5.1 Manipulating Parameters(Pn▯▯▯)

This section describes the classifications, notation, and setting methods for the parameters given in this manual.

5.1.1 Parameter Classification
There are the following two types of servo driver parameters.

Classification

Meaning

Setup Parameters

Parameters for the basic settings that are required for operation.

Tuning Parameters

Parameters that are used to adjust servo performance.

NOTE: When you edit parameters with a Panel Operator or Digital Operator, only setup parameters are displayed by default. To edit tuning parameters, set Pn00B to n.▯▯▯1 (Display all parameters).

Parameter

Meaning

When
Enabled

Classification

Pn00B

n.▯▯▯0 [default
setting]

Display only setup parameters.

After restart

Setup

n.▯▯▯1

Display all parameters.

5.1.2 Notation for Parameters
There are two types of notations used for parameters that depend on whether the parameter requires a numeric setting (parameter for numeric setting) or requires the selection of a function (parameter for selecting a function).

5.1.3 Parameter Setting Methods

You can use the Protuner or the Panel Operator to set parameters.

5.1.4 Write Protection Setting for Parameters

You can prohibit writing parameters from the Panel Operator or the Digital Operator. Even if you do, you will still be able to change parameter settings from the Protuner.

5.1.5 Initializing Parameter Settings

You can return the parameters to their default settings.

This function will not initialize the settings of the parameters that are adjusted for the FA00C, FA00D, FA00E, and FA00F utility functions.

To enable the new settings, turn the power supply to the servo driver OFF and ON again after you complete the operation.

Preparations

Always check the following before you initialize the parameter settings. • The parameters must not be write prohibited.
• The servo must be OFF.

Applicable Tools
The following table lists the tools that you can use to initialize the parameter settings.

Too

FA No./Function Name

Reference

Panel Operator

FA005

ParameterSetup Initialize Parameters(FA005)

ProTuner

[Edit Parameters ] - [Parameter Restore factory values]

5.2 The EtherCAT of Communication Specification

The EtherCAT communication setting setup by Servo Parameter Pn013.

5.2.1 The Setting of EtherCAT Station Address

Pn013

EtherCAT Station Address

Speed Position Torque

Setup Range

Setup Unit

default setting

When Enabled

Classification

0000〜FFFF

—

1

After restart

Setup

5.3 Power Supply Type Settings for the Main Circuit and Control Circuit

A servo driver with a 220-VAC power supply input can be operated on either an AC power supply input or DC power supply input to the main and control circuits. If you select an AC power supply input, you can operate the servo driver on either a single-phase power supply input or a three-phase power supply input. This section describes the settings related to the power supplies.

5.3.1 AC Power Supply Input/DC Power Supply Input Setting

Set Pn001 = n.▯X ▯▯ (Main Circuit Power Supply AC/DC Input Selection) to specify whether to use an AC or DC power supply input for the main circuit power supply to the servo driver.

If the setting of Pn001 = n.▯X ▯▯ does not agree with the actual power supply input, an A.330 alarm (Main Circuit Power Supply Wiring Error) will occur.

Example: Examples of When an A.330 Alarm (Main Circuit Power Supply Wiring Error) Occurs
● A DC power supply is connected between the B1/ and 2 terminals, but an AC power supply input is specified (Pn001 = n.▯0 ▯▯).

● An AC power supply is input to the L1, L2, and L3 terminals, but a DC power supply is specified (Pn001 = n.▯1 ▯▯).

Parameter

Meaning

When Enabled

Classification

Pn001

n.▯0▯▯
[default setting]

Use an AC power supply input.

After restart

Setup

n.▯1▯▯

Use a DC power supply input.

WARNING

●Connect the AC or DC power supplies to the specified servo driver terminals.

• Connect an AC power supply to the L1, L2, and L3 terminals and the L1C and L2C terminals on the servo driver.

• Connect a DC power supply to the B1/ and 2 terminals and the L1C and L2C terminals on the servo driver.

There is a risk of failure or fire.

●Always specify a DC power supply input (Pn001 = n.▯1 ▯▯) before you input DC power for the main circuit power supply.

If you input DC power without specifying a DC power supply input (i.e., without setting Pn001 to n.▯1 ▯▯), the servo driver’s internal elements may burn and may cause fire or damage to the equipment.

●With a DC power supply input, time is required to discharge electricity after the main power supply is turned OFF. A high residual voltage may remain in the servo driver after the power supply is turned OFF. Be careful not to get an electric shock.

●Install fuses on the power supply line if you use DC power.

●The Servomotor returns regenerative energy to the power supply. If you use a servo driver with a DC power supply input, regenerative energy is not processed. Process the regenera-tive energy at the power supply.

