H, Over-Run Error 04H, Parity Error
08H, CRC Error

Register No.

Function

Description

R4060

R4061
R4062
R4063

Error code of PSO 0

Error code of PSO 1
Error code of PSO 2
Error code of PSO 3

The error codes are:
1: Parameter 0 error
2: Parameter 1 error
3: Parameter 2 error
4: Parameter 3 error
5: Parameter 4 error
7: Parameter 6 error
8: Parameter 7 error
9: Parameter 8 error
10: Parameter 9 error
13:Parameter 12 error
15:Parameter 14 error
30: Speed setting reference number error
31: Speed value error
32: Stroke setting reference number error
33: Stroke value error
34: Illegal positioning program
35: Step over
36: Step number exceeds 255
37: Highest frequency error
38: Idle frequency error
39: Movement compensation value too large 40: Movement value exceeds range
41: DRVC instruction not allow ABS addressing 42:DRVZ can’t follow DRVC
50:Illegal operation mode of DRVZ
51:Illegal DOG input number
52:Illegal PG0 input number
53:Illegal CLR output number
60: Illegal linear interpolation command
Same as above

Same as above

Same as above

R4064
R4065
R4066
R4067

Being completed step number of positioning program

PSO 0
PSO 1
PSO 2
PSO 3

R4068
R4069

FUN147 GP0 vector speed

R4070
R4071

FUN147GP1 vector speed

Register No.

Function

Description

R4072
R4073
R4074
R4075
R4076
R4077
R4078
R4079

Pulse count remaining for output

Low Word of PSO 0
High Word of PSO 0
Low Word of PSO 1
High Word of PSO 1
Low Word of PSO 2
High Word of PSO 2
Low Word of PSO 3
High Word of PSO 3

R4080
R4081
R4082
R4083
R4084
R4085
R4086
R4087

Current output frequency

Low Word of PSO 0
High Word of PSO 0
Low Word of PSO 1
High Word of PSO 1
Low Word of PSO 2
High Word of PSO 2
Low Word of PSO 3
High Word of PSO 3

R4088
R4089
R4090
R4091
R4092
R4093
R4094
R4095

Current pulse position

Low Word of PSO 0
High Word of PSO 0
Low Word of PSO 1
High Word of PSO 1
Low Word of PSO 2
High Word of PSO 2
Low Word of PSO 3
High Word of PSO 3

Register No.

Function

Description

R4096
R4097
R4098
R4099
R4100
R4101
R4102
R4103
R4104
R4105
R4106
R4107
R4108
R4109
R4110
R4111
R4112
R4113
R4114
R4115
R4116
R4117
R4118
R4119
R4120
R4121
R4122
R4123
R4124
R4125
R4126
R4127

HSC0 current value Low Word HSC0 current value High Word HSC0 preset value Low Word HSC0 preset value High Word HSC1 current value Low Word HSC1 current value High Word HSC1 preset value Low Word HSC1 preset value High Word HSC2 current value Low Word HSC2 current value High Word HSC2 preset value Low Word HSC2 preset value High Word HSC3 current value Low Word HSC3 current value High Word HSC3 preset value Low Word HSC3 preset value High Word HSC4 current value Low Word HSC4 current value High Word HSC4 preset value Low Word HSC4 preset value High Word HSC5 current value Low Word HSC5 current value High Word HSC5 preset value Low Word HSC5 preset value High Word HSC6 current value Low Word HSC6 current value High Word HSC6 preset value Low Word HSC6 preset value High Word HSC7 current value Low Word HSC7 current value High Word HSC7 preset value Low Word HSC7 preset value High Word

R4128

Second of calendar

R4129

Minute of calendar

R4130

Hour of calendar

R4131

Day of calendar

R4132

Month of calendar

R4133

Year of calendar

R4134

Day of week of calendar

R4135

month 十 minute

◤ R4136 ◤ R4137 ◤ R4138

Current scan time
Maximum scan time
Minimum scan time

y Error < ±1ms
y Re-calculate when PLC changes from STOP to RUN

Register No.

