  • This configuration is the factory setting

Category

Specification

Notes

BIT

X

Digital Input (DI)

(Maximum 2048 points)

X0~X1023 (1024)

Corresponding to external digital input

Y

Digital Output (DO)

(Maximum 2048 points)

Y0~Y1023 (1024)

Corresponding to external digital input

TR

Temporary relay

TR0~TR31(32)

(Reserved by the system)

M

Internal relay

M0~M9119 (9120)

M0~M9119 can be planned as retentive or non-retentive relays.

Special relay

M9120~M25599 (16480)

S

Stepping relay

S0~S3103 (3104)

S0~S3103 can be planned as retentive or non-retentive relays.

T

Timer relay

T0~T1023 (1024)

C

Counter relay

C0~C1279 (1280)

WORD

TMR

Timer present value register

0.01S time base

T0~T255 (256) *

T0~T1023 can flexibly plan the number of each time base

0.1S time base

T256~T511 (256) *

1S time base

T512~T1023 (512) *

CTR

Counter present value register

16

BIT

C0~C1023 (1024)

Can be planned as retentive or non-retentive relays.

32

BIT

C024~C1279 (256)

Can be planned as retentive or non-retentive relays.

HR

DR

Data register

Retentive

R0~R14999 (15000)

* Note: Can be planned non-retentive relays.
D0~D7999 (8000)

Non-Retentive

R15000~R34767 (19768)

HR

ROR

Retentive

R43224~R47319 (4096) * Note:

When it is not planned as ROR, it can be used as a general register

Read only register

(ROR)

R43224~R47319 Can be planned as read only register, factory setting is 0*

Stored in the ROR area, does not occupy the program capacity

File register

F0~F65535(65536)

* Note: Requires access through dedicated instruction

IR

Input register (AI)

R34768~R34895 (128)

Corresponds to external analog input

OR

Output register (AO)

R35024~R35151 (128)

Corresponds to external analog output

SR

System special register

R35280~R43223 (7944)

Special Register

0.1ms timer HST register

R35451~R35466(16)

1ms timer HST register

R35435~R35442(8)

10ms timer LTM register

R35443~R35450(8)

0.1ms timing HSTA loop count

DR35467

High-speed counter register

R35280~R35311(32)

RTC register

R35312

(sec)

R35313 (min)

R35314 (h)

R35315

(day)

R35316

(month)

R35317 (year)

R35318 (week)

R35319

(h+min)

FR

File register

F0~F65535(65536)

XR

Index register

V: R43214

Z: R43216

P0~P9 :

R43194, R43196, R43198, R43200, R43202, R43204, R43206, R43208, R43210, R43212

Table 92 M-Series PLC memory