5.3.2 Single-phase AC Power Supply Input/Three-phase AC Power Supply Input Setting

If you use a single-phase, 220-VAC power supply input for the servo driver’s main circuit power supply, set parameter Pn00B to n.▯1 ▯▯ (Use a three-phase power supply input as a single-phase power supply input).

This restriction does not affect the SC3 03A model.

Parameter

Meaning

When Enabled

Classification

Pn00B

n.▯0▯▯
[default setting]

Use a three-phase power supply input.

After restart

Setup

n.▯1▯▯

Use a three-phase power supply input as a single-phase power supply input.

1. If you use a single-phase power supply input without specifying a single-phase AC power supply (Pn00B = n.▯1▯▯), an A.F10 alarm (Power Supply Line Open Phase) will occur.

2. Not all Servo driver can be run on a single-phase AC power supply input. If you connect a single-phase AC

power supply input to a servo driver that does not support single-phase power, an A.F10 alarm (Power Supply Line Open Phase) will occur.

3. If you use a single-phase 220AC power supply input, the torque-motor speed characteristic of the Servomotor will not be the same as for a three-phase AC power supply input. Decide whether to use a single-phase or three-phase AC power supply input after checking the characteristics given in the Servomotor manual or catalog.

5.4 Functions and Settings for the /S-ON (Servo ON) Signal

The /S-ON (Servo ON) signal is used to enable Servomotor operation. This section describes the function of and settings for the /S-ON signal.

5.4.1 Function of the /S-ON (Servo ON) Signal

Type

Signal

Connector Pin No.

Signal Status

Function

Input

/S-ON

Must be allocated

ON (closed)

Power is supplied to the Servomotor to enable operation.

OFF (open)

Power supply to the Servomotor is stopped and operation is disabled.

You can use Pn50A = n.▯▯X ▯ (/S-ON (Servo ON) Signal Allocation) to allocate the /S-ON signal to a different input signal terminal.

1. Always input the /S-ON signal before you input a speed, position, or torque reference to start the Servomotor. Never input the reference first and then use the /S-ON signal or turn ON the AC power supply to start the Servomotor. Doing so will degrade internal elements and may cause an accident.

2. Input the /S-ON signal while the Servomotor is stopped. You cannot turn ON the servo while the Servomotor is operating.

5.4.2 Setting to Keep the Servo ON and Supply Power to the Motor Continuously (For Pulses Type)

You can set Pn50A = n.▯▯X ▯ (/S-ON (Servo ON) Signal Allocation) to 9 (The signal is always active) to keep the servo ON and supply power to the motor continuously.

Parameter

Meaning

When Enabled

Classification

Pn50A

n.▯▯0▯
[default setting]

he S-ON signal is active when CN1-40 input signal is ON (closed).

After restart

Setup

n.▯▯9▯

The signal is always active.

(The /S-ON signal is always active.)

1. If you set this parameter to keep the servo ON continuously, power will be supplied to the motor as soon the main circuit power supply to the servo driver is turned ON. If there is already a speed, position, or torque reference input, the Servomotor or machine may perform unexpected operation. Always implement safety measures.

2. If a resettable alarm occurs and operation is disabled (power is not supplied to the motor), operation will be automatically enabled (power will be supplied to the motor) when the alarm is reset. If you set this parameter to keep the servo ON continuously, the Servomotor or machine may perform unexpected operation when an alarm is reset.

5.5 Motor Direction Setting

You can reverse the direction of Servomotor rotation by changing the setting of Pn000 = n.▯▯▯X (Rotation Direction Selection) without changing the polarity of the speed or position reference.

This causes the rotation direction of the Servomotor to change, but the polarity of the signals, such as encoder output pulses, output from the servo driver do not change. Set the appropriate direction for your system. The default setting for forward rotation is counterclockwise (CCW) as viewed from the load end of the Servomotor.

Parameter

Forward/Reve rse
Reference

Motor Direction and Encoder Divided Pulse Outputs

Applicable Overtravel Signal (OT)

Pn00 0

n.▯▯▯0
Use CCW as the forward direction.

(Default
setting

Forward
reference

P-OT (For- ward Drive Prohibit)
signal

Reverse
reference

N-OT
(Reverse Drive Prohibit)
signal

n.▯▯▯1
Use CW as the forward direc-tion.

(Reverse Rota-tion Mode)

Forward
reference

P-OT (For- ward Drive Prohibit)
signal

反Reverse reference

N-OT
(Reverse Drive Prohibit)
signal

5.6 Overtravel and Related Settings

Overtravel is a function of the servo driver that forces the Servomotor to stop in response to a signal input from a limit switch that is activated when a moving part of the machine exceeds the safe range of movement.

The overtravel signals include the P-OT (Forward Drive Prohibit) and the N-OT (Reverse Drive Prohibit) signals.