Function

Description

R4139

CPU Status

Bit0 =0, PLC STOP
=1, PLC RUN
Bit1 , Reserved
Bit2 =1, Ladder program checksum error Bit3 =0, Without ROM Pack
=1, With ROM Pack
Bit4 =1, Watch-Dog error
Bit5 =1, MA model main unit
Bit6 =1, With ID protection
Bit7 =1, Emergency stop
Bit8 =1, Immediate I/O over range
Bit9 =1, System STACK error
Bit10 =1, ASIC failed
Bit11 =1, Function not allowed
Bit12 , Reserved
Bit13 =1, With communication board
Bit14 =1, With calendar
Bit15 =1, MC main unit

R4140
R4141
R4142
R4143
R4144
R4145

Telephone Number registers

Register No.

Function

Description

R4146

Port 1 Communication Parameters Register

Set Baud Rate, Data bit… of Port 1

R4147

Transmission Delay & Receive Time-out interval time Setting,

while Port 1 being used as the master of

FUN151 or FUN150

Low Byte:Port 1 Receive Time-out interval time (Unit in 10mS)

High Byte:Port 1 Transmission Delay

(Unit in 10mS)

Register No.

Function

Description

R4148

Message Frame Detection Time Interval

.While the communication port being used as the master or slave of Modbus RTU protocol, the system will give the default time interval to identify each packet of receiving message; except this, the user can set this time interval through the high byte setting of R4148 and let M1956 be 1, to avoid the overlap of different packet of message frame.

M1956=1, High Byte of R4148 is used to set the new message detection time interval for Port 1~Port 4 (Unit in mS)

.While the communication port being used to communicate with the intelligent peripherals through FUN151
instruction, if the communication protocol without the end of text to separate each packet of message frame, it needs message detection time interval to identify the different packet. High byte of R4148 is used for this setting for Port 1~Port 4.

(Unit in mS)

R4149

Modem Interface Setting & Port0
without checking of station number for FATEK’s external communication protocol

y High Byte of R4149:
=55H, Remote-Diagnosis/Remote-CPU-Link by way of Port 1 through Modem
connection, it supports user
program controlled dial up function

=AAH, Remote diagnosis by way of Port 1 through Modem connection, it
supports Passive receiving & Active dialing operation mode

=Others, without above function

y Low Byte of R4149:
=1, Port 0 without checking of station number for FATEK’s external
communication protocol (communicating with MMI/SCADA)

=Others, Port 0 checks station number, it allows multi-drop network for data acquisition.

R4150

Power on I/O service delay time setting

y PLC is ready for I/O service after this delay time while power up. The unit is in 0.01S. The default value is 100.

R4151

Circular 1mS time base timer

y The content of R4151 will be increased by 1 every 1mS. It can be used for a more precise timing application.

R4152

Low word of HSTA CV register

HSTA is high speed timer in 0.1 mS resolution

R4153

High word of HSTA CV register

The HSTA can act as 32-bit cyclic timer or fixed time interrupt timer

R4154

PV register of HSTA

Register No.

Function

Description

R4155

Port 1 & Port 2 without station number checking for FATEK’s external
communication protocol

y Low Byte of R4155:
=1, Port 1 without station number
checking for FATEK’s external communication protocol
(communicating with MMI/SCADA)

≠1,Port 1 checks station number, it allows multi-drop network for data acquisition

y High Byte of R4155:
=1, Port 2 without station number
checking for FATEK’s external
communication protocol
(communicating with MMI/SCADA)
≠1,Port 2 checks station number, it allows multi-drop network for data acquisition

R4156

Port 3 & Port 4 without station number checking for FATEK’s external
communication protocol

y Low Byte of R4156:
=1, Port 3 without station number
checking for FATEK’s external communication protocol
(communicating with MMI/SCADA)

≠1,Port 3 checks station number, it allows multi-drop network for data acquisition

y High Byte of R4156:
=1, Port 4 without station number
checking for FATEK’s external communication protocol
(communicating with MMI/SCADA)

≠1,Port 4 checks station number, it allows multi-drop network for data acquisition

R4157

PLC OS Version

R4158

Port 2 Communication Parameters Register
(Not for High Speed CPU Link)

Set Baud Rate, Data bit…of Port 2

R4159

Transmission Delay & Receive Time-out interval time Setting,

while Port 2 being used as the master of

FUN151 or FUN150

Low Byte:Port 2 Receive Time-out interval time (Unit in 10mS)