You use the P-OT and N-OT signals to stop the machine by installing limit switches at the positions where you want to stop the machine that is operated by the Servomotor. A servo driver wiring example is provided below.

Using the overtravel function is not necessary for rotating applications such as rotary tables and conveyors. No wiring for

overtravel input signals is required. This section describes the parameters settings related to overtravel.

CAUTION

● To prevent accidents that may result from contact faults or disconnections, use normally closed limit switches.

Do not change the default settings of the polarity of the overtravel signals (P-OT and N-OT).

● If you use a Servomotor for a vertical axis, the /BK (Brake) signal will remain ON (i.e., the brake will be released) when overtravel occurs. This may result in the workpiece falling when overtravel occurs. To prevent the workpiece from falling, set Pn001 to n.▯▯1 ▯ to place the Servomotor in a zero-clamped state when it stops.

● A base block state is entered after stopping for overtravel. This may cause the Servomotor to be pushed back by an external force on the load shaft. To prevent the Servomotor from being pushed back, set Pn001 to n.▯▯1 ▯ to place the Servomotor in a zero-clamped state when it stops.

5.6.1 Overtravel Signals

The overtravel signals include the P-OT (Forward Drive Prohibit) and the N-OT (Reverse Drive Prohibit) signals.

Type

Signal

Connector Pin No.

Signal
Status

Meaning

Input

P-OT

CN1-IN2

ON

Forward drive is enabled (actual operation).

OFF

Forward drive is prohibited
(forward overtravel).

N-0T

CN1-IN3

ON

Reverse drive is enabled (actual operation).

OFF

Reverse drive is prohibited
(reverse overtravel).

You can operate the Servomotor in the opposite direction during overtravel by inputting a reference.。

5.6.2 Setting to Enable/Disable Overtravel

You can use Pn50A = n.X ▯▯▯ (P-OT (Forward Drive Prohibit) Signal Allocation) and Pn50B = n.▯▯▯X (N-OT (Reverse Drive Prohibit) Signal Allocation) to enable and disable the overtravel function.

You do not need to wire the overtravel input signals if you are not going to use the overtravel function.

Parameter

Meaning

When Enabled

Classification

Pn50A

n. 2▯▯▯
[default setting]

The forward overtravel function is enabled and the P-OT (Forward Drive Prohibit) signal is input from CN1-CN0. (CN1-IN1 For Pulses Type )

After restart

Setup

n. 8▯▯▯

The forward overtravel function is disabled. Forward drive is always enabled.

Pn50B

n.▯▯▯3
[default setting

The reverse overtravel function is enabled
and the N-OT (Reverse Drive Prohibit) signal is input from CN1-CN1.(CN1-IN2 For Pulses Type )

After restart

Setup

n.▯▯▯8

The reverse overtravel function is disabled. Reverse drive is always enabled.

5.6.3 Motor Stopping Method for Overtravel

You can set the stopping method of the Servomotor when overtravel occurs in Pn001 = n.▯▯XX (Motor Stopping Method for Servo OFF and Group 1 Alarms and Overtravel Stopping Method).

Parameter

Motor Stopping Method*

Status after Stopping

When Enabled

Classification

Pn001

n.▯▯00 [default
setting]

Dynamic brake

Coasting

After restart

Setup

n.▯▯01

n.▯▯02

Coasting

n.▯▯1▯

Deceleration according to setting of Pn406

Zero clamp

n.▯▯2▯

Coasting

n.▯▯3▯

Deceleration according to setting of Pn30A

Zero clamp

n.▯▯4▯

Coasting

* You cannot decelerate a Servomotor to a stop during torque control. For torque control, the Servomotor will be stopped with the dynamic braking or coast to a stop (according to the setting of Pn001 = n.▯▯▯X (Motor Stopping Method for Servo OFF and Group 1 Alarms)), and then the Servomotor will enter a coasting state.

Stopping the Servomotor by Setting Emergency Stop Torque
To stop the Servomotor by setting emergency stop torque, set Pn406 (Emergency Stop Torque).If Pn001 = n.▯▯X ▯ is set to 1 or 2, the Servomotor will be decelerated to a stop using the torque set in Pn406 as the maximum torque. The default setting is 800%. This setting is large enough to allow you to operate the Servomotor at the maximum torque. However, the maximum emergency stop torque that you can actually use is the maximum torque of the Servomotor.

Pn406

Emergency Stop Torque

Speed Position Torque

Torque

Setting Range

Setting Unit

Default Setting

When Enabled

Classification

0〜800

1% *

800

Immediately

Setup

* Set a percentage of the motor rated torque.

Stopping the Servomotor by Setting the Deceleration Time

To specify the Servomotor deceleration time and use it to stop the Servomotor, set Pn30A (Deceleration Time for Servo OFF and Forced Stops).

Pn30A

Deceleration Time for Servo OFF and Forced Stops

Speed Position Torque

Setting Range

Setting Unit

Default Setting

When Enabled

Classification

0〜10000

1ms

0

Immediately

Setup

If you set Pn30A to 0, the Servomotor will be stopped with a zero speed.

The deceleration time that you set in Pn30A is the time to decelerate the Servomotor from the maximum motor speed.

5.6.4 Overtravel Warnings

You can set the system to detect an A.9A0 warning (Overtravel) if overtravel occurs while the servo is ON. This allows the servo driver to notify the host controller with a warning even when the overtravel signal is input only momentarily. An alarm occurs only if overtravel occurs while the servo is ON. An overtravel warning will not be detected when the servo is OFF, even if overtravel occurs.

• The occurrence of an A.9A0 warning will not stop the motor or have any affect on host controller motion

operations. The next step (e.g., the next motion or command) can be executed even if an overtravel warning exists.

However, depending on the processing specifications and programming for warnings in the host

controller, operation may be affected when an overtravel warning occurs (e.g., motion may stop or not stop). Confirm the specifications and programming in the host controller.

• When overtravel occurs, the servo driver will perform stop processing for overtravel. Therefore, when an A.9A0 warning occurs, the Servomotor may not reach the target position specified by the host controller. Check the feedback position to make sure that the axis is stopped at a safe position.

The following parameter is set for this function.

Parameter

Meaning

When
Enabled

Classificati on

Pn00D

n.0▯▯▯
[default setting]

Do not detect overtravel warnings.

restart

Setup

n.1▯▯▯

Detect overtravel warnings.

A timing chart for warning detection is provided below.

NOTE:
1. Warnings are detected for overtravel in the same direction as the reference.

2. Warnings are not detected for overtravel in the opposite direction from the reference. Example: A warning will not be output for a forward reference even if the N-OT signal turns ON.

3. A warning status can be detected in either the forward or reverse direction if there is no reference.

4. A warning status will not be detected when the servo is turned ON even if overtravel status exists.

5. A warning status is not related to Servo ON/Servo OFF or the overtravel signal status. It will be cleared by ALM_CLR. 6. When an overtravel warning status is triggered, it will not be triggered again until the it is cleared.

7. When the software limit is detected, An overtravel warning status will still be triggered.

5.7 Holding Brake

A holding brake is used to hold the position of the moving part of the machine when the servo driver is turned OFF

so that moving part does not move due to gravity or an external force. You can use the brake that is built into a

Servomotor with a Brake, or you can provide one on the machine.

The holding brake is used in the following cases.

The brake built into a Servomotor with a Brake is a de-energization brake. It is used only to hold the Servomotor and cannot be used for braking. Use the holding brake only to hold a Servomotor that is already stopped.

5.7.1 Brake Operating Sequence

You must consider the brake release delay time and the brake operation delay time to determine the brake operation timing, as described below.

Brake Release Delay Time
The time from when the /BK (Brake) signal is turned ON until the brake is actually released.

Brake Operation Delay Time
The time from when the /BK (Brake) signal is turned OFF until the brake actually operates.

*1. Rotary Servomotors: The brake delay times for Servomotors with Holding Brakes are given in the following
table. The operation delay times in the following table are examples for when the power supply is switched on the DC side. You must evaluate the actual brake delay times on the actual equipment before using the application.

*2. Before you output a reference from the host controller to the Servo Driver, wait for at least 50 ms plus the brake release delay time after you turn ON the /S-ON signal.

*3. Use the following parameters to set the timing of when the brake will operate and when the servo will be turned OFF. • Rotary Servomotors: Pn506 (Brake Reference-Servo OFF Delay Time), Pn507 (Brake Reference Output Speed Level), and Pn508 (Servo OFF-Brake Command Waiting Time)
• Linear Servomotors: Pn506 (Brake Reference-Servo OFF Delay Time), Pn508 (Servo OFF-Brake Command Waiting Time), and Pn583 (Brake Reference Output Speed Level)
*4. After the SV_ON command is sent, wait for the brake release time plus an additional 50ms then output the command that sent by the upper device to the servo driver.

*5. Please use the following parameters to set up the brake action and servo OFF time: Pn506(Brake command – Servo OFF delay time),
Pn507(Brake command output speed value),
Pn508(Servo OFF – Brake command wait time)

5.7.2 /BK (Brake) Signal

The following settings are for the output signal that controls the brake. The /BK (Brake) signal is not allocated by default. To use the brake, change the setting of Pn50F = n.▯X ▯▯ (/BK (Brake Output) Signal Allocation). The /BK signal is turned OFF (to operate the brake) when the servo is turned OFF or when an alarm is detected. You can adjust the timing of brake operation (i.e., the timing of turning OFF the /BK signal) with the servo OFF delay time (Pn506).