High Byte:Port 2 Transmission Delay

(Unit in 10mS)

R4160

Port2 RX/TX time out setting for High Speed CPU Link

High Byte of R4160 :
=56H, User setting mode if the system default works not well, Low Byte of R4160 is used for this setting (Not suggest)
=Others, system will give the default value according to the setting of R4161

R4161

Port 2 Communication Parameters Register
(For High Speed CPU Link)

ySet Baud Rate, Parity…of Port 2 y Data bit is fixed to 8-bit
y Baud Rate≧38400 bps

R4162

Fixed time interrupt enable/disable

B7

B6

B5

B4

B3

B2

B1

B0

control

100mS50mS10mS5mS 4mS 3mS 2mS1mS

Bit=0, interrupt enabled

Bit=1, interrupt disabled

Register No.

Function

Description

R4163

Modem dialing control setting

y Low Byte of R4163 :

=1, Ignore the dialing tone and the busy tone when
dialing.

=2, Wait the dialing tone but ignore the busy tone when
dialing.

=3, Ignore the dialing tone but detect the busy tone
when dialing.

=4, Wait the dialing tone and detect the busy tone when
dialing.

=Any other value treated as value equal 4.

y High Byte of R4163 :
The Ring count setting for Modem auto answer

R4164

V index register

R4165

Z index register

R4166

System used

R4167

Model of main unit

y Low Byte of R4167:

=0, 6I + 4O (FBs-10xx)
=1, 8I + 6O (FBs-14xx)
=2, 12I + 😯 (FBs-20xx)
=3, 14I + 10O (FBs-24xx)
=4, 20I + 12O (FBs-32xx)
=5, 24I + 16O (FBs-40xx)
=6, 36I + 24O (FBs-60xx)
=7, 28I + 16O (FBs-44MN)
y High Byte of R4167:
=0, MA
=1, MC
=2, MN

Register No. Function

Description

D4000

Port 1 User-defined Baud Rate Divisor

Port 1 user-defined Baud Rate (1125~1152000 bps) D4000 = (18432000/Baud Rate) – 1

(R4146 must be 56XFH)

D4001

Port 2 User-defined Baud Rate Divisor

Port 2 user-defined Baud Rate (1125~1152000 bps) D4001 = (18432000/Baud Rate) – 1

(R4158 must be 56XFH)

D4002

Port 3 User-defined Baud Rate Divisor

Port 3 user-defined Baud Rate (1125~1152000 bps) D4002 = (18432000/Baud Rate) – 1

(R4043 must be 56XFH)

D4003

Port 4 User-defined Baud Rate Divisor

Port 4 user-defined Baud Rate (1125~1152000 bps) D4003 = (18432000/Baud Rate) – 1

(R4044 must be 56XFH)

D4004
FUN30 PID resolution of analog input

=0, 14-bit format but valid 12-bit resolution =1,14-bit format and valid 14-bit resolution

D4005

FUN30 PID gain constant

KC=D4005/Pb

Register No.

Function

Description

D4006
│
D4042

Analog input valid bit and set times of average

D4043
│
D4045

Communication function setting

D4046
│
D4052

Reserved

D4053
D4054

RTC chip
RTC time setup

RTC chip is S35390A, is able through D4054 to do time setup

D4055
│
D4059

Reserved

D4060
D4061
D4062

D4063

FUN147 GP0 error code
FUN147 GP1 error code
FUN147 the step number (positioning point) which has been completed of GP0
FUN147 the step number (positioning point) which has been completed of GP1

D4064
│
D4070

Reserved

D4071
│
D4079

Used in FBs-B2A1D/FBs-B2DA/ FBs-B4AD

D4080 D4081 D4082 D4083 D4084 D4085 D4086 D4087 D4088 D4089

P0 index register
P1 index register
P2 index register
P3 index register
P4 index register
P5 index register
P6 index register
P7 index register
P8 index register
P9 index register

D4090
│
D4095

Reserved

Remark: All the special relays or registers attached with “◤” symbol shown in the above table are write prohibited. For the special relays attached with “◤” symbol also has following characteristics
. Forced and Enable/Disable operation is not allowed.

. Can’t be referenced by TU/TD transitional contact (contact will always open)