Type

Singal

Connecter Pin No.

Singal Status

Meaning

Output

/BK

Must be allocated

ON(Closed)

Relesases the brake

OFF(Open)

Activates the brake

NOTE: The /BK signal will remain ON during overtravel. The brake will not be applied.

Allocating the /BK (Brake) Signal

To use the brake, you must allocate an output signal for the /BK signal.

Set the allocation for the /BK signal in Pn50F = n.▯X ▯▯ (/BK (Brake Output) Signal Allocation).

Parameter

Connecter Pin No.

meaning

When
Enabled

Classificati on

Pn50F

n.▯0▯▯

CN1-7,8

The /BK Signal is output from CN1-OUT0

After
restart

setup

n.▯1▯▯

CN1-9,10

The /BK Signal is output from CN1-OUT1

n.▯2▯▯[default
setting]

CN1-11,12

The /BK Signal is output from CN1-OUT2

n.▯3▯▯

CN1-32,33

The /BK Signal is output from CN1-OUT3

n.▯4▯▯

CN1-34,35

The /BK Signal is output from CN1-OUT4

n.▯5▯▯

CN1-36,37

The /BK Signal is output from CN1-OUT5

n.▯6▯▯

—

The /BK Signal is not used

If you allocate more than one signal to the same output connector pin, a logical OR of the signals is output. Allocate the /BK signal to its own output connector pin, i.e., do not use the same output terminal for another signal.

For example, never allocate the /TGON (Rotation Detection) signal and /BK signal to the same output

connector pin. If you did so, the /TGON signal would be turned ON by the falling speed on a vertical axis, and the brake would not operate.

5.7.3 Output Timing of /BK (Brake) Signal When the Servomotor Is Stopped

When the Servomotor is stopped, the /BK signal turns OFF at the same time as the /S-ON signal turns OFF. Use the servo OFF delay time (Pn506) to change the timing to turn OFF power supply to the motor after the /S-ON signal turns OFF.

Pn506

Brake Reference-Servo OFF Delay Time

Speed Position Torque

Setting Range

Setting Unit

Default Setting

When Enabled

Classification

0〜50

1ms

0

Immediately

Setup

• When the Servomotor is used to control a vertical axis, the machine moving part may move slightly due to gravity or an external force. You can eliminate this slight motion by setting the servo OFF delay time (Pn506) so that power supply to the motor is stopped after the brake is applied.

• This parameter sets the timing of stopping power supply to the Servomotor while the Servomotor is stopped.

Power supply to the Servomotor will be stopped immediately when an alarm occurs, regardless of the setting of this parameter. The machine moving part may move due to gravity or an external force before the brake is applied.

5.7.4 Output Timing of /BK (Brake) Signal When the Servomotor Is Operating
If an alarm occurs while the Servomotor is operating, the Servomotor will start stopping and the /BK signal will be turned OFF. You can adjust the timing of /BK signal output by setting the brake reference output speed level (Rotary Servomotors: Pn507, Linear Servomotors: Pn583) and the Servo OFF-Brake Command Waiting Time (Pn508). NOTE: If zero-speed stopping is set as the stopping method for alarms, the setting of Pn506 (Brake Reference Servo OFF

Delay Time) is used after the motor stops.

Pn507

Brake Reference Output Speed Level

Speed Position Torque

Setting Range

Setting Unit

Default Setting

When Enabled

Classification

0〜10000

1min-1 (RPM)

100

Immediately

Setup

Pn508

Servo OFF-Brake Command Waiting Time

Speed Position Torque

Setting Range

Setting Unit

Default Setting

When Enabled

Classification

10〜100

10ms

50

Immediately

Setup

The brake operates when either of the following conditions is satisfied:

● When the Motor Speed Goes below the Level Set in Pn507 for a Rotary Servomotor or in Pn583 for a Linear

Servomotor after the Power Supply to the Motor Is Stopped
● When the Time Set In Pn508 Elapses after the Power Supply to the Motor Is Stopped

The Servomotor will be limited to its maximum speed even if the brake reference output speed level (Rotary Servomotor: Pn507, Linear Servomotor: Pn583) is higher than the maximum speed.

5.8 Motor Stopping Methods for Servo OFF and Alarms

You can use the following methods to stop the Servomotor when the servo is turned OFF or an alarm occurs. There are the following four stopping methods.

Motor Stopping Method

Meaning

Stopping by Applying the Dynamic Brake

The electric circuits are internally connected to stop the Servomotor quickly.

Coasting to a Stop

The motor stops naturally due to friction during operation.

Zero-speed Stopping

The speed reference is set to 0 to stop the Servomotor quickly.

Decelerating to a Stop

Emergency stop torque is used to decelerate the motor to a stop.

There are the following three conditions after stopping.

Status after Stopping

Meaning

Stopping by Applying the Dynamic Brake

The electric circuits are internally connected to hold the Servomotor.

Coasting

The servo driver does not control the Servomotor. (The machine will move in response to a force from the load.)

Zero Clamping

A position loop is created and the Servomotor remains stopped at a position reference of 0. (The current stop position is held.)

• The dynamic brake is used for emergency stops. The dynamic brake circuit will operate frequently if the power supply is turned ON and OFF or the servo is turned ON and OFF while areference input is applied to start and stop the Servomotor. This may result in deterioration of the internal elements in the servo

driver. Use speed input references or position references to start and stop the Servomotor.

• If the Servomotor must be stopped by coasting rather than with the dynamic brake when the main circuit power supply or the control power supply is turned OFF before the servo is turned OFF, use a servo driver with the dynamic brake option.

• To minimize the coasting distance of the Servomotor to come to a stop when an alarm occurs, zero-speed stopping is the default method for alarms to which it is applicable. However, depending on the
application, stopping with the dynamic brake may be more suitable than zero-speed stopping.

5.8.1 Stopping Method for Servo OFF

Set the stopping method for when the servo is turned OFF in Pn001 = n.▯▯▯X (Motor Stopping Method for Servo OFF and Group 1 Alarms).

Parameter

Servomotor
Stopping Method

Status after
Servomotor Stops

When
Enabled

Classificati on

Pn001

n.▯▯▯0 [default
setting]

Dynamic brake*

Dynamic brake*

After
restart

Setup

n.▯▯▯1

Coasting

n.▯▯▯2

Coasting

Coasting

NOTE: If Pn001 is set to n.▯▯▯0 (Stop the motor by applying the dynamic brake) and the Servomotor is stopped or operates at a low

speed, braking force may not be generated, just like it is not generated for coasting to a stop.

5.8.2 Servomotor Stopping Method for Alarms

There are two types of alarms, group 1 (Gr. 1) alarms and group 2 (Gr. 2) alarms. A different parameter is used to set the stopping method for alarms for each alarm type. Refer to the following section to see which alarms are in group 1 and which are in group 2.

Motor Stopping Method for Group 1 Alarms
When a group 1 alarm occurs, the Servomotor will stop according to the setting of Pn001 = n.▯▯▯X. The default setting is to stop by applying the dynamic brake.

Motor Stopping Method for Group 2 Alarms
When a group 2 alarm occurs, the Servomotor will stop according to the settings of the following three parameters. The default setting is for zero clamping.

• Pn001 = n.▯▯▯X (Motor Stopping Method for Servo OFF and Group 1 Alarms) • Pn00A = n.▯▯▯X (Motor Stopping Method for Group 2 Alarms)
• Pn00B = n.▯▯X ▯ (Motor Stopping Method for Group 2 Alarms)

However, during torque control, the group 1 stopping method is always used. If you set Pn00B to n.▯▯1 ▯ (Apply dynamic brake or coast Servomotor to a stop), you can use the same stopping method as group 1. If you are coordinating a number of Servomotors, you can use this stopping method to prevent machine damage that may result because of differences in the stopping method.

The following table shows the combinations of the parameter settings and the resulting stopping methods.

Parameter

ServomotorStoppin g Method

Status after
Servomotor stops

When
Enabled

Classificati on

Pn00B

Pn00A

Pn001

n.▯▯0▯[default
setting]

—

n.▯▯▯0 [default
setting]

Zero-speed stop- ping

Dynamic Brake

After
restart

Setup

n.▯▯▯1

Coasting

n.▯▯▯2

n.▯▯1▯

n.▯▯▯0 [default
setting]

Dynamic Brake

Dynamic Brake

n.▯▯▯1

Coasting

n.▯▯▯2

Coasting

n.▯▯2▯

n.▯▯▯0 [default
setting]

n.▯▯▯0 [default
setting]

Dynamic Brake

Dynamic Brake

n.▯▯▯1

Coasting

n.▯▯▯2

Coasting

n.▯▯▯1

n.▯▯▯0 [default
setting]

Motor is
decelerated using the torque set in Pn406 as the
maximum torque.

Dynamic Brake

n.▯▯▯1

Coasting

n.▯▯▯2

n.▯▯▯2

n.▯▯▯0 [default
setting]

Coasting

n.▯▯▯1

n.▯▯▯2

n.▯▯▯3

n.▯▯▯0 [default
setting]

Motor is
decelerated
according to setting of Pn30A.

Dynamic Brake

n.▯▯▯1

Coasting

n.▯▯▯2

n.▯▯▯4

n.▯▯▯0 [default
setting]

Coasting

n.▯▯▯1

n.▯▯▯2

NOTE: 1. The setting of Pn00A is ignored if Pn00B is set to n.▯▯0 ▯ or n.▯▯1 ▯.

2. The setting of Pn00A = n.▯▯▯X is enabled for position control and speed control. During torque control, the setting of Pn00A = n.▯▯▯X will be ignored and only the setting of Pn001 = n.▯▯▯X will be used.

5.9 Motor Overload Detection Level

The motor overload detection level is the threshold used to detect overload alarms and overload warnings when the Servomotor is subjected to a continuous load that exceeds the Servomotor ratings.

It is designed to prevent Servomotor overheating.

You can change the detection timing for A.910 warnings (Overload) and A.720 alarms (Continuous Overload). You cannot change the detection level for A.710 alarms (Instantaneous Overload).

5.9.1 Detection Timing for Overload Warnings (A.910)

With the default setting for overload warnings, an overload warning is detected in 20% of the time required to detect an overload alarm. You can change the time required to detect an overload warning by changing the setting of the overload warning level (Pn52B). You can increase safety by using overload warning detection as an overload protection function matched to the system.

The following graph shows an example of the detection of overload warnings when the overload warning level (Pn52B) is changed from 20% to 50%. An overload warning is detected in half of the time required to detect an overload alarm.

Pn52B

Overload Warning Level

Speed Position Torque

SetupRange

SetupUnit

default setting

When Enabled

Classification

0〜100

1%

20

immediately

Setup

5.9.2 Detection Timing for Overload Alarms (A.720)

If Servomotor heat dissipation is insufficient (e.g., if the heat sink is too small), you can lower the overload alarm detection level to help prevent overheating.

To reduce the overload alarm detection level, change the setting of Pn52C (Base Current Derating at Motor Overload Detection)

Pn52C

Base Current Derating at Motor Overload Detection

Speed Position Torque

Torque

SetupRange

SetupUnit

default setting

When Enabled

Classification

0〜100

1%

100

After restart

Setup

An A.720 alarm (Continuous Overload) can be detected earlier to protect the Servomotor from overloading.

Overload detection time

NOTE: The gray areas in the above graph show where A.710 and A.720 alarms occur.

5.10 Electronic Gear Settings

The minimum unit of the position data that is used to move a load is called the reference unit. The reference unit is used to give travel amounts, not in pulses, but rather in distances or other physical units (such as μm or °) that are easier to understand.

The electronic gear is used to convert the travel distances that are specified in reference units to pulses, which are required for actual movements.

With the electronic gear, one reference unit is equal to the workpiece travel distance per refer-ence pulse input to the servo driver. In other words, if you use the servo driver’s electronic gear, pulses can be read as reference units. NOTE: 1. If you set an electronic gear in the host controller, normally set the electronic gear ratio in the servo driver to 1:1. 2. If you enable reference pulse input multiplication switching, the reference unit is defined as the position data that is n times the reference pulses input from the host controller. (“n” is the reference pulse input multiplier.)

The difference between using and not using the electronic gear is shown below.

Electronic Gear Ratio Settings
Set the electronic gear ratio using Pn20E and Pn210.

Set the electronic gear ratio within the following range.

0.001 ≤ Electronic gear ratio (B/A) ≤ 64,000
If the electronic gear ratio is outside of this range, an A.040 alarm (Parameter Setting Error) will occur.

Pn20E

Electronic Gear Ratio (Numerator)

Speed Position Torque

SetupRange

SetupUnit

default setting

When Enabled

Classification

1~1073741824

1

1

After restart

Setup

Pn210

Electronic Gear Ratio (Denominator)

Speed Position Torque

SetupRange

SetupUnit

default setting

When Enabled

Classification

1~1073741824

1

1

After restart

Setup

Calculating the Settings for the Electronic Gear Ratio

If the gear ratio between the Servomotor shaft and the load is given as n/m, where n is the number of load rotations for m Servomotor shaft rotations, the settings for the electronic gear ratio can be calculated as follows:

B

=

Pn20E

=

×

m

Electronic gear ratio

A

Pn210

Travel distance per load shaft revolution (reference units)

n

5.10.1 Electronic Gear Ratio Setting Examples

Setting examples are provided in this section.

Step

Description

Machine Configuration

Ball Screw

Rotary Table

Belt and Pulley

1

Machine
Specifications

• Ball screw lead:6mm • Gear ratio:1/1

• Rotational angle per rev- olution:360°
• Gear ratio:1/100

• Pulley dia:100mm
(Pulley circumference:314mm)
•Gear ratio:1/50

2

Encoder Resolution

8388608(23 位)

8388608(23 位)

8388608(23 位)

3

Reference Unit

0.001 mm (1 µm)

0.01 mm (10 µm)

0.005 mm (5 µm)

4

Travel Distance per
Load Shaft Revolution (Reference Units)

6 mm/0.001 mm = 6000

360°/0.01° = 36000

314 mm/0.005 mm = 62800

5

Electronic Gear Ratio

B =

8388608

×

1

A

6000

1

B =

8388608 ×

100

A

36000

1

B =

8388608 ×

50

A

62800

1

6

Parameter

Pn20E:8388608

Pn20E:838860800

Pn20E:419430400

Pn210:6000

Pn210:36000

Pn210:62800

5.11 Resetting the Absolute Encoder

In a system that uses an absolute encoder, the multiturn data must be reset at startup. An alarm related to the absolute encoder (A.810 or A.820) will occur when the absolute encoder must be reset, such as when the power supply is turned ON.

When you reset the absolute encoder, the multiturn data is reset and any alarms related to the absolute encoder are cleared.

Reset the absolute encoder in the following cases
• When an A.810 alarm (Encoder Backup Alarm) occurs
• When an A.820 alarm (Encoder Checksum Alarm) occurs
• When starting the system for the first time
• When you want to reset the multiturn data in the absolute encoder

• When the Servomotor has been replaced

CAUTION

● The multiturn data will be reset to a value between -2 and +2 rotations when the absolute encoder is reset. The reference position of the machine system will change. Adjust the reference position in the host controller to the position that results from resetting the absolute encoder.

If the machine is started without adjusting the position in the host controller, unexpected operation may cause personal injury or damage to the machine.

NOTE: 1.The multiturn data will always be zero in the following cases. It is never necessary to reset the absolute encoder in these cases. An alarm related to the absolute encoder (A.810 or A.820) will not occur.

• When you use a single-turn absolute encoder
• When the encoder is set to be used as a single-turn absolute encoder (Pn002 = n.▯2 ▯▯)
2.If a batteryless absolute encoder is used, an A.810 alarm (Encoder Backup Alarm) will occur the first time the power is turned ON. After you reset the absolute encoder, the A.810 alarm will no longer occur.

5.11.1 Precautions on Resetting

• You cannot use the /ALM-RST (Alarm Reset) signal from the servo driver to clear the A.810 alarm (Encoder Backup Alarm) or the A.820 alarm (Encoder Checksum Alarm). Always use the operation to reset the absolute encoder to clear these alarms.

• If an A.8 ▯▯ alarm (Internal Encoder Monitoring Alarm) occurs, turn OFF the power supply to reset the alarm. Always check the following before you reset an absolute encoder.

• The parameters must not be write prohibited.

• The servo must be OFF.

5.11.2 Applicable Tools

The following table lists the tools that you can use to reset the absolute encoder

Tool

FA No./Function Name

Panel Operator

FA008

ProTuner

[Encoder Setting−Reset Absolute Encoder]

5.12 Setting the Regenerative Resistor Capacity

The regenerative resistor consumes regenerative energy that is generated by the Servomotor, e.g., when the Servomotor decelerates.

If an External Regenerative Resistor is connected, you must set Pn600 (Regenerative Resistor Capacity).

WARNING

• If you connect an External Regenerative Resistor, set Pn600 and Pn603 to suitable values.

If a suitable value is not set, A.320 alarms (Regenerative Overload) will not be detected correctly, and the External Regenerative Resistor may be damaged or personal injury or fire may
result.

• When you select an External Regenerative Resistor, make sure that it has a suitable capacity.

There is a risk of personal injury or fire.

Pn600

Regenerative Resistor Capacity

Speed Position Torque

SetupRange

SetupUnit

default setting

When Enabled

Classification

0~servo driver’s maximum applica-ble motor capacity

10W

0

immediately

Setup

Pn603

Regenerative Resistance

Speed Position Torque

SetupRange

SetupUnit

default setting

When Enabled

Classification

0~65535

10mΩ

0

immediately

Setup

Set the regenerative resistor capacity to a value that is consistent with the allowable capacity of the External Regenerative Resistor. The setting depends on the cooling conditions of the External Regenerative Resistor. • For self-cooling (natural convection cooling): Set the parameter to a maximum 20% of the capacity (W) of the actually installed regenerative resistor.

• For forced-air cooling: Set the parameter to a maximum 50% of the capacity (W) of the actually installed regenerative resistor.

For a self-cooling 100-W External Regenerative Resistor, set Pn600 to 2 (×10 W) (100 W × 20% = 20 W). NOTE: 1. An A.320 alarm will be displayed if the setting is not suitable.

2. The default setting of 0 specifies that the servo driver’s built-in regenerative resistor

• When an External Regenerative Resistor is used at the normal rated load ratio, the resistor temperature increases to between 200°C and 300°C. Always apply derating. Consult the manufacturer for the resistor’s load characteristics.。

• For safety, use an External Regenerative Resistor with a thermoswitch.